Magnetrol 075 Instruction Manual Download Page 6

6

SWITCH DIFFERENTIAL ADJUSTMENT (cont.)

PREVENTIVE MAINTENANCE

NOTE: Use a new enclosing tube gasket when reassem-
bling enclosing tube to the chamber. Coat enclosing tube
threads with “anti-seizing” compound.

13. Replace enclosing tube, switch, and base on chamber.

Screw tube clockwise until tightened to 10,42 -
13,90 kgm of torque.

14. Rotate switch housing to correct position and tighten

set screw at base of switch housing. See Figure 4.

15. Bring supply wires through conduit outlet. Follow steps

5 through 10 of the “Wiring” section on page 4.

NOTE: If switch mechanism fails to function properly, check
vertical alignment of control housing and consult 
installation bulletin on switch mechanism. If the unit still
fails to function properly, consult the factory.

HIGH LEVEL CONTROLS

On high level controls, the switch trips on the higher actua-
tion point and resets on the lower actuation point.

CAUTION:

On high level controls, widening the differential
requires raising the trip point a proportionate
amount. The reset point will remain the same.

To widen the differential by raising the trip point, follow
steps 1 through 16 under “Low Level Controls”.

Switch
housing
cover

Conduit
connection

Enclosing
tube nut

Enclosing tube

See figures 6 and 7

Housing base

Float

Chamber

Figure 5

Slight play (gap)
must be allowed

(0.8 (0.03") typical

Position of bottom

jam nuts (normal

factory setting)

Replace in same position

Distance

Drop bottom
jam nuts to
increase gap
setting (see
instructions
above)

Maximum gap setting
(applies to models having
a single switch mecha-
nism with a single magnet
actuator only!)

CAUTION: After increasing
gap setting, be certain to
check for proper operation of
switch mechanism by raising
and lowering float assembly.
Magnet must 'snap' cleanly
with additional float movement
available after magnet snaps.

25 (1")

Normal factory setting

(minimal differential)

Figure 6

Differential adjustement

Figure 7

Periodic inspections are a necessary means to keep your Magnetrol level control in good working order. This control
is, in reality, a safety device to protect the valuable equipment it serves. Therefore, a systematic program of "preven-
tive maintenance" should be implemented when control is placed into service. If the following sections on "what to
do" and "what to avoid" are observed, your control will provide reliable protection of your capital equipment for many
years.

WHAT TO DO

1. Keep control clean

NEVER leave switch housing cover off the control. This
cover is designed to keep dust and dirt from interfering
with switch mechanism operation. In addition, it protects
against damaging moisture and acts as a safety feature
by keeping bare wires and terminals from being
exposed. Should the housing cover become damaged or
misplaced, order a replacement immediately.

2. Inspect switch mechanisms, terminals and connec-

tions monthly.

– Mercury switches may be visually inspected for short

circuit damage. Check for small cracks in the glass
tube containing the mercury. Such cracks can allow
entrance of air into the tube causing the mercury to
"oxidize". This is noticeable as the mercury will appear
dirty and have a tendency to "string out" like water,
instead of breaking into round pools. If these condi-
tions exist, replace the mercury switch immediately.

– Dry contact switches should be inspected for exces-

sive wear on actuating lever or misalignment of
adjusting screw at point of contact between screw
and lever. Such wear can cause false switch actuat-
ing levels. Adjust switch mechanism to compensate
(if possible) or replace switch.

Do NOT operate your control with defective or malad-

justed switch mechanisms (refer to bulletin on switch
mechanism furnished for service instructions).

– Magnetrol controls may sometimes be exposed to

excessive heat or moisture. Under such conditions,
insulation on electrical wires may become brittle,
eventually breaking or peeling away. The resulting
"bare" wires can cause short circuits.

Check wiring carefully and replace at first sign of brittle
insulation.

– Vibration may sometimes cause terminal screws to

work loose. Check all terminal connections to be cer-
tain that screws are tight. Air (or gas) operating medi-
um lines subjected to vibration may eventually crack
or become loose at connections causing leakage.
Check lines and connections carefully and repair or
replace, if necessary.

– On units with pneumatic switches, air (or gas) operat-

ing medium lines subjected to vibration, may eventu-
ally crack or become loose at connections carefully
and repair or replace, if necessary.

NOTE: As a matter of good practice, spare switches should
be kept on hand at all times.

3. Inspect entire unit periodically

Isolate control from vessel. Raise and lower liquid level
to check for switch contact and reset.

Summary of Contents for 075

Page 1: ...eactivating the switch Rising level Falling level pivot return spring UNPACKING Unpack the instrument carefully Inspect all units for dam age Report any concealed damage to carrier within 24 hours Check the contents of the packing slip and purchase order Check and record the serial number for future refer ence when ordering parts AGENCY APPROVALS Agency Approval CENELEC EEx d IIC T6 explosion proo...

Page 2: ...pecific gravity Pressure rating Models with material construction code bar C PSIG F 4 40 C 230 C 400 C 100 F 450 F 750 F A 0 65 42 7 29 0 25 2 620 420 365 B 0 75 69 0 58 6 51 7 1000 850 750 C 0 60 34 5 22 4 19 6 500 325 285 G 0 57 51 7 38 6 32 7 750 560 475 P 0 75 27 6 17 9 15 5 400 260 225 O 0 85 27 6 22 4 19 6 400 325 285 MATERIALS OF CONSTRUCTION SIZE AND TYPE OF TANK CONNECTIONS see configurat...

Page 3: ... 2 EEA E1A EZ8 EOD EO8 EY8 EO7 EY7 EEB E1B EZ7 EOM EO6 EY6 EO5 EY5 Series 2 400 C 1 2AA 22A 23A 2KD 2K8 2U8 2K7 2U7 2AB 22B 23B 2KM 2K6 2U6 2K5 2U5 Vibr resistant 750 F SPDT 2 2BA 24A 25A 2LD 2L8 2V8 2L7 2V7 2BB 24B 25B 2LM 2L6 2V6 2L5 2V5 mercury switch 3 2CA 26A 27A 2MD 268 278 267 277 2CB 26B 27B 2MM 266 276 265 275 with DPDT 1 2DA 28A 29A 2ND 2N8 2X8 2D7 2W7 2DB 28B 29B 2NM 2N6 2X6 2D5 2W5 bea...

Page 4: ...ore responsive and accurate level change in the control Liquid in a long line may be cooler and more dense than liquid in the vessel causing lower level indication in the control than actual level in the vessel Most mechanical control switch housings are designed to allow 360 positioning of the cable entries by loosening the set screw s See figure 4 On high temperature applica tions above 120 C 25...

Page 5: ... 5 5 Perform system shut down procedures as required to relieve pressure from float chamber of control Allow unit to cool a Close shut off valves if so equipped to isolate control from tank Drain off liquid in float chamber See Figure 3 on page 4 b On installations without shut off valves relieve pressure from the tank Drain liquid in tank to a level below the connections of the float chamber NOTE...

Page 6: ...avoid are observed your control will provide reliable protection of your capital equipment for many years WHAT TO DO 1 Keep control clean NEVER leave switch housing cover off the control This cover is designed to keep dust and dirt from interfering with switch mechanism operation In addition it protects against damaging moisture and acts as a safety feature by keeping bare wires and terminals from...

Page 7: ...in two place 90 apart Refer to Figure 3 on page 4 7 If mechanism is equipped with a mercury switch examine glass mercury tube closely as previously described in Preventive Maintenance section If switch is damaged replace it immediately 8 If switch mechanism is operating satisfactorily proceed to check sensing unit CHECK SENSING UNIT 1 Check to be certain liquid is entering float chamber A valve ma...

Page 8: ... 05 B75 47 1 88 67 2 63 C75 41 1 61 64 2 51 G75 38 1 50 58 2 28 P75 36 1 41 60 2 36 Part n mm inches code HL LL A75 25 0 98 52 2 05 B75 59 2 31 79 3 11 C75 53 2 08 76 3 00 G75 46 1 88 66 2 60 P75 48 1 88 72 2 83 Part n mm inches code HL LL A75 25 0 98 52 2 05 B75 76 3 00 96 3 77 C75 70 2 77 93 3 63 G75 64 2 50 84 3 30 075 75 2 94 103 4 05 P75 65 2 56 89 3 50 1 and NW 25 DIN connections NPT flanged...

Page 9: ...EMA 7 9 1 NPT F entry BASEEFA CENELEC M20 x 1 5 or 3 4 NPT F entry Pneumatic switches K Series Nema 3R 1 4 NPT F two entries J Series Nema 3R 1 4 NPT F one entry Rotation clearance L NEMA 4X IP 65 109 4 29 NEMA 7 9 100 3 94 BASEEFA CENELEC 110 4 33 Pneumatic K NEMA 3R 130 5 12 Pneumatic J NEMA 3R 110 4 33 All housings rotatable 360 Allow 200 mm 7 87 overhead clearance for cover removal Threaded so...

Page 10: ... 356 230 733 P75 217 84 573 224 93 580 356 200 712 356 200 712 inches 1 1 2 NPT 1 1 2 socket weld 1 1 2 or NW 40 1 1 2 or NW 40 Flanged upper side bottom Flanged side side Part n code A B C max A B C max D E F max G H J max A75 8 74 3 30 23 80 8 74 3 66 23 80 14 7 87 29 05 14 7 87 29 05 B75 8 56 3 88 23 00 8 84 4 25 23 30 14 8 46 28 46 14 8 46 28 46 C75 8 56 3 88 23 00 8 84 4 25 23 30 14 8 46 28 4...

Page 11: ...units only with all parts listed under items 4 through 10 assembled When ordering specify model serial number of control Item Description Models with mat l code 4 A B C G J O P75 1 Housing cover Housing Refer to bulletin 42 780 for switch housing cover and base assemblies 2 Housing base kits 3 Switch mechanism Refer to bulletin on switch mechanism furnished listed on page 4 4 Jam nuts 5 Guide wash...

Page 12: ...odels in the field Switch actuation levels have been set at the factory to meet specific customer specifications Variations in actual conditions from design conditions usually requires special control modifications Consult the factory or your local representative for assistance REPLACEMENT OF FLOAT AND STEM ASSEMBLIES Should replacement of either upper or lower float and stem assembly be required ...

Page 13: ...13 ...

Page 14: ...E So that we may efficiently process any materials that are returned it is essential that a Return Material Authorisation RMA form will be obtained from the factory It is mandatory that this form will be attached to each material returned This form is avail able through Magnetrol s local representative or by contacting the factory Please supply the following information 1 Purchaser Name 2 Descript...

Reviews: