91S Transducer

9

-

1

-

Transducer type 

(Material and unit of length)

= 316 SS in inches

= 316 SS in centimeters

= Monel or HC in inches

= Monel or HC in centimeters

Process connection

3

4

" NPT

= 1" NPT

= 1" 150 lb. flange

= 1

1

2

" 150 lb. flange

= 2" 150 lb. flange

= 1" 300 lb. flange

= 1

1

2

" 300 lb. flange

= 2" 300 lb. flange
= 1" 600 lb. flange

= 2" 600 lb. flange

Transducer material

22 = 316/316L stainless steel

HC = Hastelloy C

MM = Monel

Transducer length

Specify length in inches (from 1" to 130") or centimeters
(from 3 to 330 cm). Consult factory for lengths over
130". Minimum length is 2" (5 cm) for flange process
connections.

Echotel

®

Trident 91S/92S 

Ultrasonic Level Switches

Model 91S

Model 92S

®

Instruction Manual and Parts List

91S PART NUMBER CONSTRUCTION

Electronics

9 1 S 

-

1

Output Signal

A1A = 10 amp DPDT relay 

L1H = Opto-isolated output 

T1W = Two-wire, 8 or 16 mA current shift 

(must use Input code 2) 

Input

=

120 VAC

=

240 VAC

=

24 VDC

=

12 VDC

=

48 VDC

Housing

= NEMA 4X/7/9, aluminum sand cast, 

3

4

" NPT,

dual conduit

= NEMA 4X/7/9, aluminum sand cast, 

3

4

" NPT, 

single conduit

= NEMA 4X/7/9, 316 stainless steel, 

3

4

" NPT,

single conduit

= NEMA 4X/7/9 Group B, aluminum die cast, 1" NPT

dual conduit

Mounting

= Integral
= Remote (connecting cable required)

Connecting Cable

3 7 0 0 0

Cable Type

A1 = RG178 for 1 set point, 1–50 ft.
B1 = RG58 for 1 set point, 51-300 ft.

Cable Length

Length of cable from remote electronics to 
transducer in feet (300 feet max.)

MODEL IDENTIFICATION

Each unit has a nameplate on which the part number is
shown. The part number is coded to identify the configura-
tion of that specific unit. Listed below are the definitions of
each section of the part number, such that one can deter-
mine exactly which options the unit contains.

91S PART NUMBER CONSTRUCTION cont.

Model 91S with output signal option code A1A or L1H available with
housing option codes F or 7 only.

Model 91S with output signal option code T1W available with housing
option codes E or Y only.

316 SS Model 91S transducers have tip sensitive gaps as shown in
Figure 19 on page 17. Monel and Hastelloy C Model 91S transducers
have side gaps as shown in Figure 21 on page 18.

Summary of Contents for STI Echotel Trident 91S

Page 1: ...num sand cast 3 4 NPT dual conduit E NEMA 4X 7 9 aluminum sand cast 3 4 NPT single conduit Y NEMA 4X 7 9 316 stainless steel 3 4 NPT single conduit 7 NEMA 4X 7 9 Group B aluminum die cast 1 NPT dual c...

Page 2: ...wire 8 or 16 mA current shift must use Input code 2 Input 0 120 VAC 1 240 VAC 2 24 VDC 3 12 VDC 5 48 VDC Housing E NEMA 4X 7 9 aluminum sand cast 3 4 NPT single conduit Y NEMA 4X 7 9 316 stainless st...

Page 3: ...be an audible click as the relay changes state Also the red LED marked LED1 WET on the amplifier board will illuminate Depending on how the unit is con figured the red LED marked DS1 on the power sup...

Page 4: ...R WIRING PROCEDURES NOTE IF REMOTE SELF TEST IS USED FOLLOW INSTRUCTIONS ON PAGE 6 8 If using the malfunction relay run wiring to lower portion of TB1 as shown in Figure 4 9 Replace housing cover CAUT...

Page 5: ...Output 120 240 VAC Power Supply Board Figure 6 91S Opto Isolated Output 24 VDC Power Supply Board FOUR WIRE MODELS RELAY OPTO ISOLATED INSTALLATION WIRING cont Malf Test Wet Test Common Remote Self T...

Page 6: ...and TB5 for dual point 2 Determine whether a manual test on a wet condition or malfunction is desirable See page 15 DO NOT WIRE SEPARATE 12 VDC POWER SOURCE TO GENERATE POWER FOR REMOTE PUSH BUTTON S...

Page 7: ...g the mounting bracket provided with order Provide adequate clearance to remove housing cover 2 Remove housing cover Transducer Housing Remote Electronics Mounting Bracket Process Vessel Coaxial Cable...

Page 8: ...XIAL CABLE INSTALLATION All 91S 92S remote units are equipped with a transducer housing as shown in Figure 8 The coaxial cables from the transducer will terminate inside the transducer housing in phon...

Page 9: ...board from a separate power supply 7 Dress wiring to guard against interference or contact with cover or circuit board components 8 Prevent moisture seepage into housing by installing an approved seal...

Page 10: ...over REMOTE TRANSDUCER INSTALLATION 1 Screw transducer into tank opening using pipe com pound or thread tape If flanged bolt unit to mating flange with proper gasket NOTE Refer to Coaxial Cable Instal...

Page 11: ...ling level Setting in the RISING position adjusts the delay on a dry to wet transition with a fixed 0 5 second delay on a wet to dry transition Set in the FALLING posi tion adjusts the delay on a wet...

Page 12: ...lly Close HL High Level CM Common CF Either Auto Fill or Auto Empty functions Function Action LED1 WET LED Illuminates red when wet 16 mA LED2 DRY LED Illuminates green when dry 8 mA Time delay RISING...

Page 13: ...LLFS P1 AUTO FILL S2 BP CF Function TB2 TB3 Both gaps dry off on bottom gap wet off off top gap wet on off top gap dry on off bottom gap dry off on S1 HLFS P1 AUTO EMPTY S2 BP CF Function TB2 TB3 Both...

Page 14: ...function test The power source for this push button test is internal to the 91S 92S NOTE Remote manual self testing is available on all four wire models It is not offered on the two wire models OPTO...

Page 15: ...power supply board illuminates when the malfunction relay is ener gized Refer to the failsafe jumper table and verify that the relay action is correct 5 If the manual self test operations indicate tha...

Page 16: ...two relays via a field selectable jumper Continuous Verifies operation of Self test electronics transducer and crystal Automatic and Manual bond integrity Also a local on demand self test to force a m...

Page 17: ...SPECIFICATIONS DIMENSIONAL SPECIFICATIONS inches mm 3 00 76 87 22 Dia NPT Process connection 3 4 NPT Conduit connection 1 12 28 6 87 175 Insertion length Figure 17 Integral Group B NEMA 4X 7 9 Housin...

Page 18: ...nsitive 316 SS Transducer 87 22 Dia NPT Process connection 3 4 NPT Conduit connection 1 12 28 6 87 175 Insertion length 3 00 76 SPECIFICATIONS cont 1 62 41 Actuation 87 22 Dia Actuation Length 3 00 76...

Page 19: ...PT NEMA 4X 7 9 316 Stainless steel 004 9140 002 Single conduit 3 4 NPT 7 Remote Transducer Housing Aluminum sand or die cast 004 9105 001 316 Stainless steel 004 9142 001 8 Remote Cover Seal O Ring 01...

Page 20: ...ards before it is returned to the factory A Material Safety Data Sheet MSDS must accompany material that was used in any media All shipments returned to the factory must be by prepaid transportation A...

Reviews: