Caution:
The AC conducting wires shall be flame-retardant and routed as specified in the
Code for Fire Protection Design of Tall Buildings
(GB50045-95). In the event of
low-voltage distribution, it shall be implemented in accordance with the
Code for
Design of Low Voltage Power Distribution Installations and Wiring Systems
(GB50045-95).
The devices adopting the DC power supply include MP1800X-40, MP1800X-40W,
MP1800X-40E, and SJW12-4G.
D2.3
Suggestions on fundamental AC power supply
Suggestions on fundamental AC power supply include:
If the equipment is directly powered by mains supply, and its power supply voltage
exceeds -10%~5% of the rated voltage, or the voltage range allowed for the
equipment, a voltage regulation device shall be used to meet the requirements.
In case the communication load requires uninterruptible or transient-free AC, the
UPS or inverter power supply system shall be used.
In the case of abnormity of the mains supply, the telecommunication bureau
(station) shall equip self-provided electric generator set as self-contained power
supply, to guarantee important communication load and important power load. The
capacity thereof shall be checked to be not less than 1.5-2 times the total capacity
of the AC incessant consumers.