3.4.3 Digital Meter Calibration (cont.)
To position the decimal point and choose meter function:
3. Simultaneously press and immediately release the left and
right configuration buttons. See Figure 21.
4. To move the decimal point, press the left button until
decimal point is in desired location.
5. To choose meter function, press right button until desired
function is displayed. L in=linear, L inF=linear with five
second filter, Srt = Square root and SrtF = Square root with
five second filter.
6. Simultaneously press both configuration buttons for two
seconds to store chosen configurations.
To set 4 mA reading:
7. Press left button for two seconds.
8. Using the left button to decrease the reading and the right
to increase the reading, set display to the desired 4 mA
reading.
9. Simultaneously press both buttons to store the 4 mA
reading.
To set 20 mA reading:
10. Press right button for two seconds.
11. As in step 8 above, set display to desired 20 mA reading.
12. Simultaneously press both buttons to store the 20 mA
reading.
13. Replace transparent meter cover and transmitter junction
box cover.
3.4.4 Interface Calibration
3.4.4.1 Calibration in Process Liquids
IMPORTANT:
Displacer must always be completely sub-
merged in one or both process liquids.
1. Bring process up to operating temperature.
2. Establish interface level at desired 4 mA (10%) level
on the displacer. If 4 mA level is at the bottom of
the displacer, 4 mA point may be set with displacer
immersed in upper liquid only.
3. With unit power on, remove cover.
4. Press the ENTER key to start calibration. The
ZERO LED will light. Loop will go to 22 mA.
5. Press the DOWN key to lock in the 4 mA value.
The ZERO LED will flash and remain on. Loop will
stay at 22 mA.
6. Press ENTER to confirm the setting. The ZERO
LED will go off, and the loop will go to 4 mA.
19
48-618 ES/EZ Modulevel Displacer Level Transmitter (Top Hat Assembly Design)
%
Digital Display
Right Configuration
Button
Left Configuration
Button
Bar Graph
Figure 21
Digital Meter