Table 5-31: Anti-Shock Parameter Settings
Parameter
Display
Function
Range
Default
C07-12
Anti-Shock
Enables or disables the Anti-Shock function.
0–2
0
0 Disabled
Anti-Shock is disabled.
1 Enabled
Anti-Shock is enabled always.
2 Enbl, Not In MSpd
Disables Anti-Shock if Micro-Speed is
enabled.
C07-13
Enabling Freq
Anti-Shock is disabled until the output
frequency is above this setting.
0.0–60.0 Hz
6.0
C07-14
Re-Accel Delay
If the operator decelerates the hoist then re-
accelerates, Anti-Shock Detection is disabled
for this period of time.
0.00–2.55 sec
0.20
C07-15
Torque Delta
Torque increase required to initiate the Anti-
Shock sequence.
0–180%
10
C07-16
Detection Time
Time window to detect torque delta (C07-15).
0.01–0.50 sec
0.30
C07-17
Smoothing Freq
When the torque increase is detected, the
motor will decelerate to this frequency.
0.0–15.0 Hz
3.0
C07-18
Smoothing Decel
Deceleration time once an Anti-Shock event
has been detected. Increase this value in 0.1
sec increments if DEV faults are occurring.
0.00–1.00 sec
0.30
C07-20
Smoothing Time
Time window to smooth out the torque.
0.00–2.55 sec
1.00
C07-22
AlarmDisplayTime
When Anti-Shock is triggered, an alarm will
display on the keypad screen for the selected
duration of time.
0–30 sec
4
C07-23
No Load Torque
Any torque values below this level are
ignored. Best described as the torque level
while hoisting with an empty hook (no load).
0–100%
20
C07-24
Activation Torque
In order for Anti-Shock to be triggered, the
torque increase is required to peak above this
percentage.
0–180%
75
C07-25
Detection Method
Anti-Shock detection method.
0–2
1
0 Always Detect
Anti-Shock can be continuously detected.
1 Once Per Lift
After Anti-Shock is detected once during a lift,
it is disabled until the hoist is lowered.
2 Fault on Detect
Fault when Anti-Shock is detected.