Digital Operator Display
Fault Name
oFC02
Option Fault (CN5-C)
Two of the same options are connected simultaneously
Cause
Possible Solution
AI-A3 option connected to CN5-C port
while another option was connected to
CN5-A port.
Only one of these options, AI-A3, DI-A3, or SI-XX can be
connected to the drive at the same time.
Digital Operator Display
Fault Name
oPE05
Run command/frequency reference source selection
error
Cause
Possible Solution
Frequency reference is assigned to an
option (b3-01 = 3) but an option is not
connected.
Reconnect the option to the drive.
Digital Operator Display
Fault Name
oPE07
Multi-Function Analog Input Selection Error
Cause
Possible Solution
At least two analog input terminals are
set to the same function.
Analog input terminal and pulse train
input are set to the same function.
Adjust H3-02, H3-06, and H3-10 settings so functions no
longer conflict.