Full Height Turnstile MPT-132
Configuring the pedestrian barrier
50
7.2.2
DIP switch block S2
DIP S2.x
Function
Description
1 Heating
active
This DIP switch is used to specify whether or not the auxiliary
heating should be activated.
Options
OFF: Auxiliary heating inactive
ON: Auxiliary heating active
2 and 3
Force for starting a pas-
sage
When a clearance pending, the movement will not be started
until the customer pushes the full height turnstile. There are
four settings for the required force:
DIP S2.2
DIP S2.2
Force
OFF OFF slight
OFF ON medium
ON OFF medium-strong
ON ON strong
4 and 5
Speed
This DIP switch can be used to select one of three defined
speeds (slow/medium/fast) for normal operation:
DIP S2.4
DIP S2.5
Speed
OFF OFF slow
OFF ON medium
ON OFF fast
ON ON fast
6
Rotational direction for
homing
(viewed from above)
This DIP switch specifies the rotational direction of the center
column during homing. This means that even during homing,
no unauthorized person can pass the barrier.
Options
OFF: Counterclockwise
ON: Counterclockwise
7
Select the pedestrian
barrier setup
OFF: 3 x 120°
ON: No function
8 Software
reset
If the DIP-switch is in the position ON, the control automati-
cally performs a reset approx. 10 seconds after the occur-
rence of a non-resettable error (errors from E20 onwards). If
there are no further faults pending, homing is performed after
the voltage returns and the pedestrian barrier returns to oper-
ation.
ON: Software reset after a non-resettable error
OFF: No software reset is performed.
Table 8: DIP switch block S2