background image

 

010-200021-000 

Page 1 

DHB IOM 1.5 11-02-2023 

DHB SERIES 

Magic Aire Fan Coil Unit – Sizes 04 through 10 

Installation, Operation and Maintenance Manual  

The 

Magic Aire

®

 Fan Coil Unit

 is 

designed for use in any air distribu-

tion system. It is easily adaptable to 

most types of existing or new forced-

air heating systems, or it can be in-

stalled in an independent air cooling 

system. 

GENERAL 
 

Immediately inspect each unit 

for damage upon receipt.  

File any 

damage claims with the freight carri-

er.  Protect stored units from dam-

age.  Do not stack more than two 

high.   
 

Use these instructions in conjunction 

with other appropriate instructions, 

including but not limited to those in-

structions supplied with the outdoor 

unit (if applicable).  Installation must 

comply with all applicable local 

codes.   

Pay particular attention to the 

following words: 

NOTE

–intended to clarify or 

make installation easier.   

CAUTION

–given to prevent 

equipment damage.   

WARNING

–to alert installer 

that personal injury and/or 
equipment damage may re-
sult if installation procedure 
is not properly followed.   

EXISTING DUCT WORK 

 

 

The previously installed air distribution system 

for heating requires close inspection to determine 

its suitability for cooling. In general, heating sys-

tems designed for outside temperatures of zero 

degrees or lower will need no alteration when used 

for cooling. However, in southern sections of the 

country, the existing heating duct work may have 

to be modified to provide better air distribution and 

insulation for cooling. 

  

DUCT INSULATION AND VAPOR PROOFING 

 

 

Properly installed heating supply ducts should 

already have adequate insulation against exces-

sive heat loss. This same insulation should there-

fore be satisfactory in the summer to protect 

against heat gain. However, depending on the 

specific installation, it may be desirable to add to 

the insulation.  
 

All externally insulated duct work must have an 

adequate vapor seal for summer operation. This is 

particularly important where the duct is exposed to 

highly humid conditions in such places as attic, 

vented crawl spaces, unconditioned basements, 

and utility rooms. The vapor seal prevents conden-

sation of moisture in the insulating material and 

subsequent loss of its insulating value.   

 

 

 

NOTE

: Consult a qualified insulation contractor 

 

to insure your system is properly insulated.   

INSTALLATION 

1.  Remove all packing and foreign material from 

unit.   

2.  Check blower wheel for free rotation.   

3.  REMOVE 2ea RED SHIPPING SCREWS (See 

Figure 1).   

4.  Check copper lines, coil etc for internal or hid-

den damage.  Maintain caps and plugs until 

ready for connection to system.   

Figure 1 

Blower Shipping 

Screws 

Summary of Contents for DHB Series

Page 1: ...general heating sys tems designed for outside temperatures of zero degrees or lower will need no alteration when used for cooling However in southern sections of the country the existing heating duct...

Page 2: ...the vertical and hori zontal dimensions of the transition piece do not increase more then one inch for every seven inches of length of the transition piece 3 Provide at least three feet of straight d...

Page 3: ...ut a TXV For best results use of the factory TXV is recom mended Field installable TXV is available as an accessory FIELD INSTALLED TXV Fig 3 Install TXV by threading on to the distributor Remove pist...

Page 4: ...010 200021 000 Page 4 DHB IOM 1 5 11 02 2023 Figure 4 Service Clearances...

Page 5: ...ts After servicing properly position electrical leads in their original supports DH Series Electrical Data PSC Motor J box only no fan relay Model PSC Motor MCA MOPD Voltage HP FLA 115V 1ph 1 10 2 1 2...

Page 6: ...eriod the control will attempt to restart the motor Starting current is limited to significantly less than full load current 4 Agency Listings for the motor UL File E100625 Vol 9 for Motor Vol 7 Sect...

Page 7: ...Use the airflow tables to locate the desired operating point 2 Identify the corresponding tap number from the table 3 Move Violet wire 504 to the matching connection on terminal block TB2 How to inte...

Page 8: ...010 200021 000 Page 8 DHB IOM 1 5 11 02 2023 Airflow Table ECM VE Motor...

Page 9: ...010 200021 000 Page 9 DHB IOM 1 5 11 02 2023 Airflow Table ECM VE Motor...

Page 10: ...010 200021 000 Page 10 DHB IOM 1 5 11 02 2023 Airflow Table ECM VE Motor...

Page 11: ...010 200021 000 Page 11 DHB IOM 1 5 11 02 2023 Airflow Table ECM VE Motor...

Page 12: ...rom the DH unit as indicated on Fig 10 4 Slide accessory over the discharge end of the DH unit and make sure that the DH unit is in contact with the shelf in the ac cessory cabinet as shown on Fig 11...

Page 13: ...010 200021 000 Page 13 DHB IOM 1 5 11 02 2023 Fig 11 DHB Hot water accessory installation HW Coil Accessory Module DHB Unit Assembled DHB with HW Coil Accessory Module...

Page 14: ...010 200021 000 Page 14 DHB IOM 1 5 11 02 2023 DHB Sizes 04 10 minor rev B Double Sloped Drain Pan Hand of Connection Change Instructions 3 5 2015...

Page 15: ...onic coils Is fan wheel turning the correct direction Are mixing box dampers operating properly Is the filter clean Structural Is unit properly supported Is unit installed level necessary for proper c...

Reviews: