Not enough draught
►
Check ventilation flap, funktion radial fan,
draught free
Flue gas sensor or flamm-
roomtemperature-sensor
soiled
►
Check Flue gas sensor or flammroom-tem-
perature-sensor
Display:
[5036] PE Flame supervision fault
Description:
Flame supervision fault, minimum flue gas temperature not reached during
heating up at full power – Input FRT
Cause and Remedy:
No pellets available
►
Fill up with pellets
13.15 Flame return gate BSK (5038, 5039, 5040)
Display:
[5038] PE Flame return gate open
Description:
Flame return gate open fault (BSK - 1 2)
Cause and Remedy:
Flame return gate
unplugged
►
Connect up flame return gate and check
cable connections
Flame return gate does
not reach OPEN limit
switch
►
Check ball valve to see if it is jammed
No signal although open
►
Check cables and flame return gate
STB on the burner has
triggered
►
Surface temperature of the burner is too
high
Display:
[5039] PE Flame return gate closed
Description:
Flame return gate open fault
Cause and Remedy:
Flame return gate
unplugged
►
Connect up flame return gate and check
cable connections
Flame return gate does
not reach CLOSE limit
switch
►
Check whether ball valve is jammed, check
ball valve throughway to see if foreign ob-
jects are preventing it from closing
No signal although closed
►
Check cables and flame return gate
STB on the burner has
triggered
►
Surface temperature of the burner is too
high. The boiler switches to fault mode.
Display:
[5040] PE Flame return gate limit switch
Description:
Both flame return gate limit switches (BSK 1-2 and BSK 3-4) are closed at the
same time
Cause and Remedy:
Both limit switches
activated
►
Check flame return gate, check cables, check
connectors
13.16 Suction system (Fault 5043)
Display:
Suction system
Description:
Hopper cannot be filled up even after 3 suction cycles
Cause and Remedy:
Storage room empty
►
Fill up with pellets
Extraction system is
blocked
►
Clear extraction system
Operating Manual AutoPellet® PES 20, 32, 56
Summary of Contents for PES 20
Page 26: ...PE 568 USA 2 0 26 Setting language date and time at Pelletronic Touch...
Page 32: ...Menu navigation of Pelletronic Touch PE 568 USA 2 0 32 Main Menu...
Page 57: ...Favorite 57 Operating Manual AutoPellet PES 20 32 56...
Page 92: ...PE S K B 36 56 PE 568 USA 2 0 92 Cleaning the boiler every year...
Page 100: ......
Page 101: ......