ELECTRICAL INSTALLATION
For both 24vdc and 90vdc devices:
1. Connect vdc power source to the terminals marked 1, 2.
2. Connect protective grounding circuit* to the terminal marked with the P.E. symbol .
*
NOTE:
Both the functional-earth and protective-earth connections to ground are mandatory. The protective-earth
ground connection is required for safety and regulatory compliance. The functional-earth ground connection is
required for noise immunity, reliability, and Electromagnetic Compliance (EMC) with the European Union (EU) EMC
directive for CE-mark conformance.
RATED COIL CURRENTS
NOTE:
The coil system has been changed from Class A to Class F. Refer to the nameplate on your unit to
determine which insulation class you have. If you have Class F insulation, the nameplate will denote Class F. If you
have Class A, there will be no notation on the nameplate.
Maximum Current @ 0°C, adc
Maximum Current @ 0°C, adc
Supply Voltage, vdc
Supply Voltage, vdc
0 - 24
0 - 90
0 - 24
0 - 90
Model
Class A
Class F
Class A
Class F
Model
Class A
Class F
Class A
Class F
GBA, GBAM
0.94
1.32
0.25
0.28
GCA, GCAM
0.94
1.32
0.25
0.28
GBB, GBBM
1.06
1.75
0.28
0.37
GCB, GCBM
1.06
1.75
0.28
0.37
GBC, GBCM
1.56
2.06
0.42
0.55
GCC, GCCM
1.56
2.06
0.42
0.55
GBD, GBDM
2.03
2.68
0.54
0.69
GCD, GCDM
2.03
2.68
0.54
0.69
GBE, GBEM
---
2.76
---
0.80
Rated Current, adc
Rated Current, adc
Supply Voltage, vdc
Supply Voltage, vdc
0 - 24
0 - 90
0 - 24
0 - 90
Model
Class F
Class F
Model
Class F
Class F
GBA, GBAM
0.76
0.16
GCA, GCAM
0.76
0.16
GBB, GBBM
1.00
0.21
GCB, GCBM
1.00
0.21
GBC, GBCM
1.18
0.32
GCC, GCCM
1.18
0.32
GBD, GBDM
1.54
0.39
GCD, GCDM
1.54
0.39
GBE, GBEM
1.58
0.46
GCE, GCEM
1.58
0.46
ENVIRONMENTAL SPECIFICATIONS
Temperature Range:
Operating
0°C to 40°C
Storage
-30° to +80°C
Relative Humidity:
5% to 85%
Pollution Degree:
2 (IEC664-1)
Altitude:
0 to 2000 meters