9

 
9.2 Dancer 

Applications 

 

Symptom 

Possible Cause 

Solution or Diagnostic 

No AC power. 
 

Verify incoming power is correct 
voltage and frequency. 
 

Fuses blown. 

Clutch / Brake wires shorted together 
or shorted to ground. 
 

Clutch / Brake wires open 
circuit. 

Disconnect clutch / brake wires at the 
DFC-90 and check for proper clutch / 
brake resistance between the wires. 
 

No clutch / brake 
output. 

Jumper not installed 
between 20 and 21. 

Install jumper between terminals 20 
and 21. 

DFP or DFP-2 sensor not 
wired properly or wires 
shorted. 

Verify DFP or DFP-2 sensor is wired 
properly and follow the calibration 
procedure in section 6.3. 
 
Voltage between terminals 24 and 26 
should be 10 vdc. 
 
Voltage between terminals 25 and 26 
should change as the DFP or DFP-2 
is moved through its travel. 

Dancer not calibrated. 

Follow the calibration procedure in 
section 6.3. 

Clutch / Brake 
output full on or full 
off. 

DFC-90 in 

PID

 mode and 

RUN/STOP switch is not 
wired properly. 

Verify RUN/STOP switch wiring.  

PID

 

mode needs a RUN/STOP switch for 
proper operation. 

RUN/STOP switch not 
connected or not wired 
properly. 

Verify RUN/STOP switch wiring. 

Clutch / Brake 
output does not 
increase during 
stop time. 

STOP MULT

iplier 

potentiometer not set 
properly. 

Turn 

STOP MULT

 potentiometer 

clockwise to increase the stopping 
torque. 

Dancer arm hunting 
during stopping. 

STOP MULT

iplier is being 

used. 

Turn 

STOP MULT

 potentiometer 

counter clockwise to decrease the 
hunting during stopping.  See Stop 
Multiplier note at end of section 6.3. 

Incorrect type of meter. 

Meter should be a current meter with  
1 ma full scale and no more than  
3 kohm resistance. 

Remote meter not 
working. 

Meter wires shorted or 
open. 

Disconnect meter wiring at the DFC-
90 and check for proper meter 
resistance between the wires. 

 
 

Summary of Contents for DFC-90

Page 1: ...current ranges Maximum outputs for the individual ranges are 0 125 0 25 0 5 and 1 0 adc The appropriate range is determined by the current rating of the clutch or brake to be controlled For best torq...

Page 2: ...the IP rating The enclosure may be opened by inserting a flat blade screwdriver under the retaining tabs in the base See figure 2 5 0 Follower Arm Applications 5 1 Electrical Connections Figure 5 sho...

Page 3: ...is half way through its travel DFP 2 To find the electrical center point of pot rotation use a digital multimeter type ohm meter to measure from the white wire wiper to the red or black wire Turn the...

Page 4: ...lete and the DFC 90 is ready for operation Optional adjustments Stop Multiplier and Stop Time The STOP MULT pot can be used to increase the torque while the machine is stopping The increased torque is...

Page 5: ...are isolated and may be ground referenced Figure 7 Dancer Electrical Connections 6 2 Sensor Setup The DFP or DFP 2 position sensor should be at the center of rotation when the dancer is halfway throu...

Page 6: ...achine stopped set the switch to This turns the integrator on 7 Run the machine near full roll and at a slow speed and use the pot to center the dancer Clockwise rotation of moves the dancer up toward...

Page 7: ...e dancer is overshooting To do this move the stable dancer away from its set position by pushing on the dancer by bumping the unwind rewind roll or by some similar means If the dancer goes past the se...

Page 8: ...tion 5 3 Voltage between terminals 20 and 22 should be greater than zero and should change as the DFP or DFP 2 is moved through its travel Remote tension potentiometer resistance is less than 10 kohms...

Page 9: ...not calibrated Follow the calibration procedure in section 6 3 Clutch Brake output full on or full off DFC 90 in PID mode and RUN STOP switch is not wired properly Verify RUN STOP switch wiring PID m...

Page 10: ...Residual Current Device Types A or B IEC755 Worst Case Fault Current 1 6 amp ac Inputs Signal DFP or DFP 2 Potentiometer 1 to 10 kohm watt minimum Tension Potentiometer 10 kohm minimum watt minimum R...