VertIcaL (tHrOuGH-tHe-rOOF)
appLIcatIOnS
This gas fireplace has been approved for,
• Vertical installations up to 40' (12 m) in height. Up to
a 10' (3 m) horizontal vent run can be installed within
the vent system using a maximum of two 90° elbows.
Figure 18
Figure 18 -
Support Straps for Horizontal Runs
VentInG InStaLLatIOn
•
Up to two 45° elbows may be used within the horizontal
run. For each 45° elbow used on the horizontal plane,
the maximum horizontal length must be reduced by
18" (450 mm).
Example:
Maximum horizontal length
No elbows = 10’ (3 m)
1x45° elbows = 8.5’ (2.6 m)
2x45° elbows = 7’ (2.1 m)
•
A minimum of an 8' (2.5 m) vertical rise is required.
•
Two sets of 45°elbows offsets may be used within the
vertical sections. From 0 to a maximum of 8' (2.5 m)
of vent pipe can be used between elbows.
Figure 19
•
The maximum angular variation allowed in the system
is 270°.
Figure 19
•
The minimum height of the vent above the highest point
of penetration through the roof is 2' (610 mm).
Example:
Elbow 1 = 90°
Elbow 2 = 45°
Elbow 3 = 45°
Elbow 4 = 90°
Total Angular Variation = 270°
nOte:
Horizontal sections of this vent system require a
minimum of 3" clearances to combustibles at the top of the
flue and 1" clearance at the sides and bottom until the flue
penetrates the outside wall. A minimum 1" clearance all
around the flue is acceptable at this point of penetration.
Vertical sections of this vent system require a minimum of
1" clearance to combustibles on all sides of the pipe.
24" Min.
1
2
3
4
1
2
3
4
FP1179
max bends
Figure 19 -
Maximum Elbow Usage
FP1179
FP1183
max height
40' Maximum Height
12' Minimum Height
10'
Maximum
Support Straps
Every 3'
24" Min.
FP1183