46-649 Jupiter Magnetostrictive Transmitter - F
OUNDATION
fieldbus™
25
5.3
Specifications
5.3.1 Functional
System Design
Measurement Principle
Magnetostrictive time-of-flight
Input
Measured Variable
A return signal is generated from the precise location where the magnetic
field of the MLI float intersects the magnetostrictive wire
Zero and Span
6 inches to 400 inches (15 to 999 cm)
User Interface
Keypad
3-button menu-driven data entry and system security
Indication
2-line
×
8-character display
Digital Communication
F
OUNDATION
fieldbus
™
, H1 (31.25 kbits/sec)
Interoperability test kit (ITK Revision)
ITK 4.61
LAS capable
Yes, Device type: Linkmaster
Minimum Operating Voltage
9 VDC
Quiescent Current Draw
15 mA
DEV Revision
0X01
Function Blocks
1xRB, 2xAI(s)
Damping
Adjustable 0-25 seconds
Power
(Measured at instrument terminals)
Fieldbus General Purpose/Explosion Proof 9 to 32 VDC (17 mA maximum current draw)
FISCO/FNICO
9–17.5 VDC (17 mA maximum current draw)
Housing
Material
Aluminum A356T6 (<0.20% copper), optional 316 stainless steel
Cable Entry
3
⁄
4
" NPT and M20
5.3.2 Performance
Accuracy
±0.015"
Repeatability
±0.005% of full span or 0.005" (0.127 mm) (whichever is greater)
Linearity
0.020% of full span or 0.031" (0.794 mm) (whichever is greater)
Maximum level rate of change
6 inches per second
Response time
0.1 second
Warm-up
<5 second
Upper dead zone
None
Lower dead zone
<2" (5 cm), SIL 2: <5" (13 cm)
Ambient temperature range
Transmitter:
-40° to +175° F (-40° to +80° C)
LCD:
-10° to +160° F (-20° to +70° C)
Process temperature
External Mount:
-40° to +248° F (-40° to +120° C)
-320° to +850° F (-195° to +455° C) (with factory insulated MLI)
Direct Insertion:
-40° to +200° F (-40° to +95° C)
High temperature probe:
-40° to +500° F (-40° to +260° C)
Humidity
0 to 99% non-condensing
Electromagnetic compliance
EN 61326
Maximum Pressure (Direct Insertion)
1700 psig @ +100° F
(limited to the pressure rating of the selected flange or float)