33
DVB4136 Direct Vent Gas Fireplace
20012322
������
������������������������
����
Continuous PIlot
Off/On Switch
Remote/Off
Switch
“S” Pilot Connection
“I” Pilot
Connection
FP1762
Figure 60: AF4000
MOD Module Right
Side
Pilot flame is always on/ will
not extinguish
•
Ensure the CONTINUOUS PILOT switch on the control module (Fig. 60) is set to
OFF.
•
Verify the gas supply is turned on.
•
Ensure the pilot flame will ignite. If not, see pilot flame troubleshooting above.
•
Make sure the green and white leads from the module are securely connected to
the terminals labeled “MAIN: on the valve body. (Fig. 62)
•
Make certain the pilot flame is in contact with the flame rectification sensor on the
pilot assembly. This valve is equipped with a pilot flame adjustment screw. (Fig.
62) If the pilot flame is too small it will not contact the flame rectification sensor
and will not complete the safety circuit.
•
Ensure the pilot flame is properly located to ignite the main flame.
•
Check continuity of main burner coil in gas valve. Remove wire connector. If there
is no continuity, replace valve.
Main flame will not light
Troubleshooting AF4000 Valve
(continued)
������
�����������������
����
6 Volt DC Adapter
Power Connection
8 Pin IPI
Connection
FP1764
Figure 61: AF4000 MOD Module End
Inlet
PILOT
Pilot Adj.
Outlet
MAIN
FP1769
AF4000 valve face
2/07
��
��
Figure 62: AF4000 Valve Face
Main Connection
Pilot Connection
FP1769