5
Screen
Action
Comment
Transmitter Display
Transmitter default display. Level, % Output, and Loop
values cycle every 5 seconds.
Transmitter Display
Transmitter displays Level measurement in cm or in.
Transmitter Display
Transmitter displays % Output measurement derived from the
4-20 mA span.
Transmitter Display
Transmitter displays Loop measurement (mA).
Select units for level
cm or inches.
measurement readout.
Enter level value of the low
Set level at low calibration point
calibration point
and adapt with Up and Down the displayed value
Transmitter Display
Transmitter displays capacitance at low calibration point in pF
Enter level value of the high
Set level at high calibration point
calibration point
and adapt with Up and Down the displayed value
Transmitter Display
Transmitter displays capacitance at high calibration point in pF
Enter the level value for the
4 mA level cannot be set at a lower level than the end of the probe
4 mA point.
Enter the level value for the
20 mA level cannot be set at a higher level than the top of the
20 mA point.
probe
Enter the damping factor.
A Damping factor (1-45 seconds) may be added to smooth a
noisy display and/or output due to turbulence.
Enter the default value.
Select 3.6 mA, 22 mA or HOLD (last value). 3.6 mA is not
valid if unit includes HART.
Enter HART ID number.
Select a HART poll address (0-15). Enter 0 for a single
transmitter installation.
Fine tune the 4 mA point.
Attach a mA meter to the output. If the output does not equal
4.0 mA, adjust the value on the display to equal 4.00 mA.
Fine tune the 20 mA point.
Attach a mA meter to the output. If the output does not equal
20.0 mA, adjust the value on the display to equal 20.00 mA.
Enter a mA Output value.
Set mA Output to any given value to perform loop test.
None, do not adjust.
Transmitter displays capacitance at present level
None, do not adjust.
Transmitter displays internal timing count with fixed capacitance
(factory diagnostic)
None, do not adjust.
Transmitter displays internal timing count with probe disconnected
(factory diagnostic)
None, do not adjust.
Transmitter displays internal timing count at present level
(factory diagnostic)
Reinitialize all values.
Reinitialize - choose YES to reset all configuration values
back to factory defaults.
None, do not adjust.
Transmitter displays version number of firmware
Enter new password.
Use arrows to select desired value. Values between 1 and
255
CALIBRATION - TRANSMITTER WITH LCD SCREENMENU: STEP BY STEP PROCEDURE
Run mode
Dia
gnostics
Configuration
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
22
*Level*
*%Output*
*Loop*
Level
xx.x cm
%Output
xx.x%
Loop
xx.xx mA
Units
xxx
Lo Cal
xxx.x lu
Lo Cap
Xxxx pF
Hi Cal
xxx.x lu
Hi Cap
Xxxx pF
Set 4mA
xxx.x
Set 20mA
xxx.x
Damping
xx sec
Fault
Choice
Poll Adr
xx
Trim 4
xxxx
Trim 20
xxxx
Loop Tst
xx.x mA
Prb Rdg
Xxxx pF
Osc Tst
Xxx tk
Opn Prb
xxxx tk
23
21
# Ticks
xxxx
Reint
xxx
Vern.nAa
= min. required calibration
24
New Pass
xxx