Flex 4EX2 / 6EX2 MRX CE Instruction Manual
November 2018
Page 24 of 44
6EX2:
* PB1...PB6
→
Pushbutton number.
* Normal
→
Normal momentary contact.
* LED 1 - LED 4
→
Pushbutton toggled function with designated LED indication.
4.1.9
Display Frequency Band
1. Rotate the power switch key to OFF ( 0 ) position.
2. With the STOP button elevated, press and hold PB2 and PB4 at the
same time.
3. Rotate the power switch key to ON ( I ) position.
4. Release PB2 and PB4 at the same time. The system will enter
Frequency Band Display mode.
5. The Status LED displays the preset transmitter frequency band with
orange, green and red blinks. An orange blink represents the hundreds (+
1
00), a
green blink represents the tens (+0
1
0) and a red blink represents the units (+00
1
). For
example,
8
orange blinks followed by
6
green blinks and
3
red blinks is
863
MHz.
6. Exit Frequency Band Display mode by rotating the power switch key to OFF ( 0 )
position.
4.1.10 Output Feedback Settings
Up to 4 assignable relay outputs can be programmed into the system and feedback to
the transmitter LED indicators during operation. These settings require using the
infrared IR programmer unit. Please contact Magnetek field service for more details.
Function
Number
Display
Type
PB1
PB2
PB3
PB4
PB5
PB6
1
1 Red
Normal
Normal
Normal
LED 4
Normal
Normal
2
2 Reds
Normal
Normal
LED 3
LED 4
Normal
Normal
3
3 Reds
Normal
LED 2
LED 3
LED 4
Normal
Normal
4
4 Reds
LED 1
LED 2
LED 3
LED 4
Normal
Normal
7
7 Reds
Normal
Normal
Normal
Normal
Normal
LED 2
8
8 Reds
Normal
Normal
Normal
Normal
LED 1
LED 2