Screen

Action

Comment

Transmitter Display

Transmitter default display. Level, % Output, and Loop
values cycle every 5 seconds.

Transmitter Display

Transmitter displays Level measurement in cm or in.

Transmitter Display

Transmitter displays % Output measurement derived from the
4-20 mA span.

Transmitter Display

Transmitter displays Loop measurement (mA).

Select units for level

cm or inches.

measurement readout.

Enter level value of the low

Set level at low calibration point

calibration point

and adapt with Up and Down the displayed value

Transmitter Display

Transmitter displays capacitance at low calibration point in pF

Enter level value of the high

Set level at high calibration point

calibration point

and adapt with Up and Down the displayed value

Transmitter Display

Transmitter displays capacitance at high calibration point in pF

Enter the level value for the

4 mA level cannot be set at a lower level than the end of the probe

4 mA point.

Enter the level value for the

20 mA level cannot be set at a higher level than the top of the 

20 mA point.

probe

Enter the damping factor.

A Damping factor (1-45 seconds) may be added to smooth a 
noisy display and/or output due to turbulence.

Enter the default value.

Select 3.6 mA, 22 mA or HOLD (last value). 3.6 mA is not
valid if unit includes HART.

Enter HART ID number.

Select a HART poll address (0-15). Enter 0 for a single
transmitter installation.

Fine tune the 4 mA point.

Attach a mA meter to the output. If the output does not equal 
4.0 mA, adjust the value on the display to equal 4.00 mA.

Fine tune the 20 mA point.

Attach a mA meter to the output. If the output does not equal 
20.0 mA, adjust the value on the display to equal 20.00 mA.

Enter a mA Output value.

Set mA Output to any given value to perform loop test.

None, do not adjust.

Transmitter displays capacitance at present level

None, do not adjust.

Transmitter displays internal timing count with fixed capacitance
(factory diagnostic)

None, do not adjust.

Transmitter displays internal timing count with probe disconnected
(factory diagnostic)

None, do not adjust.

Transmitter displays internal timing count at present level
(factory diagnostic)

Reinitialize all values.

Reinitialize - choose YES to reset all configuration values
back to factory defaults.

None, do not adjust.

Transmitter displays version number of firmware

Enter new password.

Use arrows to select desired value. Values between 1 and
255

CALIBRATION - TRANSMITTER WITH LCD SCREENMENU: STEP BY STEP PROCEDURE

Run mode

Dia

gnostics

Configuration

1

2

3

4

5

6

7

8

9

10

11

12

13

14

15

16

17

18

19

20

22

*Level*

*%Output*

*Loop*

Level

xx.x cm

%Output

xx.x%

Loop

xx.xx mA

Units

xxx

Lo Cal

xxx.x lu

Lo Cap

Xxxx pF

Hi Cal

xxx.x lu

Hi Cap

Xxxx pF

Set 4mA

xxx.x

Set 20mA

xxx.x

Damping

xx sec

Fault

Choice

Poll Adr

xx

Trim 4

xxxx

Trim 20

xxxx

Loop Tst

xx.x mA

Prb Rdg

Xxxx pF

Osc Tst

Xxx tk

Opn Prb

xxxx tk

23

21

# Ticks

xxxx

Reint

xxx

Vern.nAa

= min. required calibration

24

New Pass

xxx

Summary of Contents for KOTRON SMART RF 805

Page 1: ...R F Capacitance Level Measurement Installation and Operating Manual KOTRON SMART RF MODEL 805 TRANSMITTER...

Page 2: ...and record the serial number for future reference when ordering parts MOUNTING Nameplate partnumber amplifier serial n tag n 2 cable entries one plugged M20 x 1 5 3 4 NPT or PG 13 5 Handtighten or us...

Page 3: ...local current meter Ex Non Ex Ex Non Ex Ex Non Ex CAUTION ALWAYS check for proper grounding Improper grounding will cause malfunction of the unit CALIBRATION NOTE When connected to an approved barrie...

Page 4: ...nt is the highest level from which the calibration is performed Hi Cal is measured from the end of the probe Lo Cal cm or inches Low Calibration point is the lowest level from which the cal ibration i...

Page 5: ...single transmitter installation Fine tune the 4 mA point Attach a mA meter to the output If the output does not equal 4 0 mA adjust the value on the display to equal 4 00 mA Fine tune the 20 mA point...

Page 6: ...oom Display Power Supply Current Meter 250 RL 450 CONNECTIONS Connection of your Hart communicator at power terminals and in wiring compartment at first junction box between unit and control room HART...

Page 7: ...y HART software does not Contact manufacturer of your HART information e g Mfgs ID Device account for Mfgs ID s greater master software for upgrade This is a Serial etc but will not read any than 63 M...

Page 8: ...3 003 Housing cover blind 316 SST Consult factory 5 Housing cover with glass 36 4410 001 Housing cover with glass 316 SST Consult factory 8 APPROVALS Agency Description ATEX II 1G EEx ia IIC T4 ambien...

Page 9: ...Electronic Module Yes Yes Yes Yes Yes Yes Yes No No No No No No Display has Text No Reseat Boards Check Power Supply and Wiring Loop Resistance Wrong Correct Loop Resistance Start Good Display No Act...

Page 10: ...lure to Operate with Correct Loop Inputs Display Working Yes No Retest Unit Good Display Key Board Responds Replace Electronic Module No Check Loop Current at Wiring Board Loop Current 22 4 0 mA Adjus...

Page 11: ...heck Calibration Parameters Yes Yes Yes Corrupt Display Text Replace Electronic Module No Yes Replace Electronic Module Same Error Message Retest No Yes Active HART Analog Loop Correct Trim 4 20mA Che...

Page 12: ...Material Aluminium A356T6 0 25 copper or 316 SST 1 4401 IP 65 Net and Gross Weight 2 70 kg net 3 20 kg gross Overall Dimensions H 214 mm 8 43 x W 111 mm 4 38 x D 188 mm 7 40 FUNCTIONAL PHYSICAL Descri...

Page 13: ...e view Optional Mounting Flange 3 4 NPT 1 NPT 1G 1 BSP Optional Mounting Flange Optional Anchor Assembly Optional Weight 13 0 50 bare probe 16 0 625 insulated probe 5 0 1875 6 0 2500 75 2 95 34 1 32 1...

Page 14: ...X II 1G EEx ia II C T6 A complete measuring system consists of a 1 Smart R F KOTRON 805 amplifier 2 KOTRON Probe a full range of rigid and flexible probes for conductive and non conductive media is av...

Page 15: ...15...

Page 16: ...Material Authorisation RMA form will be obtained from the factory It is mandatory that this form will be attached to each material returned This form is available through Magnetrol s local representat...

Reviews: