Follow  these  instructions  carefully  to  ensure  safe  installation.  Failure  to  follow 

instructions exactly can create a fire hazard.
The appliance cannot be installed on a carpet, tile or other combustible material other 

than wood flooring. If installed on carpet or vinyl flooring, the appliance shall be installed 

on a metal, wood or noncombustible material panel extending full width and depth of 

the appliance.

W

ARNING

CLEARANCES

CLEARANCES TO COMBuSTIBLES 

MANTEL CLEARANCES 

NOTE: The combustible area above the facing must not protrude more than 

3

/

4

" from the facing. If it does, 

it is considered a mantel and must meet the mantel requirements listed in this manual. 

Figure 5 - Clearances 

Figure 5a - Mantel clearances.

NOTE

All mantel shelves, regardless of depth, should be a mini

-

mum of 12" from top opening of fireplace. Mantel shelf 

shall not exceed 12" maximum depth at 12" minimum 

height from opening.

Summary of Contents for 300DVBH

Page 1: ...l information consult a qualified installer service agency or the gas supplier This appliance may be installed in an aftermarket permanently located manufactured home USA only or mobile home where not...

Page 2: ...n 28 Check Gas Type 28 Installing Gas Piping to Fireplace Burner System Location 28 Checking Gas Pressure 30 Electrical Installation 30 Electrical Wiring 30 Remote Wall Mounted Switch 31 Remote Wall S...

Page 3: ...this unit is not properly installed by a qualified service person with glass door properly seated and sealed combustion leakage can occur CARBON MONOXIDE POISONING Early signs of carbon monoxide pois...

Page 4: ...ll a qualified service person to arrange for replacement of the unit 19 Do not operate fireplace if any log is broken 20 Do not use a blower insert heat exchanger insert or any other accessory not app...

Page 5: ...y rating determined under continuous operating conditions and was deter mined independently of any installed system Thermal efficiency up to 75 AFUE efficiency up to 71 Hi Lo Knob product SPECIFICATIO...

Page 6: ...been received You should have the following Fireplace Firebox and Burner System Rock Wool Log Set Items Required For Installation Tools Building Supplies Phillips Screwdriver Framing Materials Hammer...

Page 7: ...lowing Figure 2 and the chart below for your specific installation requirements See Figure 3 on Page 8 for firebox dimensions The framing headers may rest on the top of the firebox standoffs Do not br...

Page 8: ...Pipe Rear L R D 161 2 181 2 Rear Width E 28 29 Glass Height F 18 203 8 Total Height G 337 8 405 8 Depth H 15 181 4 Figure 3 Fireplace Dimensions DESCRIPTION Key Letter 300DVBH 400DVBH Height to Stando...

Page 9: ...and draperies due to heat from appliance Never obstruct the front opening of the fireplace Do not install in the vicinity where gasoline or other flammable liquids may be stored Vent pipe routing See...

Page 10: ...l flooring the appliance shall be installed on a metal wood or noncombustible material panel extending full width and depth of the appliance WARNING clearances Clearances to combustibles mantel cleara...

Page 11: ...lace to the floor Use four 4 screws to attach fireplace to framing The side nailing flanges are 1 2 or 5 8 to accommodate different wall thickness SECURING FIREPLACE to floor or framing Figure 6 Secur...

Page 12: ...Be aware of electrical wiring locations in walls and ceilings The following actions will void the warranty on your venting system Installation of any damaged venting component Unauthorized modificatio...

Page 13: ...f this vent system require a minimum of 3 clearances to combustibles at the top of the flue and 1 clearance at the sides and bottom until the flue penetrates the outside wall A minimum 1 clearance all...

Page 14: ...1 Remove the eight 8 screws securing the flue pipe adapter to the fireplace body See Figure 9 2 Set the flue pipe adapter aside complete with the gasket Do not damage the gaskets as the adapter and ga...

Page 15: ...each floor level If an offset is needed in the attic additional pipe and elbows will be required You may use a chase with a vent termination with exposed pipe on the exterior of the house See Installi...

Page 16: ...ventilated soffit located above the terminal within a horizontal distance of two 2 feet 610mm from the centerline of the terminal 18 457mm minimum E Clearance to unventilated soffits 12 305mm minimum...

Page 17: ...he vertical and horizontal dimensions of the vent system 1 Determine the height of the center of the horizontal vent pipe exiting through the outer wall Using this dimension on the Sidewall Vent Graph...

Page 18: ...r s tabs Attach Simpson s DirectVent Pro by fully inserting into the collar and securing with self tapping screws The screws shall only penetrate the flue outer wall Refer to vent manufacturer s insta...

Page 19: ...o All Four Sides Vent Cap Wood Screw Cut Vinyl Siding Away to Fit Standoff Wood Screw Simpson Termination 985 Bolt Apply Mastic to All Four Sides Nut Standof 950 Figure 20 Installing Firestop on Horiz...

Page 20: ...exits through foundations less than 20 below outcrop the termination must be flush up with outcropped wall above It is best to locate the fireplace in such a way that minimizes the number of offsets...

Page 21: ...n A plus B must not be greater than 17 5 2m The maximum number of 45 elbows permitted per side wall installation is two 2 These elbows can be installed in either the vertical or horizontal run For eac...

Page 22: ...ase of snorkel Install drain pipe Install window well not supplied Refill hole with 12 of coarse gravel leaving a clearance of approximately 4 below snorkel See Figure 26 3 Install vent system 4 Ensur...

Page 23: ...y 18 450mm Example Maximum horizontal length No elbows 10 3m 1x45 elbows 8 5 2 6m 2x45 elbows 7 2 1m A minimum of an 8 2 5m vertical rise is required Two sets of 45 elbows offsets may be used within t...

Page 24: ...e plumb down from the ceiling to the position of the flue exit Mark the center point where the vent will penetrate the ceiling Drill a small locating hole a this point Drop a plumb line from the insid...

Page 25: ...p roof pitches Nearby trees adjoining roof lines steep pitched roofs and other similar factors may cause poor draft or down drafting in high winds Increasing the vent height may solve this problem NOT...

Page 26: ...parately UL1777 listed type flex venting only 3 Start the flexible vent as follows A Installing the inner flex adaptor and pipe see Figure 1 1 Insert the long side of the 4 inner ring inte exhaust pip...

Page 27: ...bed by the flexible vent manufacture and in such a way as to maintain concentric inner and outer vent spacing D Attaching flexible venting to vertical termination assemblies 1 When using Simpson pipe...

Page 28: ...alling gas piping to fireplace burner system location installation items needed Before installing fireplace and burner system make sure you have the items listed below External regulator supplied by i...

Page 29: ...ip leg in supply line as shown in Figure 40 Locate sediment trap drip leg where it is within reach for cleaning Install in piping system between fuel supply and burner system Locate sediment trap drip...

Page 30: ...ure reading be sure and turn captured screw clockwise firmly to reseal Do not over torque Check test points for gas leaks Figure 41 Gas Pressure Check at Gas Valve Pressure Test IN Pressure Test OUT H...

Page 31: ...lways check with local code Figure 42 Wiring Diagram for Wall Switch Do not connect 110V to wall switch WARNING Electrical installation Figure 43 Blower Wiring Diagram Remote Wall Switch Position the...

Page 32: ...ter firebrick panel on the back wall first Stand firebrick panel straight up against the back of fireplace with the bottom edge at bottom of inner firebox 4 Repeat Step 3 with the left and right side...

Page 33: ...the unit to establish yellow flame in the front See Figure 46 4 Place log 1 into place by setting the log over the two pins on the grate toward the back The two round holes on the bottom of the logs s...

Page 34: ...he two notches on the bottom of this log with the two protrusions on log 1 2 This log when seated fits in the middle above logs 1 2 See Figure 50 8 Place log 5 into place by matching the two notches o...

Page 35: ...bar Figure 52 Placement of Log 6 Figure 53 Placement of Log 7 HBDV400 only Figure 54 a b Andiron Placement 400DVBH and 300DVBH Figure 55 Universal Andirons final installation installing universal and...

Page 36: ...air may result in a fire or explosion D Do not use this appliance if any part of it has been under water Immediately call a qualified service technician to inspect the appliance and to replace any par...

Page 37: ...closed it is possible to start the lighting operation The gas control knob is designed to be operated by hand DO NOT use any tools during this operation Damaged knobs may result in serious injury WARN...

Page 38: ...lows you to turn on and to turn off the main burner without using the gas valve knob Make sure the button is in the ON position to light the main burner See Figure 57 Lighting the burner Depress and t...

Page 39: ...in operation See Figure 61 The pilot flame has three distinct flames one engulfing the thermopile one engulfing the thermocouple and the other reaching to the main burner burner Inspect area around th...

Page 40: ...Handle glass door with care to avoid striking or scratching it on hard objects To clean glass door follow Glass Removal procedure outlined in the Final Installation section Film deposit on the inside...

Page 41: ...nection at the gas valve is fully inserted and tight Disconnect the thermocouple from the valve place one millivolt lead wire on the tip of the thermocouple and the other meter lead wire on the thermo...

Page 42: ...for maximum flame impinge ment on thermocouple A Check for flue product leak Replace defective pipe section B Check horizontal venting piping is running upward 1 4 per foot Do not run the pipe level...

Page 43: ...54D5032 43 1 2 3 5 6 7 10 4 9 11 replacement partS fireplace components...

Page 44: ...k Right TB 1 54D0285 54D0187 7 Standard Firebrick Left TB 1 54D0285 54D0186 5 Standard Firebrick Center CR 1 26D7097 26D7105 6 Standard Firebrick Right CR 1 26D7096 26D7104 7 Standard Firebrick Left C...

Page 45: ...54D5032 45 1 2 3 4 5 6 7 11 12 13 14 15 2T 2I 2C 8 8A 400DVBH 8B 300HBDV 10 Millivolt engine replacement partS...

Page 46: ...03 14D0503 7 Injector 1 62D3006 20H3156 62D3004 33D5039 8 Burner Assembly 1 54D5115 54D5115 54D5006 54D5006 9 Venturi 1 45D0600 45D0600 45D0600 45D0600 10 Wire Assembly 1 44D0500 44D0500 44D0500 44D05...

Page 47: ...Profile Vertical Termination Cap 46DVA VC 980 4DT VC 1 1 Square Horizontal Termination Cap aluminum 46DVA HC 985 4DT HC Round Horizontal Termination Cap Square Base aluminum 46DVA HRCS Sconce Termina...

Page 48: ...Description Qty 300DVBH 400DVBH 1 Rear Log 1 54D5125 54D5040 2 Right Log 1 54D5126 54D5041 3 Left Log 1 54D5127 54D5042 4 Mid Top Log 1 54D5129 54D5043 5 Right Top Log 1 54D5128 54D5044 6 Left Front L...

Page 49: ...feet above finished grade in the area of the venting including but not limited to decks and porches the following requirements shall be satisfied 1 INSTALLATION OF CARBON MONOXIDE DETECTORS At the tim...

Page 50: ...purposes c MANUFACTURER REQUIREMENTS GAS EQUIPMENTVENTING SYSTEM PROVIDED When the manufacturer of Product Approved side wall horizontally vented gas equipment provides a venting system design or ven...

Page 51: ...y will also be void if the appliance is not operated and maintained according to the operating instructions supplied with the appliance and does not extend to 1 firebox burner assembly dam age by acci...

Page 52: ...52 54D5032 AUGUST 2008 54D5032 Rev 5 MHSC 149 Cleveland Drive Paris Kentucky 40361 www mhsc com...

Reviews: