10
58-603 Pulsar
®
Model R86 Radar Transmitter
Level Units
Select the Units of measurement for the level output:
• Inches
• Feet
• Millimeters
• Centimeters
• Meters
Tank Height
Enter tank height (in Level Units selected)
Antenna Model
• RB1-x — 1½" horn
• RB2-x — 2" horn
• RB3-x — 3" horn
• RB4-x — 4" horn
Antenna Extension
0
For nozzle height
″
1" (25 mm) (for threaded process connection only; refer to antenna
nameplate):
1
For nozzle height 4" (100 mm)
2
For nozzle height 8" (200 mm)
3
For nozzle height 12" (300 mm)
4
For nozzle height 24" (600 mm)
5
For nozzle height 48" (1200 mm)
6
For nozzle height 72" (1800 mm)
Antenna Mount
Select the type of Antenna Mounting to the vessel (refer to antenna nameplate):
• NPT (National Pipe Thread)
• BSP (British Standard Pipe)
• Flange (ANSI or DIN)
Dielectric Range
Enter the Dielectric Range for the material to be measured.
Below 1.7 (light hydrocarbons like propane and butane; stillwell only)
1.7 to 3.0 (most typical hydrocarbons)
3.0 to 10 (varying dielectric, for example: mixing tanks)
Above 10 (water-based media)
H
A
R
T
O
n
ly
4 mA Set Point
(LRV)
Enter the level value (0%-point) for the 4 mA point. Lower Range Value (LRV).
Refer to Section 1.4.1.1.
20 mA Set Point
(URV)
Enter the level value (100%-point) for the 20 mA point. Upper Range Value (URV).
Refer to Section 1.4.1.1.
PV Alarm
Selection
Enter the desired output state when a Failure Indicator is active.
• High (22 mA)
• Low (3.6 mA)
• Hold (hold last value is not recommended for standard configuration). Consult factory.
1.4.1 Setup Wizard Menu Options