DVB7 Series Direct Vent Gas Fireplace
8
54D7051
CleARANCeS
CleARANCeS to CoMBuStIBleS
W
ARNING
Follow these instructions carefully to ensure safe installation. Failure
to follow instructions exactly can create a fire hazard.
the appliance cannot be installed on a carpet, tile or other combustible
material other than wood flooring. If installed on carpet or vinyl flooring,
the appliance shall be installed on a metal, wood or noncombustible
material panel extending full width and depth of the appliance.
71” Minimum
11” Minimum
12”
Max.
Min. 4”
From Either
Side Wall
FP2248
mantel clearances
Figure 4 -
Clearances
Ceiling
Combustible Mantel
5”
7”
11”
3”
12”
8”
6”
2”
FP2204a
mantel clearances
Wall
Stud
Standoff
FP04
Top of Exhaust
Louvers
Side View
1"
2
56O
”
3"
4"
1
56O
”
2
56O
”
45°
FP2093A
mantel side clearance
Wall
Combustible
Material Area
Side of Fire-
place Opening
FP093a
top View
Figure 5 -
Mantel Clearances
MANtel CleARANCeS
Note:
The combustible area above the facing must
not protrude more than 1/" from the facing. If it does,
it is considered a mantel and must meet the mantel
requirements listed in this manual.
W
ARNING
Never obstruct or modify the air inlet or
outlet grilles (louvers). this may create
a fire hazard.