DECLARATION OF PERFORMANCE

V15-09

Fire damper  

“FMC-EIS-120”

Madel Air Technical Diffusion S.A, 
C/ Pont de les Bruixes P-5, P.I. La Gavarra, 08540 CENTELLES (Barcelona) 

To prevent fire and reduce smoke spreading from one fire compartment to
another through the air ductwork system which may penetrate fire separating
vertical compartments, according to Standard EN 15650:2010 (annex ZA.1).

System 1, according to Construction Products Regulation nº 305/2011

APPLUS - 0370                                                                                                                                                                                                   
Performed tasks:
- Determination of the product type on the basis of type testing (including
sampling), type calculation, tabulated values or descriptive documentation of 
the
product;
- Initial inspection of the manufacturing plant and of factory production control;
- Continuous surveillance, assessment and evaluation of factory production 
control.

System 1
Certification number: 0370 

– CPR – 3178

Test report: 
15/10323-820
15/10323-819
15/10702-2171

6. Performances (EN 15650 :2010):

Performances

Dimensions

Type

Wall

Type of 

installation

Mechanism 

orientation

Class

Rigid wall

Reinforced 

concrete

≥ 110 mm

Built-in

0-360º

EI 120 (v

e

  i

↔o) S (500Pa)

Rigid wall

Brick wall

 

≥ 110 mm

Built-in

0-360º

EI 120 (v

e

  i

↔o) S (500Pa)

Rigid floor

Reinforced 

concrete

 

≥ 150 mm

Built-in

0-360º

EI 120 (h

o

  i

↔o) S (500Pa)

Sensing element load bearing capacity

Sensing element response temperature

Closure time

50 cycles

…- /MA/ - 300 cycles

…- /M7F…V/ - 10.200 cycles

Sensing element response temperature and load bearing capacity

Opening and Closing cycle

1. Product and identification name:

Ø

 

100 - 315 mm

Essential characteristics

Cycling (opening and closing) on fire test.

Cycling (opening and closing) according to Standard for CE Marking

5. Certification body:

DECLARATION OF PERFORMANCE (Nº 0370-CPR-2178)

Approved

Approved

Approved

Joan Arcarons Alibés
(Technical Director)

Durability of operational reliability according to 15650:

7. The performances of the product identified in point 1, are in line with the declared performance in point 6.
This declaration of performance is issued under the responsibility of the
manufacturer listed in point 2.
Signed for and on behalf of the manufacturer:

Centelles,09/09/2015

Nominal activation conditions/ sensitivity:

Response delay according to EN 1366-2:

Approved

Durability of response delay according to EN1366-2:

4. Assessment of conformity system:

Operational reliability according to EN 1366-2

3. Uses to:

2. Name and address of manufacturer:

Summary of Contents for FMC-EIS-120

Page 1: ...when reaches that temperature Reset is manual except for motorized dampers The fire dampers FMC EIS 120 work as a separator between two sectors of fire and ensure the same fire resistance that the str...

Page 2: ...S 500Pa Rigid wall Brick wall 110 mm Built in 0 360 EI 120 ve i o S 500Pa Rigid floor Reinforced concrete 150 mm Built in 0 360 EI 120 ho i o S 500Pa Sensing element load bearing capacity Sensing ele...

Page 3: ...n 100 150 160 200 250 300 mm mm 98 123 148 158 198 248 298 H1 mm 315 313 6 31 38 125 Dn 100 150 160 200 250 300 mm mm 98 123 148 158 198 248 298 H1 mm 315 313 6 31 38 1 Casing 2 Rubber sealing ring 3...

Page 4: ...rd Internal and external thermoelectrical fuse 72 C Automatic resetting Automatic closing by fuse 72 C Remote closing by interruption of power supply Manual test switch LED status fusible indicator Po...

Page 5: ...ction of wall floor Placement in wall floor Device position Wall Floor Device position 0 360 The minimum distance between fire dampers and construction elements will be 75mm The minimum distance betwe...

Page 6: ...ION SUPPORT Place the damper next the construction support indicated line which is painted on the label The arrows show the construction support direction B TEST MEASUREMENTS After placing the damper...

Page 7: ...ing Open and close the damper to check that the blade does not touch the duct SWITCHES NORMALLY CLOSED CONTACTS COM NF NO COM NF NO FC DC Closed damper signal Open damper signal CONTACT FC COM NO NF B...

Page 8: ...to European Standard series FMC EIS 120 M7F230V diam Operated by means of a servomotor at 230V M7F230 with closed switches Circular dampers made from galvanized steel and non combustible board Therma...

Page 9: ...125 0 008 76 382 150 0 0125 113 564 160 0 0146 129 646 200 0 0244 207 1034 250 0 0403 329 1645 300 0 0601 480 2398 315 0 0668 530 2651 PRESSURE DROP AND SOUND POWER LEVEL Pa Pa 20 200 2000 2 3 4 5 6...

Reviews: