46
UK | 7 System features
7.3 PPB 30 K/RC
The PPB 30 K unit works like the PPB 30 O
described above, but has the following addi-
tional functions:
● The PPB 30 K has an integrated humidity
sensor as standard. The internal sensor’s
value is always used for the humidity
measurement. Measurements from other
sensors connected to the RLS 45 K are not
taken into account.
● For dehumidification mode, intensive venti
-
lation (IL) or the exhaust air function (ABL)
can be set:
PPB 30 K
commissioning software
PPB 30 RC
service mode
● The PPB 30 K/RC has 2 operating modes
with different functionalities: Automatic
operation (regulation) or system operation
(exceeding of limit value).
The operating mode appropriate for your
PPB 30 K can be selected and set via the
commissioning software. For PPB 30 RC
the setting is made in service mode. For
more information
chapter 14.
7.4 Wired room air control RLS 45 O /
RLS 45 K
i
Combinations of RLS 45 O and
PPB 30 K are not permitted.
Each
RLS 45 O
can control up to 6 fans, for
example 6x PP 45 units or 3x PPB 30 O units.
A
mixture of systems
on one RLS 45 O
control is
not
permitted
.
Each
RLS 45 K
can control up to 6 fans, for
example 6x PP 45, 3x PPB 30 O/K or a mix
-
ture of PPB 30 K and PP 45 units.
All settings are undertaken and unit statuses
displayed on the RLS. RLS 45 K with com
-
missioning software. PP 45 O, PP 45 K and
PPB 30 O are connected to connections Fan1
and Fan2. PPB 30 K are only connected with
RS 485 bus.
7.5 Radio system from PP 45 RC/
PPB 30 RC units
●
Each PP 45 RC/PPB 30 RC ventilation unit
is equipped with a radio module.
● The RC units are operated with a DS 45 RC
radio switch. This can be simply glued to
the installation location on the wall.
● Alternatively, wired combination systems
with EnOcean module PP 45 EO can be
used. These are then operated using the
RLS 45 K control.
● The radio system can be extended with a
PP 45 Act 1-channel radio actuator for the
“Supply air for exhaust air units” function.
For connection
Radio actuator assembly
instructions, for further details see chapter
10.4.
Master-slave operation
●
With radio-controlled systems, associated
PP 45 unit pairs
work in
master-slave mode
.
● Slave units (RC ventilation units, radio
sensors, radio switches etc.) are learned-in
on the master unit. The master unit is then
responsible for the handling with the slave
unit
chapter 10.2.
● Only one slave unit can be assigned to
each master ventilation unit.
● Slave ventilation units are connected to the
master.
● Other components (radio sensors, radio
switches etc.) are only learned-in on the
master unit.
● To learn-in EnOcean components
Operating instructions, chapter 7.
7.6 Service mode
Mode intended for the specialist installer
to set and set up the unit functions and to
register wired sensors
Commissioning
instructions.
The commissioning software can also be
used with the RLS 45 K control.