DHB IOM 1.5 11-02-2023 

Figure 5 

PSC Motor Option 

Unit Wiring 

ELECTRICAL CONNECTIONS

 

 

PSC MOTOR:  NOTE:  PSC motor option 

DOES NOT provide fan relay or low voltage 

fan circuit.   
 

Figure 5 illustrates the internal wiring for the 

unit.  
 

The utility box (4x4 junction box or “j-box 

only”) is mounted on the coil connection 

side of the unit. All leads pass through a 

strain relief where they enter the utility box.  
 

Wiring within the cabinet has been positively 

located and supported so that it does not 

pass over sharp metal edges or come in 

contact with moving parts. After servicing, 

properly position electrical leads in their 

original supports.  
 

 

DH Series Electrical Data

 

PSC Motor (J

-

box only 

-

 no fan relay

 

Model

 

PSC Motor

 

MCA

 

MOPD

 

Voltage

 

HP

 

FLA

 

  

115V/1ph

 

1/10

 

2.1

 

2.6

 

  

DHB04

 

208

-

230V/1ph

 

1/10

 

.9

 

1.1

 

15

 

  

277V/1ph

 

1/6

 

.9

 

1.1

 

  

  

115V/1ph

 

 

3.7

 

4.6

 

  

DHB06

 

208

-

230V/1ph

 

1/6

 

1.2

 

1.5

 

15

 

  

277V/1ph

 

  

.9

 

1.1

 

  

  

115V/1ph

 

  

4.1

 

5.1

 

  

DHB08

 

208

-

230V/1ph

 

1/4

 

1.6

 

2.0

 

15

 

  

277V/1ph

 

  

2.0

 

2.5

 

  

  

115V/1ph

 

  

6.9

 

8.6

 

  

DHB12

 

208

-

230V/1ph

 

1/3

 

2.2

 

2.8

 

15

 

  

277V/1ph

 

  

2.4

 

3.0

 

  

Notes: 

1.  MCA= Minimum Circuit Ampacity 

2.  MOPD= Maximum Overcurrent Protective Device, in 

amps. 

3.  FLA = Full Load Amps 

4.  HP = Motor nominal horsepower 

5.  All motors are 60Hz 

6.  Use minimum wire size #14 AWG 75C wire at unit 

7.  PSC option includes 3-speed motor with wires terminated 

in J-Box.  No control circuit is provided. 

Summary of Contents for DHB Series

Page 1: ...general heating sys tems designed for outside temperatures of zero degrees or lower will need no alteration when used for cooling However in southern sections of the country the existing heating duct...

Page 2: ...the vertical and hori zontal dimensions of the transition piece do not increase more then one inch for every seven inches of length of the transition piece 3 Provide at least three feet of straight d...

Page 3: ...ut a TXV For best results use of the factory TXV is recom mended Field installable TXV is available as an accessory FIELD INSTALLED TXV Fig 3 Install TXV by threading on to the distributor Remove pist...

Page 4: ...010 200021 000 Page 4 DHB IOM 1 5 11 02 2023 Figure 4 Service Clearances...

Page 5: ...ts After servicing properly position electrical leads in their original supports DH Series Electrical Data PSC Motor J box only no fan relay Model PSC Motor MCA MOPD Voltage HP FLA 115V 1ph 1 10 2 1 2...

Page 6: ...eriod the control will attempt to restart the motor Starting current is limited to significantly less than full load current 4 Agency Listings for the motor UL File E100625 Vol 9 for Motor Vol 7 Sect...

Page 7: ...Use the airflow tables to locate the desired operating point 2 Identify the corresponding tap number from the table 3 Move Violet wire 504 to the matching connection on terminal block TB2 How to inte...

Page 8: ...010 200021 000 Page 8 DHB IOM 1 5 11 02 2023 Airflow Table ECM VE Motor...

Page 9: ...010 200021 000 Page 9 DHB IOM 1 5 11 02 2023 Airflow Table ECM VE Motor...

Page 10: ...010 200021 000 Page 10 DHB IOM 1 5 11 02 2023 Airflow Table ECM VE Motor...

Page 11: ...010 200021 000 Page 11 DHB IOM 1 5 11 02 2023 Airflow Table ECM VE Motor...

Page 12: ...rom the DH unit as indicated on Fig 10 4 Slide accessory over the discharge end of the DH unit and make sure that the DH unit is in contact with the shelf in the ac cessory cabinet as shown on Fig 11...

Page 13: ...010 200021 000 Page 13 DHB IOM 1 5 11 02 2023 Fig 11 DHB Hot water accessory installation HW Coil Accessory Module DHB Unit Assembled DHB with HW Coil Accessory Module...

Page 14: ...010 200021 000 Page 14 DHB IOM 1 5 11 02 2023 DHB Sizes 04 10 minor rev B Double Sloped Drain Pan Hand of Connection Change Instructions 3 5 2015...

Page 15: ...onic coils Is fan wheel turning the correct direction Are mixing box dampers operating properly Is the filter clean Structural Is unit properly supported Is unit installed level necessary for proper c...

Reviews: