Before You Begin

3.3.1 Site Preparation

Each Eclipse transmitter is built to match the specific physi-
cal specifications of the required installation. Make sure the
probe connection is correct for the threaded or flanged
mounting on the vessel or tank where the transmitter will
be placed. See Mounting, Section 3.4.

Make sure that the wiring between the power supply and
Eclipse transmitter are complete and correct for the type of
installation.

When installing the Eclipse transmitter in a general purpose
or hazardous area, all local, state, and federal regulations and
guidelines must be observed. See Eclipse Installation &
Operating Manual 57-600, Wiring, Section 2.5.

3.3.2 Equipment and tools

No special equipment or tools are required to install the
Eclipse transmitter. The following items are recommended:

• Open-end wrenches or adjustable wrench to fit the process

connection size and type. Coaxial probe 1

1

2

" (38 mm), twin

rod probe 1

7

8

" (47 mm), transmitter 1

1

2

" (38 mm). A torque

wrench is highly desirable.

• Flat-blade screwdriver

• Fieldbus compatible power supply with proper termination

3.3.3 operational Considerations

Operating specifications vary based on Probe model
number.

3.4

Mounting

The Eclipse transmitter can be mounted to a tank using a
variety of process connections. Generally, either a threaded
or flanged connection is used. For information about the
sizes and types of connections available, see Probe Model
Numbers, Section 7.5.2.

NOTE: Do not place insulating material around any part of the Eclipse

transmitter including the probe flange as this may cause exces-
sive heat buildup.

Make sure all mounting connections are properly in place
on the tank before installing the probe. Compare the name-
plate on the probe and transmitter with the product infor-
mation; make sure the Eclipse probe is correct for the
intended installation.

12

57-640 Eclipse Guided Wave Radar Transmitter - F

OUNDATION

fieldbus

Summary of Contents for Enhanced Model 705

Page 1: ...Guided Wave Radar Level Transmitter Enhanced Model 705 with Foundation fieldbus digital output 705 software v3 x Foundation fieldbus operating Manual...

Page 2: ...ection provided by equipment may be impaired Notice of Copyright and Limitations Copyright 2016 Magnetrol International All rights reserved Magnetrol Magnetrol logotype and Eclipse are regis tered tra...

Page 3: ...l Mount 19 3 4 5 2 Remote Mount 19 4 0 Function Blocks 20 4 1 Overview 20 4 1 1 Universal Fieldbus Block Parameters 20 4 2 Resource Block 21 4 3 Transducer Block 24 4 3 1 Transducer Block Parameters 2...

Page 4: ...e varying 4 20 mA current a digi tal communications scheme such as FOUNDATION fieldbus considers the two wires as a network The network can carry many process variables as well as other information Th...

Page 5: ...sult A FOUNDATION fieldbus system allows for mul tiple variables to be brought back from each device to the control room for additional trending and reporting 3 Maintenance The self diagnostics residi...

Page 6: ...tween the power supply in the safe area and the device in the hazardous area H1 also supports the Fieldbus Intrinsically Safe Concept FISCO model which allows more field devices in a network The FISCO...

Page 7: ...g wiring and configuring the Eclipse level transmitter These procedures are intended for experi enced installers of electronic level measurement instruments See Complete Installation Section 3 0 for d...

Page 8: ...nection or flange bolts NOTE Leave the plastic protective cap in place until ready to install the transmitter Do not use sealing compound or TFE tape on probe connection to transmitter as this connect...

Page 9: ...nce with all regulations and codes 1 Remove the cover of the upper wiring compartment of the transmitter 2 Attach a conduit fitting and mount the conduit plug in the spare opening Pull the power suppl...

Page 10: ...ext step of the configuration program the default password is 1 7 After entering the last value allow 10 seconds before removing power from the transmitter The following configuration entries are the...

Page 11: ...future reference when ordering parts Model Number Serial Number 3 2 Electrostatic Discharge ESD Handling Procedure MAGNETROL electronic instruments are manufactured to the highest quality standards Th...

Page 12: ...t the process connection size and type Coaxial probe 11 2 38 mm twin rod probe 17 8 47 mm transmitter 11 2 38 mm A torque wrench is highly desirable Flat blade screwdriver Fieldbus compatible power su...

Page 13: ...Pressure probe Model 7xP High Pressure probe Model 7xR Overfill probe Model 7xS Steam probe and Model 7xT Interface probe require added clearance Process temperature pressure dielectric and viscosity...

Page 14: ...rs etc a bare tank wall parallel to the probe is acceptable 3 4 2 1 To install a rigid twin rod probe Make sure the process connection is at least 2 NPT or a flanged mounting Make sure that there is a...

Page 15: ...evices 2 b Loosen the two 10 32 set screws 3 on both securing devices using a 3 32 2 5 mm hex wrench and slide the securing devices off of the probe c Slide the TFE weight off of the probe d Cut and r...

Page 16: ...ed connections tighten the hex nut of the probe process connection For flanged connections tighten flange bolts Probe can be stabilized by placing into a non metallic cup or bracket at the bottom of t...

Page 17: ...ds Probes The Model 7x2 and 7x5 Bulk Solids probes are designed for a 3000 lb 1360 kg pull down force for use in applications such as sand plastic pellets and grains It is offered with a maximum 75 fo...

Page 18: ...nches of coating from the two cables f Slide the weight back on to the probe g Reinstall the two cable clamps and tighten h Enter the new probe length inches or cm in software 3 4 4 4 To install a Mod...

Page 19: ...ction for wiring configuration and viewing When the transmitter is facing the desired direction use a 11 2 38 mm wrench to tighten the universal connection on the transmitter to 15 ft lbs A torque wre...

Page 20: ...Block Parameters The following are general descriptions of the parameters common to all blocks Additional information for a given parameter is described later in that specific block section ST_REV st...

Page 21: ...Block The RESOURCE block contains data specific to the Enhanced Model 705 transmitter along with some information about the firmware NOTE The Resource Block has no control function MODE_BLK Must be i...

Page 22: ...interval between copies of non volatile NV parameters to NV memory NV mem ory is only updated if there has been a significant change in the dynamic value and the last value saved will be available fo...

Page 23: ...he static data in the block BLOCK_ALM Block Alarm is used for configuration hardware connection or system problems in the block The cause of any specific alert is entered in the subcode field The firs...

Page 24: ...ollowed by these additional required parameters UPDATE_EVT Update Event an alert generated by a write to the static data in the TRANSDUCER block Another important parameter found later in the TRANS DU...

Page 25: ...on the nameplates attached to the transmitter and probe PROBE_LENGTH is shown in SENSOR_UNITs LEVEL_OFFSET Enter the distance from the probe tip to the desired 0 reference in PROBE_UNITs The accept ab...

Page 26: ...f the probe 10 inches above the bottom of the tank The user wants the 0 point at 24 inches and the 100 point at 60 inches as referenced from the bottom of the tank When the Eclipse transmitter is moun...

Page 27: ...arameters are WINDOW CONVERSION_FACTOR and SCALE_OFFSET WINDOW is used to adjust for the variations in the analog section of the Eclipse TDR measurement engine CON VERSION_FACTOR and SCALE_OFFSET are...

Page 28: ...y supplied when simulate is enabled When simulate is disabled the simulate value and status track the actual value and status XD_SCALE The high and low scale values engineering units code and number o...

Page 29: ...The block alarm is used for all configuration hardware connection failure or system problems in the block ALARM_SUM The current alert status unacknowledged states unreported states and disabled states...

Page 30: ...t to Direct with improper OUT_SCALE The AI block uses the STATUS_OPTS setting and the TRANSDUCER PV LIMIT value to modify the AI PV and OUT QUALITY Damping Filter is a feature of the AI block The PV_F...

Page 31: ...e will be displayed subject to limitations nec essary for a 6 character display 999999 Value 99999 Representative examples are shown below Because the Model 705 transmitter has four Analog Input block...

Page 32: ...algorithm as Backward or Bi linear BAL_TIME The specified time for the internal working value of bias to return to the operator set bias BKCAL_IN The analog input value and status for another blocks B...

Page 33: ...he alarm limit used to detect the HI alarm condition HI_PRI The priority of the HI alarm IN The connection for the PV input from another block LO_ALM The LO alarm data LO_LIM The setting for the alarm...

Page 34: ...allowed SP_LO_LIM The lowest SP value allowed SP_RATE_DN Ramp rate for downward SP changes SP_RATE_UP Ramp rate for upward SP changes STATUS_OPTS Allows one to select options for status handling and...

Page 35: ...ne Transmitter Display All MeasType selections 4 PrbModel select User Select the type of probe used Select from 7xa x 7xB x 7xd x 7xE x 7xF E 7xF F 7xF x 7xF 4 7xF P 7xG x 7xJ x 7xK x 7xL x 7xM x 7xn...

Page 36: ...ersion 22 DispFact select None Select Yes to display factory parameter menus 23 History Status None Diagnostic Display to view present status and recent exceptions 24 Run Time xxxx x h None Diagnostic...

Page 37: ...7xK Distance in mm from fiducial to user reference point 44 Snsr Val xxx x su None Distance to the target relative to the sensor reference point 45 CalPtLo xxx x su Superuser The lower calibrated poi...

Page 38: ...to OOS the TRANSDUCER BLOCK will still output level but the QUALITY will be shown as Bad and the SUB_STATUS is Out of Service When the Enhanced Model 705 measurement cycle fails to find a valid output...

Page 39: ...the Analog Input block The Simulate feature is typically used to exercise the operation of an AI block by simulating a TRANSDUCER block input This feature can not be activated without the placement of...

Page 40: ...near very top of probe Check for buildup or obstructions near top of probe Select higher dielectric range Check for condensation in probe connection Add Blocking Distance LEVEL and AI OUTPUT values P...

Page 41: ...t Value Mode OK 15 0x00008000 Good Non Specific Not Limited Mode User Access 7 0x00000080 Bad OOS Not Limited Mode Factory Access 5 0x00000020 Bad OOS Not Limited Fault Default Params 28 0x10000000 Ba...

Page 42: ...robe Model is proper for the dielectric of the medium 4 Consult factory EOP Probe Length End of Probe signal from a dry probe is out of range 1 Ensure the Probe Length is entered correctly 2 Set Diele...

Page 43: ...cable shield can be capacitively grounded in multiple places to improve EMC protection Ensure all devices are on the live list and the schedule has been downloaded Ensure that the Resource Block then...

Page 44: ...up G T4 Class III Type 4X 705 52XX XXX Non Incendive Class I Div 2 Groups A B C D 705 52XX XXX Suitable for Class II Div 2 Group G T4 Class III Type 4X atEX 705 52XX AXX Intrinsically Safe II 1G EEx i...

Page 45: ...7 2 1 agency Specifications Foundation fieldbus System 57 640 Eclipse Guided Wave Radar Transmitter FOUNDATION fieldbus 45...

Page 46: ...56T6 0 20 copper optional 316 stainless steel Cable Entry 3 4 NPT and M20 46 57 640 Eclipse Guided Wave Radar Transmitter FOUNDATION fieldbus Environment Operating Temperature 40 to 175 F 40 to 80 C D...

Page 47: ...nce Model 705 Specifications will degrade with Model 7xB 7xD and 7xP probes and or fixed threshold configuration Top 24 inches of Model 7xB probe 1 2 inches 30 mm Specification for top 48 inches of si...

Page 48: ...plosion Proof Z030 9151 003 FISCO Z030 9151 004 O ring Viton 012 2201 237 Consult Factory for alternative O ring materials Housing cover without glass 004 9193 003 Housing cover with glass GP IS 036 4...

Page 49: ...e Intrinsically Safe ATEX JIS EEx ia IIC T4 C Integral Explosion Proof ATEX EEx d ia IIC T4 must be ordered with Conduit Connection Codes 0 and 1 D Remote Explosion Proof ATEX EEx d ia IIB T4 must be...

Page 50: ...316L stainless steel NACE construction K 316 316L stainless steel probe and process connection ASME B31 1 specifications model 7xS only N Enlarged coaxial probe 316 316L stainless steel probe 2 minimu...

Page 51: ...500 ANSI Raised Face Flange 23 1 150 ANSI Raised Face Flange 24 1 300 ANSI Raised Face Flange 25 1 600 ANSI Raised Face Flange 27 1 900 1500 ANSI Raised Face Flange 28 1 2500 ANSI Raised Face Flange 3...

Page 52: ...orque Tube Flange UT 31 2 600 Masoneilan Proprietary Carbon Steel Torque Tube Flange UU 31 2 600 Masoneilan Proprietary 316 Stainless Steel Torque Tube Flange UV 31 2 600 Masoneilan Proprietary Carbon...

Page 53: ...5 StrapTbl Pt05 56 STRAPPING_TABLE_POINT06 StrapTbl Pt06 57 STRAPPING_TABLE_POINT07 StrapTbl Pt07 itEM PaRaMEtER naME PaRaMEtER LaBEL 58 STRAPPING_TABLE_POINT08 StrapTbl Pt08 59 STRAPPING_TABLE_POINT0...

Page 54: ...l Process Medium Tag Electronics Serial TROUBLESHOOTING Probe Serial Working Value Non Working Value Level Volume optional Interface optional Interface Volume opt Probe Model Probe Mount Measurement T...

Page 55: ...eet Copy blank page and store calibration data for future reference and troubleshooting Item Value Value Value TROUBLESHOOTING Working Value Non Working Value FidTicks FidSprd Fid Type HF Cable Fid Ga...

Page 56: ...will be determined on the basis of the applicability of our warranty No claims for misapplication labor direct or consequen tial damage will be allowed Return Material Procedure So that we may effici...

Reviews: