Full Height Turnstile MPT-132
Troubleshooting
61
10.3 Downloading new software to logic controller MBC-110
NOTE!
Before a download, the position of the DIP switch
on the MBC-110 must be noted so that the unit can
be restored to its previous operating state following
the download.
1. Note switch position of the 16 DIP switch on the MBC-110.
2. Isolate the power supply to the pedestrian barrier. Wait a few
seconds until the capacitors in the power pack have dis-
charged.
3. Set all 16 DIP switches on the MBC-110 to the ON position.
4. Restore the power supply to the pedestrian barrier.
5. The MBC-110 detects from the position of the DIP switch that
a download is to be executed.
6. The MBC-110 is initializing. The display first shows "P" and
then "G".
7. The MBC-110 assumes the waiting state. The display shows
"L" and a flashing stop. At this point in time, the download can
be cancelled by switching off the power supply.
8. Set all 16 DIP switches to the OFF position.
9. The download is executing:
The program memory of the logic controller is erased. The
display on the MBC-110 shows "c" (clear) and a flashing
stop.
The new software is being downloaded. The display shows
"d" (download) and a flashing stop.
The new software is activated by booting the logic control-
ler. A rotating bar appears in the display.
10. Disconnect the power supply again.
11. Reset the DIP switches on the MBC-110 to the old position
you noted down earlier.
12. Reconnect the power supply. The unit starts to operate.
NOTE!
If the download failed, run another download. Con-
tact MAGNETIC if necessary.