Magnetrol STI Echotel Trident 91S Instruction Manual And Parts List Download Page 11

11

RELAY WIRING

Model 91S/92S units have a number of different relay wiring
options. The table below lists relay contact positions for all
possible combinations of power failure, state of the trans-
ducer gap and failsafe switch position. Each user must
decide, from consideration of the overall system, which
combinations of the above constitutes failsafe and alarm
conditions; and, select the appropriate relay wiring and fail-
safe positions.

*

Failsafe jumper on amplifier should be kept in low position if it 
is a relay 91S.

POWER SUPPLY BOARD USER SELECTIONS

Failsafe

Failsafe

Sensor

Jumper

Jumper 

Alarm

Malfunction

Gap

on

on Power

Relay

Relay

Condition Amplifier*

Supply*

(P2)

(P1)

Wet

L

L

Energized

Energized

Dry

L

L

De-Energized

Energized

Malfunction

L

L

De-Energized

De-Energized

Wet

H

H

De-Energized

Energized

Dry

H

H

Energized

Energized

Malfunction

H

H

De-Energized

De-Energized

Relay Wiring Chart—91S only

Designation

Function

Action

Allows energized state of 

High (H) or 

alarm relay to set for wet or 

P1

Low (L) level

dry condition.

failsafe

H = de-energized when wet
L = de-energized when dry

J = alarm relay will always 
de-energize with a malfunction.

Joint (J) or

I = with a malfunction &

P2*

Independent (I)

failsafe jumper (P1) in

Malfunction

(H) position, alarm relay will
energize (or remain energized 
if sensor was dry when 
malfunction was detected)

Selector switch definitions on power supply 
board—91S only

The malfunction relay always de-energizes on a fault detection.

AMPLIFIER BOARD 

USER SELECTION DESIGNATIONS

WET LED (LED1)
An LED which illuminates red when liquid fills the sensor tip
or gap.

DRY LED (LED2)
An LED which illuminates green when air is in the sensor tip
or gap.

Time Delay Potentiometer (R31)
The adjustable time delay (R31) can be variable from 0.5 to
30 seconds. This can be used under turbulent conditions to
reduce relay chattering.

High/Low Level Failsafe (P2 Jumper)
The term failsafe denotes the position the relay contacts
assume when power to the unit is lost. To set a high level
failsafe (relay energized dry), place jumper between middle
pin and (HIGH) pin on P2. To set low level failsafe (relay ener-
gized wet), place jumper between middle pin and (LOW) pin.

Time Delay on Rising and/or Falling Jumper (P1)
The jumper (P1) can be set to delay on rising or to delay
falling level. Setting in the (RISING) position adjusts the
delay on a dry to wet transition with a fixed 0.5 second
delay on a wet to dry transition. Set in the (FALLING) posi-
tion adjusts the delay on a wet to dry transition with a fixed
0.5 second delay on a dry to wet transition. Totally removing
jumper provides delay on rising and falling level.

Auto Fill/Auto Empty Selection (P1–Dual point)
A jumper which allows the selection of an automatic fill or
automatic empty function.

Control–Malfunction Relay Action (P2–Dual point)
A jumper which allows joint or independent actuation of the
control and malfunction relay. Independent (IND) allows
separate action of each relay while joint (JOINT) ties the
control with malfunction together if either changes state.

Top Point Relay LED (DS2)
An LED on the 92S power supply board which illuminates
red when control relay tied to top point changes state.

Bottom Point Relay LED (DS3)
An LED on the 92S power supply board which illuminates
red when the control relay tied to the bottom point ener-
gizes.

Malfunction Relay LED (91S–DS2, 92S–DS1)
An LED on the power supply illuminates red when the mal-
function relay is energized, indicating a normal condition. In
case of a failure, light will go off.

Control Function Switch (92S–S2)
A three position switch which allows the user to select the
control function of the dual point unit. Select from simple
B o t t o m P o i n t – T o p P o i n t o p e r a t i o n , C o n t r o l
Function–Bottom Point, or Control Function–Top Point.

TIME DELAY

All Model 91S/92S units are provided with an adjustable
time delay of approximately 0.5 to 30 seconds. The time
delay potentiometer is on the upper right corner of the
amplifier PC board and marked TIME DELAY. There is a
jumper selector marked P1 on the amplifier board. This is
the wet and/or dry time delay. The time delay can be made
on rising and/or falling level. When the jumper is placed in
the (RISING) position, there will be an adjustable delay on a
dry to wet transition, with a fixed 0.5 second delay on wet
to dry transition. When the jumper is set in the (FALLING)
position, the delay will be on a wet to dry transition with a
fixed delay of 0.5 seconds on a dry to wet transition. If no
jumper is placed on the pins, the delay will be in both direc-
tions. Minimum time delay occurs with potentiometer
adjustment fully counterclockwise. Increase time delay by
turning clockwise. Refer to Figure 9 on page 8.

POWER SUPPLY BOARD 

USER SELECTION DESIGNATIONS

Summary of Contents for STI Echotel Trident 91S

Page 1: ...num sand cast 3 4 NPT dual conduit E NEMA 4X 7 9 aluminum sand cast 3 4 NPT single conduit Y NEMA 4X 7 9 316 stainless steel 3 4 NPT single conduit 7 NEMA 4X 7 9 Group B aluminum die cast 1 NPT dual c...

Page 2: ...wire 8 or 16 mA current shift must use Input code 2 Input 0 120 VAC 1 240 VAC 2 24 VDC 3 12 VDC 5 48 VDC Housing E NEMA 4X 7 9 aluminum sand cast 3 4 NPT single conduit Y NEMA 4X 7 9 316 stainless st...

Page 3: ...be an audible click as the relay changes state Also the red LED marked LED1 WET on the amplifier board will illuminate Depending on how the unit is con figured the red LED marked DS1 on the power sup...

Page 4: ...R WIRING PROCEDURES NOTE IF REMOTE SELF TEST IS USED FOLLOW INSTRUCTIONS ON PAGE 6 8 If using the malfunction relay run wiring to lower portion of TB1 as shown in Figure 4 9 Replace housing cover CAUT...

Page 5: ...Output 120 240 VAC Power Supply Board Figure 6 91S Opto Isolated Output 24 VDC Power Supply Board FOUR WIRE MODELS RELAY OPTO ISOLATED INSTALLATION WIRING cont Malf Test Wet Test Common Remote Self T...

Page 6: ...and TB5 for dual point 2 Determine whether a manual test on a wet condition or malfunction is desirable See page 15 DO NOT WIRE SEPARATE 12 VDC POWER SOURCE TO GENERATE POWER FOR REMOTE PUSH BUTTON S...

Page 7: ...g the mounting bracket provided with order Provide adequate clearance to remove housing cover 2 Remove housing cover Transducer Housing Remote Electronics Mounting Bracket Process Vessel Coaxial Cable...

Page 8: ...XIAL CABLE INSTALLATION All 91S 92S remote units are equipped with a transducer housing as shown in Figure 8 The coaxial cables from the transducer will terminate inside the transducer housing in phon...

Page 9: ...board from a separate power supply 7 Dress wiring to guard against interference or contact with cover or circuit board components 8 Prevent moisture seepage into housing by installing an approved seal...

Page 10: ...over REMOTE TRANSDUCER INSTALLATION 1 Screw transducer into tank opening using pipe com pound or thread tape If flanged bolt unit to mating flange with proper gasket NOTE Refer to Coaxial Cable Instal...

Page 11: ...ling level Setting in the RISING position adjusts the delay on a dry to wet transition with a fixed 0 5 second delay on a wet to dry transition Set in the FALLING posi tion adjusts the delay on a wet...

Page 12: ...lly Close HL High Level CM Common CF Either Auto Fill or Auto Empty functions Function Action LED1 WET LED Illuminates red when wet 16 mA LED2 DRY LED Illuminates green when dry 8 mA Time delay RISING...

Page 13: ...LLFS P1 AUTO FILL S2 BP CF Function TB2 TB3 Both gaps dry off on bottom gap wet off off top gap wet on off top gap dry on off bottom gap dry off on S1 HLFS P1 AUTO EMPTY S2 BP CF Function TB2 TB3 Both...

Page 14: ...function test The power source for this push button test is internal to the 91S 92S NOTE Remote manual self testing is available on all four wire models It is not offered on the two wire models OPTO...

Page 15: ...power supply board illuminates when the malfunction relay is ener gized Refer to the failsafe jumper table and verify that the relay action is correct 5 If the manual self test operations indicate tha...

Page 16: ...two relays via a field selectable jumper Continuous Verifies operation of Self test electronics transducer and crystal Automatic and Manual bond integrity Also a local on demand self test to force a m...

Page 17: ...SPECIFICATIONS DIMENSIONAL SPECIFICATIONS inches mm 3 00 76 87 22 Dia NPT Process connection 3 4 NPT Conduit connection 1 12 28 6 87 175 Insertion length Figure 17 Integral Group B NEMA 4X 7 9 Housin...

Page 18: ...nsitive 316 SS Transducer 87 22 Dia NPT Process connection 3 4 NPT Conduit connection 1 12 28 6 87 175 Insertion length 3 00 76 SPECIFICATIONS cont 1 62 41 Actuation 87 22 Dia Actuation Length 3 00 76...

Page 19: ...PT NEMA 4X 7 9 316 Stainless steel 004 9140 002 Single conduit 3 4 NPT 7 Remote Transducer Housing Aluminum sand or die cast 004 9105 001 316 Stainless steel 004 9142 001 8 Remote Cover Seal O Ring 01...

Page 20: ...ards before it is returned to the factory A Material Safety Data Sheet MSDS must accompany material that was used in any media All shipments returned to the factory must be by prepaid transportation A...

Reviews: