background image

6

UVLC Series

4. 

Compare the maximum BTU/hour rating the space 

can support with the total BTU/hour used by the appli-
ances.
Example:   76,800 BTU/hour the space can support
               80,000 BTU/hour used by appliances
In this example, the maximum BTU/hour that the space 
can support is less than the total used by the appli-
ances. The space is considered to be 

Confined Space. 

Additional air must be provided to meet the require-
ments on the vent-free gas log set. 
The installation and the provisions for combustion and 
ventilation air must conform with the National Fuel Gas 
Code, ANSI Z223.1/NFPA 54, or the CSA-B149.1 Instal-
lation Code (Series).

A confined space may be ventilated in two ways:

A.

 Open up or provide at least two ventilating grilles to 

an adjoining unconfined space. (Fig. 2)
Each of the two grilles must provide an opening of at 
least 50 square inches, with all opening dimensions be-
ing at least 3”. One grille must be within 12” of the ceil-
ing; the other within 12” of the floor. (If the total exceeds 
100,000 BTU/hour, additional grilles will be needed.)

B.

 Vent the room directly to the outdoors. (Provide one 

square inch of opening for each 4,000 BTU/hr.)
For further information on ventilation guidelines and siz-
ing specifications, follow the National Fuel Gas Code/
NFPA 54/ANSI Z223.1/NFPA 54, Section 5.3.
If the total BTU/hour used by the appliances is less than 
the maximum BTU/hr the space can support, the room 
meets the 

Unconfined Space

 criteria and no further 

ventilation is needed. 

WARNING:

 Before installing the gas log set in a solid-

fuel burning fireplace, the chimney flue and firebox must 

be cleaned of soot, creosote, and loose paint by a quali-

fied chimney cleaner.

WARNING

This heater shall not be installed in a confined 
space or unusually tight construction unless 
provisions are made for adequate combustion 
and ventilation air.

WARNING

If the area in  which the heater may be operated 
is smaller than that defined as an  unconfined 
space, or if the building is of unusually tight 
construction, provide adequate combustion and 
ventilation air by one of the methods described 
in the  National Fuel Gas Code, ANSI Z223.1/
NFPA 54, 1992, Section 5.3, or applicable codes.

VO370-2

Ventilation 

options 

3/26/99   djt

Fig. 2

  Ventilation options for confined spaces.

OPTION 1 -

 

Vents to Ad-

joining Rooms

OPTION 2 -

 

Remove Door 

to Adjoining 

Room

OPTION 3 -

 

Vents to Ad-

joining Rooms

12”

12”

VO370-2

Example:

Gas Range 

 

 55,000 BTU/hour

Vent-Free LogSet 

+25,000 BTU/hour

   

Total 

 80,000 BTU/hour

Summary of Contents for Woodland UVLC18RN

Page 1: ...RBON MONOXIDE POISONING MAY LEAD TO DEATH When used without fresh air vent free log sets may give off carbon monoxide an odorless poisonous gas Some people pregnant women people with heart or lung dis...

Page 2: ...ve been designed and tested to operate safely when installed according to the installation instruc tions contained in this manual Read all instructions before starting the installation The vent free g...

Page 3: ...opening a window or otherwise providing additional ventilation to the area Min Fireplace Dimensions A B C D Logset Gas Front Rear Overall Overall Pressure w c Manifold Min Input Max Input Setting Wid...

Page 4: ...actory built replace or ventless rebox enclosure State provincial or local codes may only allow opera tion of this appliance in a vented con guration Check your state provincial or local codes If unve...

Page 5: ...ent free Gas Heater Vented Gas Heater Other Gas Appliances Do not include Direct vent appliances as these use outdoor air for combustion and vent to the outdoors Modern construction standards have res...

Page 6: ...each 4 000 BTU hr For further information on ventilation guidelines and siz ing speci cations follow the National Fuel Gas Code NFPA 54 ANSI Z223 1 NFPA 54 Section 5 3 If the total BTU hour used by th...

Page 7: ...ion Preparation A 1 2 inch gas supply line must be supplied to the rebox In most cases this will require drilling a gas line access hole through the masonry wall The gas supply line should then be sea...

Page 8: ...the damper locking bracket Attach the damper stop with the screws provided Fig 6 NOTE Some of the early units may not have the holes in the end of the damper locking bracket If this is the case use t...

Page 9: ...of the replace to a height of at least 20 and the full width of the replace A combustible at mantel shelf can be no closer than 38 from the top of the replace opening Fig 7b With Hood If a hood is in...

Page 10: ...lve ON and carefully check all gas con nections for leaks with a soapy water solution or a sniffer DO NOT TEST FOR LEAKS WITH AN OPEN FLAME Upon completing your gas line connection a small amount of a...

Page 11: ...wall switch to the valve termnals Remote Wall Switch Optional Model GWSK 1 Thread wire through the electrical knockout located on either side of the replace Do not cut the wire or insulation on metal...

Page 12: ...normal You may wish to have the windows open to dissipate any odors during the curing process Flame Appearance To obtain proper operation it is imperative that the pilot and main burner ame characteri...

Page 13: ...NG smell all around the heater area for gas Be sure to smell next to the oor because some gas is heavier than air and will settle on the oor WHAT TO DO IF YOU SMELL GAS Do not try to light any replace...

Page 14: ...Replace piezo ignitor For air in the lines Thermopile needs a minimum of 325mV All wiring connections Replace thermopile Thermocouple needs a minimum of 14mV Defective valve turn to pilot meter should...

Page 15: ...ali ed eld service person Always keep the appliance area clear and free from combustible materials gasoline and other ammable vapors and liquids Never obstruct the ow of combustion and ventilation air...

Page 16: ...ci cations prices and discontinue colors and products at any time without notice UVLC Supreme Vent Free Gas Logs 1 Complete Log Set 20003423 20000327 20003428 1a Back Log 20003425 7583198 20003430 1b...

Page 17: ...el Door Painted 20005340 20005345 20005345 11 Back Plate 20003023 20000321 20000321 12 Right Side Grate Painted 20005338 20005338 20005338 13 Left Side Grate Painted 20005339 20005339 20005339 14 Fett...

Page 18: ...enamel in Midnight Black AC110 Remote WAll Switch 5 7 99 djt AC100 FIREPLACE HOOD 3 29 99 DJT AC111 Fireback from VErmont 5 7 99 djt NOTE If any of the original wire as supplied with the appliance mu...

Page 19: ...de chaleur de la chambre combustion et du br leur en c ramique de tout produit CFM Corporation sont garanties pour la vie de l acheteur d origine le tout sujet une preuve d achat et aux conditions et...

Page 20: ...CFM Corporation 2695 Meadowvale Blvd Mississauga Ontario Canada L5N 8A3 800 668 5323 www cfmcorp com CFM Corporation...

Reviews: