background image

20301852

58

DVBL7 Series Gas Fireplace

requirements for the Commonwealth of 
Massachusetts

This product must be installed by a licensed plumber or 
gas  fitter  when  installed  within  the  Commonwealth  of 
Massachusetts.

Note regarding Vented Products

Flex line installation must not exceed 36 inches and must 
have a T shutoff valve.
Any residence with a direct vent product must have a CO 
detector installed in the residence.
Installation of the fireplace or vented gas log in the State 
of Massachusetts requires the damper to be permanently 
removed or welded in the fully open position.
In addition, neither a naturally vented gas log nor a vent-
free product may be installed in a bedroom or bathroom in 
the State of Massachusetts.
All gas fitting and installation of this heater shall only be 
done by a licensed gas fitter or licensed plumber.
For all side wall horizontally vented gas fueled equipment 
installed  in  every  dwelling,  building  or  structure  used  in 
whole or in part for residential purposes, including those 
owned or operated by the Commonwealth and where the 
side wall exhaust vent termination is less than seven (7) feet 
above finished grade in the area of the venting, including but 
not limited to decks and porches, the following requirements 
shall be satisfied:

Installation of Carbon Monoxide Detectors

At the time of installation of the side wall horizontal vented 
gas fueled equipment, the installing plumber or gas fitter 
shall observe that a hard wired carbon monoxide detector 
with an alarm  is installed on each additional level of the 
dwelling,  building  or  structure  served  by  the  side  wall 
horizontal  vented  gas  fueled  equipment.  It  shall  be  the 
responsibility of the property owner to secure the services 
of qualified licensed professionals for the installation of hard 
wired carbon monoxide detectors.
In the event that the side wall horizontally vented gas fueled 
equipment is installed in a crawl space or an attic, the hard 
wired  carbon  monoxide  detector  with  alarm  and  battery 
back-up may be installed on the next adjacent floor level.
In the event that the requirements of this subdivision can not 
be met at the time of completion of installation, the owner 
shall have a period of thirty (30) days to comply with the 
above requirements; provided, however, that during said 
thirty (30) day period, a battery operated carbon monoxide 
detector with an alarm shall be installed.

approved Carbon Monoxide Detectors

Each carbon monoxide detector as required in accordance 
with the above provisions shall comply with NFPA 720 and 
ANSI/UL 2034 listed and IAS certified.

Signage

A metal or plastic identification plate shall be permanently 
mounted to the exterior of the building at a minimum height 

of eight (8) feet above grade directly in line with the exhaust 
vent terminal for the horizontally vented gas fueled heating 
appliance or equipment. The sign shall read, in print size no 
less than one-half (1/2) inch in size, 

“GaS VeNt DIreCtLy 

BeLow, KeeP CLear oF aLL oBStruCtIoNS”.

Inspection

The state or local gas inspector of the side wall horizontally 
vented  gas  fueled  equipment  shall  not  approve  the 
installation unless, upon inspection, the inspector observes 
carbon  monoxide  detectors  and  signage  installed  in 
accordance  with  the  provisions  of  248  CMR  5.08(2)(a)1 
through 4.

exemptions

The  following  equipment  is  exempt  from  248  CMR 
5.08(2)(a)1 through 4:

• 

The equipment listed in Chapter 10 entitled “Equipment 
Not Required To Be Vented” in the most current edition 
of NFPA 54 as adopted by the Board; and

• 

Product Approved  side  wall  horizontally  vented  gas 
fueled  equipment  installed  in  a  room  or  structure 
separate from the dwelling, building or structure used 
in whole or in part for residential purposes.

MaNuFaCturer requIreMeNtS

Gas equipment Venting System Provided

When  the  manufacturer  of  Product Approved  side  wall 
horizontally  vented  gas  equipment  provides  a  venting 
system  design  or  venting  system  components  with  the 
equipment, the instructions provided by the manufacturer 
for  installation  of  the  equipment  and  the  venting  system 
shall include:

• 

Detailed instructions for the installation  of the venting 
system design or the venting system components; and

• 

A complete parts list for the venting system design or 
venting system.

Gas equipment Venting System Not Provided

When the manufacturer of a Product Approved side wall 
horizontally vented gas fueled equipment does not provide 
the parts for venting the flue gases, but identifies “special 
venting  systems”,  the  following  requirements  shall  be 
satisfied by the manufacturer:

• 

The  referenced  “special  venting  system”  instructions 
shall  be  included  with  the  appliance  or  equipment 
installation instructions; and

• 

The  “special  venting  systems”  shall  be  Product 
Approved  by  the  Board,  and  the  instructions  for  that 
system shall include a parts list and detailed installation 
instructions.

A copy of all installation instructions for all Product Approved 
side  wall  horizontally  vented  gas  fueled  equipment,  all 
venting instructions, all parts lists for venting instructions, 
and/or  all  venting  design  instructions  shall  remain  with 
the  appliance  or  equipment  at  the  completion  of  the 
installation.

f i r e - p a r t s . c o m

Summary of Contents for DVBL7 Series

Page 1: ...fer to this manual For assistance or additional information consult a qualified installer service agency or the gas supplier Thisappliancemaybeinstalledinanaftermarket permanently located manufactured...

Page 2: ...ting Burner 31 Checking Gas Pressure Signature Command System 32 Electrical Wiring SCS 32 Junction Box Wiring 33 Command Center Wall Installation 33 Wall Switch Installation 33 Signature Command Wirin...

Page 3: ...IMPORTANT SAFETY INFORMATION This fireplace is a vented product This fireplace must be properly installed by a qualified service person The glass door must be properly seated and sealed If this unit...

Page 4: ...cked or broken Code Approval Direct Vent type appliances draw all combustion air from outside of the dwelling through the vent pipe These appliances have been tested by CSA and found to comply with th...

Page 5: ...shown in BTU per hour and are certified without deration for elevations up to 4 500 feet 1 370 m above sea level For elevations above 4 500 feet 1 370 m in USA installations must be in accordance wit...

Page 6: ...mm 17 zn 446 mm F 22B zn 567 mm 25ZC zn 656 mm 25ZC zn 656 mm G 29ZZ cx 745 mm 31M 810 mm 31M 810 mm H 30Z zn 764 mm 31ZB zn 811 mm 35ZB zn 913 mm I 3 76 mm 3 76 mm 3 76 mm J 1 25 mm 1 25 mm 1 25 mm...

Page 7: ...specific installation requirements Refer to Figure 2 for firebox dimensions The framing headers may rest on the top of the firebox standoffs Do not bring headers below top of standoffs NOTE When plan...

Page 8: ...heat from appliance Never obstruct the front opening of the fireplace Do not install in the vicinity where gasoline or other flammable liquids may be stored Vent pipe routing Refer to Venting section...

Page 9: ...nstalled on a carpet tile or other combustible material other than wood flooring If installed on carpet or vinyl flooring the appliance shall be installed on a metal wood or noncombustible material pa...

Page 10: ...nly noncombustible materials i e brick tile slate steel or other materials with a UL fire rating of Zero may be used to cover the black painted face of the appliance It is permissible to bring combust...

Page 11: ...direct vent components can be used All restrictions clearances and allowanc es that pertain to the rigid piping apply to the flexible venting Flex kits may not be modified Flex kits may be added to t...

Page 12: ...y above the meter regulator assembly 5 m above the meter regulator assy I Clearance to service regulator vent outlet 3 91 cm 3 91 cm J Clearance to nonmechanical air supply inlet 6 15 cm for appliance...

Page 13: ...m of 3 914 mm below the termination cap 3 All gravity air intakes within 3 914 mm of a termination cap must be a minimum of 1 305 mm below the termination cap General Information Assembling Vent Pipes...

Page 14: ...the finished outside wall to the center of the pipe on the fireplace Vertical Dimension From the Floor of Unit to the Center of the Horizontal Vent Pipe 57 from floor to center eg A eg B T Lock Pipes...

Page 15: ...he vertical rise is 71 2 ft or more only a 1 clearance is needed on top of any horizontal run Vertical sections of this vent system require a minimum of 1 clearance to combustibles on all sides of the...

Page 16: ...ined the horizontal vent length is re duced by 36 914 mm Figures 13 14 This does not apply if the 90 elbows are used to increase or redirect a vertical rise Figure 12 12 Min 3 x 90 Elbows FP1176 Figur...

Page 17: ...vent opening Step 3 Place fireplace into position Measure the vertical height X required from the base of the flue collars to the center of the wall opening Figure 17 Step 4 Install the unitized T Loc...

Page 18: ...lex vent pipe to the appliance col lar as described on Page 13 Secure the end with the first spring 18C v 476 mm from the flex pipe end to the unit Step 6 Slide the 7 178 mm flex vent pipe over the 4...

Page 19: ...ecessary to ex tend vent pipes out as far as the protruding wall face Figure 22 VERTICAL THROUGH THE ROOF APPLICATION his gas fireplace has been approved for Vertical installations up to 40 12 m in he...

Page 20: ...ow the shingles Figure 29 8 Install appropriate pipe sections until the venting is above the flashing Figure 29 9 Install storm collar and seal around the pipe 10 Add additional vent lengths for prope...

Page 21: ...Termination Vent Storm Collar Flashing Lowest Discharge Opening Concentric Vent Pipe 1 Minimum Clearance to Combustibles FP1971 Horizontal Overhang Figure 28 Minimum Chimney Clearance Roof Pitch H fee...

Page 22: ...equipment shutoff valve with 1 8 NPT tap is an acceptable alternative to test gauge connection Purchase the CSA design certified equipment shutoff valve from your dealer For propane LP connections on...

Page 23: ...s moisture and contaminants and keeps them from going into the burner system gas controls If sediment trap drip leg is not installed or is installed wrong burner system may not run properly NOTE The g...

Page 24: ...pressure reading be sure and turn captured screw clockwise firmly to reseal Do not over torque Check test points for gas leaks Electrical Wiring This fireplace will work without any electrical supply...

Page 25: ...bottom of fireplace Figure 33 3 Tilt glass frame out and lift glass frame up until it clears three tabs on top of fireplace 4 Set glass frame aside Each clamp has a quick spring force When reinstallin...

Page 26: ...h prevailing codes 2 Remove the external junction box cover by removing the screw from the left side of the outside firebox wall Junc tion box was installed at the factory 3 The junction box cover has...

Page 27: ...on the thermal sensor are perpendicular to the clip Figure 39 WARNING It is important to arrange the blower wire har ness so the wires can not come in contact with blower fan blades 13 Connect wiring...

Page 28: ...ensor Installation Figure 40 Location of White Dial on Speed Control Blower Motor Blower Motor 110 115V AC Blower Plug Black White Green FP1910 SC blower wiring diagram 8 08 Variable Fan Control OFF O...

Page 29: ...service technician Force or attempted repair may result in a fire or explosion D Do not use this appliance if any part of it has been under water Immediately call a qualified service technician to ins...

Page 30: ...time when the magnet is closed it is possible to start the lighting operation The gas control knob is designed to be operated by hand DO NOT use any tools during this operation Damaged knobs may resul...

Page 31: ...itch allows you to turn on and to turn off the main burner without using the gas valve knob Make sure the button is in the ON position to light the main burner Figure 43 Lighting the burner Depress an...

Page 32: ...ing General 1 This fireplace is equipped with the Signature Control valve which operates on 6 volts The 6 volt DC adapter plugs into the fireplace junction box A C power supply Four 4 AA batteries are...

Page 33: ...not extend beyond the 15 ft wire cable provided If a longer distance is required the 15 ft may be extended up to 30 ft maximum by using two 2 SCSWEK cables plugged together Route the wire from juncti...

Page 34: ...Connector Control Board to Command Center OFF LO LED ON HI Master Switch Command Center Optional Wall Switch Plug in Connector Stepper Motor to Control Board DC Power Green Ground Plug in Connector Co...

Page 35: ...the control will not work correctly WARNING Electrical connections should only be performed by a qualified licensed electrician Main power supply must be turned off before connecting the fan to the ma...

Page 36: ...OTSDV blower wiring OPTIONAL FAN BLOWER SYSTEMS BLOTSDV AUTOMATIC THERMOSTAT BLOWER Figure 51 BLOTSDV Blower Wiring Diagram FP2685 Before installing the blower wire the receptacle into an electrical c...

Page 37: ...as supplier s instructions If you cannot reach your gas supplier call the fire department C Use only your finger to push in the master switch Never use tools If the switch will not func tion by hand d...

Page 38: ...s go to next step 4 Press the master switch to the ON position Within eight 8 seconds it will beep once This indi cates the system is ready 5 Press ON button Sparker will spark and pilot flame will li...

Page 39: ...ock out X X X X X LCD Backlight X X X X X Security Codes 16 X X X X X Countdown 6 hr Timer X X X Standard Thermostatic Control Mode X X X Smart Mode Thermostat Auto Flame Blower Modulation X X Three B...

Page 40: ...One beep for RF receiver ON or two beeps for RF receiver OFF will be given as confirmation Refer to Figure 57 for location 2 After the RF receiver is on holding the OFF button on the Command Center w...

Page 41: ...eight 2 Press the OFF button to decrease flame height The first two presses will decrease the flame height to medium and low 3 The third press on OFF will turn off the main burner In standing pilot co...

Page 42: ...pin on the burner Also match the cut out on the bottom of the log with the bars on the grate Note When this log is in place pull towards the front 3 Place the right front log 4 over the burner and gra...

Page 43: ...ght log 2 by resting it over the upper right log and the rear log This log will curve to the middle as it rests over the rear log final installation LG613 DVBL upper rear log LG612 DVBL left front top...

Page 44: ...soon as the heater is installed and periodically during normal operation In normal operation at full rate and after operating for about 15 to 30 minutes the flame should be yellow and slightly taller...

Page 45: ...e used Handle glass door with care to avoid striking or scratching it on hard objects To clean glass door follow Glass Removal procedure outlined in the Final Installation section Film deposit on the...

Page 46: ...thermocouple connec tion at the gas valve is fully inserted and tight Disconnect the thermocouple from the valve place one millivolt lead wire on the tip of the thermocouple and the other meter lead w...

Page 47: ...lame impingement on thermocouple A Check for flue product leak Replace defective pipe section B Check horizontal venting piping is running upward 1 4 per foot Do not run the pipe level or downward C C...

Page 48: ...ry polarity wrong LED on the Command Center does not show solid green The 5 pin connector on the AC board broken or bent AC plug is plugged to AC mains Battery voltage low Using battery Check valve co...

Page 49: ...96K 74D0211TK 4 Control Cover 1 20302002 74D0038K 74D0119 Accessories Field Installed Options 5 T Stat Blower w Speed Control 1 BLOTBLDV BLOTBLDV BLOTBLDV 5 SCS Blower w Time Delay 1 BLOTBCDVSC BLOTBC...

Page 50: ...20301852 50 DVBL7 Series Gas Fireplace REPLACEMENT PARTS Standing Pilot Millivolt control 1 2C 2I 2T 2 4 5 6 3 8 9 7 10 11 12 13 14 743000 BLDV millivolt parts fire parts com...

Page 51: ...0 69D0030 69D0030 5 Rocker Switch 1 41D0048 41D0048 41D0048 41D0048 6 Piezo Igniter 1 14D0503 14D0503 14D0503 14D0503 7 Injector 1 20H3147 33D5039 33D5040 57D0210 8 Burner Assy 1 74D0098K 74D0098K 74D...

Page 52: ...20301852 52 DVBL7 Series Gas Fireplace REPLACEMENT PARTS SIGNATURE COMMAND SYSTEM 743000 BLDV SC parts 1 2 3 4 20 5 6 7 8 9 13 14 15 16 17 12 fire parts com...

Page 53: ...S NOTE TSFSC must be used with SCS A C Module to control lights blower and aux Item Description Qty 300DVBL 300DVBL 400DVBL 400DVBL 500DVBL 500DVBL NSC7 PSC7 NSC7 PSC7 NSC7 PSC7 1 Gas Valve Assembly 1...

Page 54: ...300DVBL 400DVBL 500DVBL 1 Rear Log 1 1 20302144 74D0059 74D0059 2 Top Right Log 2 1 20302145 74D0060 74D0060 3 Front Upper Log 3 1 20302146 74D0061 74D0061 4 Right Front Log 4 1 20302147 74D0062 74D01...

Page 55: ...Collar 8 pack 47TLVTK 8 flashing NOT included Vertical Vent Termination w 1 12 6 12 Flashing Storm 47TLVTKA Collar and Ceiling Support Kit Vertical Vent Termination w 6 12 12 12 Flashing 47TLVTK8 Sto...

Page 56: ...VBL only Rear Vent Cool Touch Termination w Siding Shield for 7TRVCT 8 Straight out Applications and Firestop 8 pack Rear Vent Hot Touch Termination w Siding Shield for 7TRVHT 8 Straight out Applicati...

Page 57: ...20301852 57 DVBL7 Series Gas Fireplace fire parts com...

Page 58: ...e with the above provisions shall comply with NFPA 720 and ANSI UL 2034 listed and IAS certified Signage A metal or plastic identification plate shall be permanently mounted to the exterior of the bui...

Page 59: ...Warranty will also be void if the appliance is not operated and maintained according to the operating instructions supplied with the appliance and does not extend to 1 firebox burner assembly damage b...

Page 60: ...les caract ristique de rendement nerg tique de foyer au gaz nerguide Selon CSA P 4 1 09 Efficiency Ratings Model EnerGuide Ratings Fireplace Efficiency 300DVBLNSC7 tbd 300DVBLPSC7 64 2 400DVBLNV7 63 8...

Reviews: