FMC-EIS-120

09/15

TECHNICAL DATA

FREE AREA  FOR THE AIR  PASS(m

2

)

Dpt(Pa)

Ø

 nominal

(mm)

Afree

(m

2

)

Qmin

(m

3

/h)

Qmax

(m

3

/h)

100

0,0045

47

235

125

0,008

76

382

150

0,0125

113

564

160

0,0146

129

646

200

0,0244

207

1034

250

0,0403

329

1645

300

0,0601

480

2398

315

0,0668

530

2651

PRESSURE DROP AND SOUND POWER LEVEL

Pa (Pa)

20

200

2000

2

3

4

5

6

7

8

9

10

3000

100

Ø315

Ø250

Ø200

Ø160

Ø125

Ø100

1000

Q (m

3

/h)

V(m/s)

0

5

10

15

20

25

30

35

40

45

50

55

60

65

70

2

3

4

5

6

7

8

9

10

DPt (Pa)

70

20

V(m/s)

Summary of Contents for FMC-EIS-120

Page 1: ...when reaches that temperature Reset is manual except for motorized dampers The fire dampers FMC EIS 120 work as a separator between two sectors of fire and ensure the same fire resistance that the str...

Page 2: ...S 500Pa Rigid wall Brick wall 110 mm Built in 0 360 EI 120 ve i o S 500Pa Rigid floor Reinforced concrete 150 mm Built in 0 360 EI 120 ho i o S 500Pa Sensing element load bearing capacity Sensing ele...

Page 3: ...n 100 150 160 200 250 300 mm mm 98 123 148 158 198 248 298 H1 mm 315 313 6 31 38 125 Dn 100 150 160 200 250 300 mm mm 98 123 148 158 198 248 298 H1 mm 315 313 6 31 38 1 Casing 2 Rubber sealing ring 3...

Page 4: ...rd Internal and external thermoelectrical fuse 72 C Automatic resetting Automatic closing by fuse 72 C Remote closing by interruption of power supply Manual test switch LED status fusible indicator Po...

Page 5: ...ction of wall floor Placement in wall floor Device position Wall Floor Device position 0 360 The minimum distance between fire dampers and construction elements will be 75mm The minimum distance betwe...

Page 6: ...ION SUPPORT Place the damper next the construction support indicated line which is painted on the label The arrows show the construction support direction B TEST MEASUREMENTS After placing the damper...

Page 7: ...ing Open and close the damper to check that the blade does not touch the duct SWITCHES NORMALLY CLOSED CONTACTS COM NF NO COM NF NO FC DC Closed damper signal Open damper signal CONTACT FC COM NO NF B...

Page 8: ...to European Standard series FMC EIS 120 M7F230V diam Operated by means of a servomotor at 230V M7F230 with closed switches Circular dampers made from galvanized steel and non combustible board Therma...

Page 9: ...125 0 008 76 382 150 0 0125 113 564 160 0 0146 129 646 200 0 0244 207 1034 250 0 0403 329 1645 300 0 0601 480 2398 315 0 0668 530 2651 PRESSURE DROP AND SOUND POWER LEVEL Pa Pa 20 200 2000 2 3 4 5 6...