background image

035-000049-001 

Page 19 

HCA IOM 1.1 8-28-2017 

START-UP 

Pre-Startup 

BUILDING ENVELOPE

All building windows and 

doors should be installed and closed before starting 
unit.  During summer construction, avoid unit sweating 
by allowing for gradual pull down:  use elevated chilled 
water temperature, reduce chilled water flow rate 
(gpm), use maximum available airflow.   
HEATING FLUID TEMPERATURE-Maximum entering 
water temperature is 180°F, unless nameplate indicates 
200°F.  

CAUTION

:  If unit is marked for 200°F maxi-

mum entering water temperature, customer must en-
sure that water vaporization does not occur especially 
at higher elevations when entering water temperatures 
are greater than 190°F.    
TEMPERATURE CONTROLS-Check that unit or wall 
mounted thermostat or field-supplied controller is con-
nected to the unit.   
OUTSIDE AIR AND FREEZE PROTECTION- 

WARNING:  Insure that the unit is protected against 

freezing conditions   Failure to provide freeze pro-
tection may result in equipment or property dam-
age.  

Freeze protection measures are customer-

provided and installed and include but are not limited to 
low-limit thermostats, automatic temperature controls, 
and use of glycol based heat transfer fluids (see section 
FREEZE PROTECTION OF WATER PIPING).   
1.  If “locking quadrant” manual damper operator pro-
vided, set to desired position.     
2.  If damper actuator provided, insure that actuator 
opens the damper when the fan turns on, and closes 
when fan stops.   Test mixing box controls to make sure 
OA damper closes on power failure or upon activation 
of customer-supplied and installed low limit thermostat 
or other freeze protection device.   

Start-Up Check List — 

Remove all construction debris 

from unit interior. 

Remove tools and all foreign objects 

before starting unit. Checklist—perform full startup 
checklist located on the last page of this manual, and 
submit to the factory to register the warranty.   

FILTERS — Install unit filters in all filter sections.  Pro-
tect open filters from drywall dust and construction de-
bris. 
MOTOR/FAN ASSEMBLY 
1.  Hand turn fan to make certain it turns freely and fan 

wheel does not rub the inlet ring.   

2.  Check fan speed with a laser-type tachometer to 

confirm operating speed (access doors must be 
closed to apply correct external static pressure to 
the fan).   

3.  Check direction of rotation (see Fig. 15).  
4.  Check vibration. If excessive vibration occurs, 

check for the following: 

A.  Shipping screws removed.  
B.  Inadequate airflow.   
C.  Damaged wheel.   
D.  Loose mounting bolts. 
E.  Wheel or motor out of balance. 
F.  External vibration isolators improperly ad-

justed. 

G.  Out-of-balance or corroded wheel 

(rebalance or replace if necessary). 

H.  Accumulation of material on wheel (remove 

excess material). 

Fig. 15 — Fan Wheel Rotation

COILS 
1.  Make sure freeze protection measures are 

in place to protect water coils from freezing 
(see section FREEZE PROTECTION OF 
WATER PIPING).   

2.  Make sure hydronic (water based chllled 

water and hot water) systems are filled and 
have air removal devices in operation.   

3.  For hydronic coils with 3ea connections, 

make sure that the supply connection is at 
the bottom (air leaving side of coil) and re-
turn connection is in the middle (air entering 
side of coil), and the top connection is 
capped with the factory-provided cap.   

Start-Up—Run Fan, Set Airflows 

CONTROLS 
Set up control system so that it correctly runs 
the fan as needed and activates control valves 
when required.  Note that operating cooling with 
the fan off can cause the cabinet temperature to 
become too low and result in condensation in-
side and outside the unit cabinet, leading to un-
safe conditions.  When fan is not running, cool-
ing should be inactive.   

START THE FAN 
With 4-Speed Control:   
1.  Using a thermostat:  Route R, C and G1 

connections in the HCA control box to the 
matching thermostat connections (include 
G2 and G3 if required).  Set thermostat to 
run the fan at speed G1.   

2.  Without a thermostat:  Jump together the R 

and G1 terminals in the control box.   

3.  While fan is running, adjust potentiometer 

marked “FLO1” that controls fan speed G1 
using a small flat blade screwdriver.  Repeat 
for the other speeds as needed.   

With 0-10VDC Control:   
1.  Using a thermostat:  Route R, C, + (plus) 

and -(minus) connections in the HCA control 
box to the matching thermostat connections.  
Set the thermostat to run the fan.   

2.  Without a thermostat: Provide a DC control 

voltage across the + (plus) and — (minus) 
terminals.   

3.  Fan starts at 2.0VDC.  Fan speed varies 

across available range (pre-programmed at 
factory) from 2.0 VDC (minimum speed) to 
10.0 VDC (maximum speed).    

Summary of Contents for HCA 04

Page 1: ...ARNING Hazardous voltage Discon nect and Lock Out all incoming power sources before servicing or installing unit ELECTRIC SHOCK CAN CAUSE DEATH WARNING This equipment may be in stalled well above fini...

Page 2: ...035 000049 001 Page 2 HCA IOM 1 1 8 28 2017 THIS PAGE INTENTIONALLY LEFT BLANK...

Page 3: ...G Remove Shipping Screws 4 PREINSTALLATION 5 Rigging 5 Unit Weight Calculation 5 INSTALLATION 6 18 Unit Suspension 6 7 External Vibration Isolators 7 Ductwork 8 Electrical 9 11 Service Clearance 12 Co...

Page 4: ...ampers until their operators are disconnected BE SURE that fans are properly grounded before working on them Failure to follow these warnings could result in personal injury or equipment damage DANGER...

Page 5: ...l Code IMC section 307 2 3 requires the use of auxiliary drain pans Many municipalities have adopted this code Magic Aire holds that this practice represents the standard for professional installation...

Page 6: ...ming be construct ed from structural steel or formed strut mate rials With Mixing Boxes HCA units sizes 30 40 with mixing boxes should be supported with crossbeams at each end of the unit and at the d...

Page 7: ...JURY CAUSED BY FALLING EQUIPMENT If uncertain about how to connect to the structure consult a qualified structural engineer Floor mounting Unit may be mounted on a housekeeping pad floor or platform C...

Page 8: ...side of a field provided flexible duct to the fan discharge duct collar on the front of the unit Attach the other side to the supply ductwork Seal the connec tions using duct mastic or HVAC tape Refe...

Page 9: ...WARNING For use with copper conductors only INSTALLATION ELECTRICAL INSTALLATION ELECTRICAL Typical wiring diagrams are shown on the fol lowing pages FOR REFERENCE Always re fer to the wiring diagram...

Page 10: ...circuit protection and wiring 6 To start the fan connect R and G1 or G2 or G3 to energize fan at each respective speed Add connection to terminal FLO4 on the control board EVOECM 4SPD to enable a four...

Page 11: ...components is the responsibility of the in staller including branch circuit protection and wiring 6 To start the fan apply 2 0VDC to plus and minus terminals Fan speed is variable from 2 0VDC minimum...

Page 12: ...S MAY BE ON ONE SIDE OR ON BOTH SIDES 4 REFER TO INSTALLATION INSTRUCTIONS FOR UNIT HANGING SUSPENSION REQUIREMENTS 5 COIL DRAINPAN OR BLOWER REPLACEMETN REQUIRES UNIT TO BE REMOVED TO FLOOR FOR SAFE...

Page 13: ...vent losing seal when starting up the unit After the fan is running with the design fan inlet negative pressure the elevation of the water on the unit side of the trap will be 1 below the drain invert...

Page 14: ...nto the condensate line between the trap and the gate valve instead of open to the atmosphere Figure 9 illustrates the typical piping at the end of every steam supply main Omitting this causes many fi...

Page 15: ...with a bucket trap or any trap which has provision for passing air The great majority of high pressure return mains terminate in hot wells or deaerators which vent the air Fig 10 Multiple Coil High P...

Page 16: ...s length The outer tubes are expanded into plate fins The completed assembly includes the supply and condensate header and side casings which are built to slant the fin tube bundle back to ward the co...

Page 17: ...ions The lower split of face split coils should be first on last off Fig 13 Row split coils utilize special intertwined circuits either split of these row split coils can be first on last off SUCTION...

Page 18: ...o use drop solenoid valve control as illustrated above and let the suction cutoff unloaders ride with the load The second is to use drop solenoid valve control as illustrated above with electric un lo...

Page 19: ...tachometer to confirm operating speed access doors must be closed to apply correct external static pressure to the fan 3 Check direction of rotation see Fig 15 4 Check vibration If excessive vibration...

Page 20: ...use any aggressive paint solvent cleaning agents when cleaning 5 Never use a high pressure cleaner or water spray for cleaning particularly when the fan is running WARNING Wet cleaning under volt age...

Page 21: ...prevent the formation and build up of acids There are additional precautions and control strate gies as found in various catalogues and in the ASHRAE Fundamentals Handbook when the enter ing air tempe...

Page 22: ...clear space 3 Remove the flat coil stubout panel Refer to Figure 16 and 17 Note that there is another coil access panel on the opposite side of the unit SERVICE Coil Drainpan Removal and Reinstallatio...

Page 23: ...il panel Figure 23 and 24 8 Remove coils from unit along with drainpan Drainpan will slide out of unit Figure 25 or 26 To remove coils and drainpan top will need to be lifted up as shown in Figure 21...

Page 24: ...nation up to 24 hours after sampling A low pH and high alkalinity cause system problems even when both values are within ranges shown The term pH refers to the acidity basicity or neutrality of the wa...

Page 25: ...mary Auxiliary cu in note 2 Hot Water 1 row gal Hot Water 2 row gal Coil Face Area Pre Filter 12 x 24 16 x 32 3 Not all combinations equaling 10 rows are allowed Please refer to New Magic 4 Software f...

Page 26: ...035 000049 001 Page 26 HCA IOM 1 1 8 28 2017...

Page 27: ...necessary for proper condensate drainage Is properly sized condensate trap present Is the condensate disposal system operating correctly Is auxiliary external condensate drain pan installed as recomm...

Page 28: ...035 000049 001 Page 28 HCA IOM 1 1 8 28 2017 THIS PAGE INTENTIONALLY LEFT BLANK...

Page 29: ...035 000049 001 Page 29 HCA IOM 1 1 8 28 2017 THIS PAGE INTENTIONALLY LEFT BLANK...

Page 30: ...035 000049 001 Page 30 HCA IOM 1 1 8 28 2017 HCA Series Air Handler Installation Operation and Maintenance Manual...

Reviews: