Framing and Finishing

1.  Choose fireplace location.
2.  Place fireplace into position and secure to floor with 
  1

¹⁄₂

" screws, or nails. The holes to secure the fire-

place to the floor are located just behind the access 
door grille on the left and right hand side of the 
fireplace. 

FP1023

side nailing flange

1/27/00  djt

C

A

B

Adjustable Drywall Strip

(Nailing Flange)

  Screw 

Drywall

 Position 

Depth

 

1/2" (13 mm)

 

5/8" (16 mm)

 

3/4" (19 mm)

Adjustable

1/2", 5/8" & 

3/4" Spacing

FP1023

Fig. 4

  Adjustable drywall strip (nailing flange).

A

B

D

C

FP1400

DVHVAC

mantel setup

8/03

Mantel

Top Louvre Opening

Front Glass

Side View

Optional Hearth

Gas Knock-Out

Electrical 

Knock-

Out

Electrical Cable 

Knock-Out

FP1400

Mantel Chart

 

Ref.  

From Top 

Ref. 

Depth

 

 

Louvre (Min.) 

 

(Max.)

 

15

¹⁄₅

" (394 mm) 

7" (178 mm)

 

48" (1219 mm) 

any

Mantel Leg Chart

 

From Fireplace 

Depth

 

Side (Min.) 

(Max.)

 

7

¹⁄₂

" (191 mm) 

1

³⁄₄

" (44 mm)

Fig. 5

   Combustible mantel installation.

3.  Frame in fireplace. It is important to allow for finished 

face when setting the depth of the frame. 

4.  Attach fireplace to frame using adjustable frame 

drywall strips (located behind access door for ship-
ping). Preset depth to suit facing material (adjustable 
to 1/2", 5/8" or 3/4" depths). (Fig. 4)

5.  Screw through slotted holes in drywall strip and then 

screw into pre-drilled holes on fireplace side. Meas-
ure from face of fireplace to face of drywall strip to 
determine final depth. (Fig. 4)

Supply Air Duct Systems

The DVHVAC36 fireplace has three 6" (152 mm) diam-
eter supply air outlets. Duct runs of up to 65 equivalent 
feet (19.8 m) using 6" (152 mm) round duct (or equiva-
lent), are permissible. Duct runs of up to 40 equivalent 
feet (12.2 m) are permitted using 5" (127 mm) round 
duct (or equivalent). Runs of up to 30 equivalent feet   
(9 m) are permitted when using 4" (102 mm) round duct 
(or equivalent).  In all cases, size and install the supply 
air system using industry approved standards which 
result in a quiet and low static system.

Return Air Plenum

The DVHVAC36 is equipped with a 16" x 16"  (256 x 
256 mm) return air duct connection. Size and install the 
return air system using industry approved standards 
that result in a quiet and low static system.

Air Conditioning

The coil cabinet has been sized to fit most major brands 
of evaporator coil. (Fig. 6) The brackets supplied inside 
the coil cabinet represent the lowest height above the 
fireplace cabinet that the coil may be mounted. For best 
results, it is recommended that low air restriction types 

Summary of Contents for DVHVAC36

Page 1: ...cannot reach your gas supplier call the re department WARNING IF THE INFORMATION IN THIS MANUAL IS NOT FOLLOWED EXACTLY A FIRE OR EXPLOSION MAY RESULT CAUSING PROPERTY DAMAGE PERSONAL INJURY OR LOSS...

Page 2: ...eral Venting 9 General Venting Information Termination Location 10 General Information Assembling Vent Pipes 11 Twist Lock Pipes 11 How to Use the Vent Graph 12 Sidewall Venting Graph 12 Corner Instal...

Page 3: ...at the gas valve and pilot light are turned off before you attempt to clean this re place 7 The venting system chimney of this replace should be checked at least once a year and if needed your venting...

Page 4: ...ci cations Ref DVHVAC36 Ref DVHVAC36 A 36 914 mm N 9 245 mm B 34 870 mm O 6 175 mm C 21 533 mm P 2 58 mm D 33 838 mm Q 2 51 mm E 63 1621 mm R 3 97 mm F 70 1780 mm S 4 102 mm G 16 410 mm T 1 2 13 mm H...

Page 5: ...Remove the access panel on the front of the air cir culating blower section by removing the 10 24 nuts Remove the jack plug from the air circulating blower motor by gently depressing tab 5 Attach the...

Page 6: ...depth to suit facing material adjustable to 1 2 5 8 or 3 4 depths Fig 4 5 Screw through slotted holes in drywall strip and then screw into pre drilled holes on replace side Meas ure from face of repl...

Page 7: ...f any part of it has been under water Immediately call a quali ed service technician to inspect the replace and replace any part of the control which has been under water Gas Inlet Manifold Pressures...

Page 8: ...test point therefore it is not necessary to pro vide a 1 8 test point up stream of the control When using copper or ex connector use only approved ttings When using black iron pipe always provide a un...

Page 9: ...BLUE R W1 G Y GND CHASSIS GND 24 VAC RTN 24 VAC HOT TH TP PILE TH PILE THERMOPILE GAS VALVE TP TH TP TH EMERGENCY HEAT SWITCH 14 YELLOW 15 BLUE 13 BLUE 12 YELLOW RED WHITE L1 L2 TP TH TH LIMIT 16 YELL...

Page 10: ...3 91cm J Clearance to nonmechanical air supply inlet 6 15cm for appliances 10 000 6 15cm for appliances to building or the combustion air inlet to any Btuh 3kW 12 30cm for 10 000 Btuh 3kW 9 other app...

Page 11: ...suggest putting a lubricant Vaseline or similar on the male end of the twist lock pipe prior to assembly TWL100 Twist Lock Pipe 3 12 99 djt Male End Female End Screw Holes TWL100 Fig 11 Twist lock pip...

Page 12: ...se applications Refer to Venting Components listed for different installation requirements The maximum horizontal distance between the rear of the appliance and the outside face of the rear wall is 20...

Page 13: ...rmination 4 collar into the 4 pipe then the 7 collar into the 7 pipe Do not force the venting into position If the pipes do not line up with the termina tion collars disassemble elbows or pipes and re...

Page 14: ...alled in either the vertical or horizontal run When one 1 90 elbow is installed directly onto another off the back of the replace the maximum horizontal vent length is 36 914 mm Fig 19 For each 45 elb...

Page 15: ...4 100 Vent Opening 2 99 djt Vent Opening for Combustible Wall 9 240 mm 9 240 mm Fireplace Hearth Framing Detail Vent Opening for Noncombustible Wall 7 190 mm VO584 100 Fig 22 Locate vent opening on wa...

Page 16: ...uirement STEP 7 Support the horizontal pipes every 36 914 mm with metal pipe straps Make sure the horizontal vent pipe is installed on a level horizontal plane STEP 8 Re check the replace to make sure...

Page 17: ...pe Straps Every 3 914mm CFM148 Fig 30 Support straps for horizontal runs Up to two 2 45 elbows may be used within the horizontal run For each 45 elbow used on the hori zontal level the maximum horizon...

Page 18: ...and 7 collars of vertical vent termination and install If there is a room above ceiling level restop spacers must be installed on both the bottom and the top side of the ceiling joists If an attic is...

Page 19: ...ustable length 7TDVP3566 35 to 64 adjustable length Pipe sections for vertical or horizontal venting Model 7TDVP8 Model 7TDVP12 Model 7TDVP24 Model 7TDVP36 Model 7TDVP48 Firestop Spacer Model 7DVFS At...

Page 20: ...other airborne particles to cling to the glass surface Also initial paint curing may deposit a slight lm on the glass It is therefore recommended the glass FP1405 DVHVAC remove glass frame 8 03 Clamps...

Page 21: ...to the ON position This will turn on the replace burner in a low re condition The unit will provide heat to the room in which the replace is installed When power is restored toggle the emergency heat...

Page 22: ...and logs 2 Place refractory side supports so that the hole ts over the screw head on the rebox oor 3 Place refractory base sides on the oor of the re box 4 Attach adjustable tabs packed with refracto...

Page 23: ...the oor because some gas is heavier than air and will settle on the oor WHAT TO DO IF YOU SMELL GAS Do not try to light any replace Do not touch any electric switch Do not use any phone in your buildi...

Page 24: ...An interrupter block not supplied must be used to conduct this test 3 Pilot burning no gas to A Thermostat or wires defective Check wall switch and wires for proper connections main burner Valve knob...

Page 25: ...tem consist of burner tube gas ori ce pilot assembly thermopile millivolt gas valve Most of these components may require only an occasional checkup and cleaning and some may require adjustment If repa...

Page 26: ...C parts 7 02 4a b 1e 1f 1d 1c 1b 1a 1195 CFM Corporation reserves the right to make changes in design materials speci cations prices and discontinue colors and products at any time without notice DVHV...

Page 27: ...t 54273 8b Ori ce Pilot Prop 54272 9 Pilot 3 Way 10001295 10 Pilot Tubing w ttings 53211 11 Manifold Tubing w ttings 57318 12 Thermocouple 53373 13 Thermopile 51827 14 Electrode Ignitor w cable 100012...

Page 28: ...ang bay window assembly over existing window frame assembly Do not remove existing window frame as sembly 6 Re install upper louvre assembly Remove all plastic from brass trims 7 Bottom brass trim is...

Page 29: ...29 DVHVAC36 10001195...

Page 30: ......

Page 31: ...mageisfoundtobethefaultofthemanufacturer repairs will be authorized at no charge to the customer parts and or labor Any part and or component replaced under the provisions of this warranty is covered...

Page 32: ...EnerGuide Ratings Steady State D O E Fireplace Ef ciency Fan OFF Fan ON AFUE DVHVAC36RN 76 83 84 77 1 DVHVAC36RP 76 84 85 77 1 410 Admiral Blvd Mississauga Ontario Canada L5T 2N6 800 668 5323 www cfmc...

Reviews: