Table A1-1. GPD 315 Parameters - Continued
SETTING RANGE
SETTING
FACTORY
USER
PARA.
CONSTANT
NAME
(AND UNITS)
INCREMENT
SETTING
SETTING
REF.
0: Fwd / Rev command (3 wire control)
Multi-function Input
[can only be set in n052]
1
1
Selection 1 (Terminal S1)
1: Forward run (2 wire control)
(1)
2: Reverse run (2 wire control)
3: External Fault (N.O.)
Multi-function Input
4: External Fault (N.C.)
1
2
Selection 2 (Terminal S2)
5: Fault Reset
(2)
6: Multi-step speed ref. cmd. A
Multi-function Input
7: Multi-step speed ref. cmd. B
1
3
Selection 3 (Terminal S3)
8: Multi-step speed ref. cmd. C
(0)
9: Multi-step speed ref. cmd. D
Multi-function Input
10: JOG Selection
1
5
Selection 4 (Terminal S4)
11: Accel/Decel time change cmd.
(5)
5.18
12: External Base Block (N.O.)
Multi-function Input
13: External Base Block (N.C.)
1
6
Selection 5 (Terminal S5)
14: Speed search from max. freq.
(6)
Multi-function Input
15: Speed search from set freq.
Selection 6 (Terminal S6)
16: Accel/Decel hold command
1
7
17: Remote/Local selection
(7)
18: Serial Communication / control ckt.
selection
19: Fast Stop - Fault (N.O.)
20: Fast Stop - Alarm (N.O.)
Multi-function Input
21: Fast Stop - Fault (N.C.)
1
10
Selection 7 (Terminal S7)
22: Fast Stop - Alarm (N.C.)
(10)
23: PID control off
24: I value reset (PID)
25: I value hold (PID)
34: Up / Down command
35: Loop Test [can only be set in n056]
0: Fault
Multi-Function Output
1: During running
1
0
Selection 1
2: Speed Agree
(Terminals MA, MB & MC)
3: Zero Speed
4: Frequency detection 1
5: Frequency detection 2
6: Overtorque detection (N.O.)
Multi-Function Output
7: Overtorque detection (N.C.)
1
1
5.19
Selection 2
10: Minor Fault
(Terminals P1 & PC)
11: During Base Block
12: Local / Remote
13: Ready
14: During auto restart
Multi-Function Output
15: During undervoltage
Selection 3
16: During reverse run
1
2
(Terminals P2 & PC)
17: During speed search
18: Serial Comm. Controlled
``
19: PID feedback loss
Analog Frequency Reference
0 to 255
1 (%)
100
Gain
5.8
Analog Frequency Reference
-100 to 100
1 (%)
0
Bias
n062
Analog frequency reference
0.00 to 2.00
0.01 (sec)
0.10
filter time constant
n065
Monitor Output
0: Analog monitor output
1
0
Selection
1: Pulse monitor output
0: Output frequency
1: Output Current
2: DC Bus Voltage
Multi-function Analog Output
(10V / 400 VDC [800 VDC])
(Terminals AM & AC)
3: Motor Torque
1
0
5.17
(10V / Motor rated torque)
4: Output Power
(10V / Drive Capacity kW)
Analog Monitor Gain
0.00 to 2.00
0.01
1.00
n068
Analog Frequency Reference
-255 to 255
1%
100
Gain (Voltage Ref Input)
n069
Analog Frequency Reference
-100 to 100
1%
0
Bias (Voltage Ref Input)
Summary of Contents for GPD 315
Page 1: ...GPD 315 Technical Manual Magne Tek ...
Page 20: ...1 14 ...
Page 32: ...3 2 ...
Page 76: ...5 40 PID Block Diagram ...
Page 80: ...5 44 ...
Page 96: ...A1 8 ...
Page 100: ...A3 2 ...
Page 102: ...A4 2 ...
Page 110: ...A6 6 ...
Page 114: ......
Page 116: ......