Maico BSB FSD-C Series Installation, Operation And Maintenance Instructions Download Page 13

10 Commissioning, Maintenance and Test

1

2

 

 Fault Finding 

Symptom 

Fault 

Corrective Action 

Damper not in its 

‘normal’ state or 

Green LED on the 

Thermal 

 Fuse 

(TF) is not 

illuminated 

No power / incorrect 

supply 

Check supply/terminations Check signal 

connections 
If open circuit, replace probe 

Actuator faulty

TF  tripped.  Remove 

TF

 from duct, separate 

two halves,

 continuity

 

check the two contacts 

within the probe 

section (or test with 

new probe)

Replace 

Damper does not 

travel fully open / 

closed 

Damper seized

(Check 

that the mid point function 

is not set)

 

Clean and lubricate. 

Operate manually a 

couple of times then remove any excess 

lubricant.

Casing 

dented/damaged or 

not round 

Minor damage may be corrected carefully 

with a mallet. (BSB always recommend 

replacement of damaged dampers) 

Foreign body 

interfering with blade 

sweep (commonly

 

rivet or screw)

 

Inspect inside of damper case. Remove 

any offending item 

Damper blade and/

or actuator does 

not move open 

D

amper internals have 

been exposed to 

excessive moisture 

Report and log any damage found with actions to be taken.

 

Gently apply pressure to blade by hand to 

move open. Use Scotch Bright pad RED 

07447 grade, wet with duck oil and clean 

the damper internally at the point where 

the blade closes. Wipe dry and leave 

clean. 

‘Massage’ exposed peripheral blade seal 

until pliable.

10.1  

Pre-check BEFORE power is established – Check the actuator voltage is 

suitable for the application. 24V has a grey case, 230V has an orange case.

10.2 

In accordance with BS9999 Annex W.1, inspections should be undertaken at 

least annually, or more frequently where corrosive or dirty conditions prevail. 

The maintenance log should be reviewed at each inspection and the 

frequency adjusted as required dependent upon findings. (BSB also 

recommend a maximum of 1 year between inspections which should start 

more frequently initially and reduce frequencies only if conditions are proven 

to allow).

10.3 

Check damper is in its 'normal state'.

10.4 

If damper is not in its 'normal state', refer to fault finding chart otherwise 

continue.

10.5 

As a pre-check BEFORE power is established – When the actuator 

orientation has been changed or the actuator has been replaced, it should be 

wound manually using the manual reset. If resistance is encountered – over-

winding can result in permanent damage to the damper which may invalidate 

the warranty.

10.6 

The actuator can be 'locked' open by winding manually with key provided, 

then locked and also released by rotating the black lever (next to the golden 

symbol) on face of actuator.

10.7 

Switch to power to actuator. LED on TF will illuminate, and actuator will start 

on travel to DRIVE-END position. After 60 seconds, visually check that 

damper blade position and signaling corresponds.

10.8 

IMPORTANT: Press and hold test switch button on the TF to allow damper 

to travel to its closed position. Visually check that the damper blade position 

and signal corresponds. (This is to ensure that the actuator functions 

electrically and overrides the manual reset facility, should it have been used, 

as it is feasible to leave the damper inadvertently reset without the TF being 

functional if this test is not carried out)

10.9 

Release TF button to allow damper to drive to normal position.

10.10  If damper has seized – Open the damper (even partially if possible). Clean 

the inside of the damper case where the blade seals make contact. Use a 

soft cloth with a light application of light lubricant (Connect Duck Oil 

recommended). From the outside of the case, lightly apply a light lubricant 

into blade axle bearings. Remove excess lubricant.

10.11  It is important to log, and review maintenance frequency based on 

inspections and test history.

10.12  Use of heavy oils is not permitted, as this can lead to a build-up of dust/dirt 

on damper surfaces.

10.13  The PML actuator is maintenance-free.

6

12

Summary of Contents for BSB FSD-C Series

Page 1: ...E READ IN THEIR ENTIRETY BEFORE COMMENCING WORK TO ENSURE COMPLIANCE BEFORE COMMENCING WORK TO ENSURE COMPLIANCE Dampers will only be CE marked if Installed as tested These instructions are followed A...

Page 2: ...il required Dampers are designed for installation within internal normal dry filtered H V systems 1 FSD C Damper Installation Operating Maintenance Instructions 1 Health and Safety 1 1 Only competent...

Page 3: ...SD C M9 6 1 Preferably prepare opening whilst building wall or cut opening if wall already exists 3 Equipment required 3 1 Equipment and tools will vary dependent upon the fire barrier construction th...

Page 4: ...trally in wall opening width height Using drywall screws fix Installation Plate to wall using drywall screws Important Ensure the screws pick up the track lining the aperture so that the proper fire i...

Page 5: ...pping blunt point screws quantity to suit damper size These are optional accessories at the time of purchase of dampers 7 2 Prepare and install damper into position 7 2 1 Remove the clamp plate from t...

Page 6: ...damper cleats and join to upper drop rods with a coupling nut and lock nuts as per view C of the installation drawing 7 2 13 Fit a pair of M10 nuts to each lower drop rod underneath the damper bottom...

Page 7: ...al and ST4 8x19 safety self tapping screws 7 3 9 Tighten all screws to securely sandwich the FFC material 7 3 10 If necessary for aesthetic purposes only trim any excess FFC material protruding near t...

Page 8: ...n new position w wi it th ho ou ut t changing the blade s position Secure with the 10mm AF head screws 5Nm followed by the set point assembly and 8mm AF head screw 3Nm Test refer to section 12 9 Setti...

Page 9: ...Closed use 1 2 open when not fully open use 4 6 open indication when mid set point function use 1 3 8 5 8 6 Retighten the retaining screw to approx 3Nm Re apply power and check desired open position...

Page 10: ...11 Actuator and Thermal Fuse Access Maintenance Install zone 5 Default Position 2 9...

Page 11: ...zones in the below images d and blue zones in the below images 10...

Page 12: ...can lead to a build up of dust dirt on damper surfaces 12 13 The PML actuator is maintenance free 6 10 Commissioning Maintenance and Test 10 1 Pre check BEFORE power is established Check the actuator...

Page 13: ...a couple of times then remove any excess lubricant Casing dented damaged or not round Minor damage may be corrected carefully with a mallet BSB always recommend replacement of damaged dampers Foreign...

Page 14: ...Electrical details 24V Grey actuator case 230V Orange actuator case 13...

Page 15: ...Print name Signature Company Date Actuator mid point setting circle if applicable 30 35 40 45 50 55 60 65 70 75 80 85 90 FAIL SAFE POSITION POWER OFF position Tick appropriate FINAL INSPECTION BY Prin...

Page 16: ...sult from continuous product development The information contained within this brochure is correct at the time of going to press For full details of the complete BSB Product Range please refer to our...

Reviews: