MADDALENA microCLIMA ULTRA Installation And Operating Instructions Manual Download Page 12

 

 

 

 

 

 

2015_03_03 

 

 

 

 

 

 

12 

 

If fewer read-outs are carried out, the unused ‚credit’ is stored in the instrument and can be used later. 
During M-Bus communication with the calculator the other interfaces (push-button, optical interface) of the device 
cannot be used. 

13.2.6

 

M-Bus addresses 

Calculators with the M-Bus option can be addressed primarily or secondarily.  
Both addresses can be set via the optical interface using the Device Monitor or via the M-Bus interface.  
The factory setting of the ID-No. (secondary address) is identical to the serial no. 

13.3

 

Radio interface wireless M-Bus EN 13757-3, EN 13757-4 (optional) 

The radio interface is for the transmission of meter data (absolute values). 

General information about the radio interface 

Installation of radio components between or behind heating pipes, or the presence of other bulky obstacles directly 
over or in front of the housing must be avoided. 
The  transmission  quality  (range,  telegram  processing)  of  radio  components  can  be  negatively  influenced  by 
instruments  or  equipment  with  electromagnetic  emissions,  such  as  telephones  (particularly  LTE  mobile  radio 
standard), Wi-Fi routers, baby monitors, remote control units, electric motors, etc. 
In  addition,  the  construction  of  the  building  has  a  strong  influence  on  the  transmission  range  and  coverage. 
Furthermore, when using installation boxes (substations) they must be equipped with non-metallic covers or doors. 
The factory-setting of the meters clock is standard (winter) Central European Time (GMT +1). There is no automatic 
changeover to daylight savings (summer) time. 
The radio function is deactivated upon delivery (factory-setting). See section 0 “

*Factory settings may vary from the 

above. 

Activation of the radio interface”

13.3.1

 

Technical data radio 

Frequency 

868 MHz 

Transmission power 

up to 12 dBm 

Protocol 

wireless M-Bus based on EN 13757-3 

Selectable modes  

S1/T1/C1 

Telegrams 

-

 

Short telegram conform to AMR (OMS-Spec_Vol2_Primary_v301): energy 
(heat/cooling energy, pulse input 1, pulse input 2), total volume, flow, power, 
information message, return flow temperature, temperature difference  

-

 

Long telegram for walk-by read-out: energy (heat/cooling energy, pulse input 1, 
pulse input 2), total volume, information message, 15 monthly values 

Encryption

 

AES: Advanced Encryption Standard; key length: 128 bits

 

13.3.2

 

Radio configuration* 

Parameter  

Possible settings 

Factory setting 

Mode  

S1/T1/C1; unidirectional 

T1 (unidirectional) 

Transmission period  

00:00 - 24:00; any time period in the day  

7:00 am - 7:00 pm 

Transmission interval   120 seconds - 240 minutes 

120 seconds (heat meters) 

Weekdays  

Monday – Sunday (any weekday) 

Monday - Friday 

Weeks in a month  

1 – 4 (4: uninterrupted, incl. a possible 5

th

 week) 

1 – 4 (4: uninterrupted) 

Months  

1 - 12 

1 - 12 

Radio activation date   01.01 - 31.12. (day. Month) 

not set 

AES-128- Encryption  

-

 

Not encrypted; 

-

 

Encrypted: 
-

 

Master Key 

Master Key; not activated 

Summary of Contents for microCLIMA ULTRA

Page 1: ...lations for electrical installations are to be observed This product fulfils the requirements of the European Council Directive on Electromagnetic Compatibility EMC Directive 2004 108 EC The identific...

Page 2: ...be implemented at the installation site 4 2 General information on the ow sensor Be careful not to pick up the ow sensor on the plastic housing Always pick up and carry the sensor on the threaded or...

Page 3: ...9 3 260 12 60 24 180 14 4 5 3 DN25 5 10 200 G 2 20 100 40 130 28 8 8 2 6 300 110 30 9 5 4 Mounting position Cooling meter See section 5 Installation for Cooling Applications Straight pipe sections Non...

Page 4: ...g System Please inspect and check all dimensions to be sure that there is suf cient space in the intended location for installation of the ow sensor Flush the system thoroughly before installing the o...

Page 5: ...w The calculator should be mounted on the wall for example Attention must be paid that the cables connected to the calcu lator are laid such that condensation water cannot run along them and into the...

Page 6: ...lable which makes it possible for the wall mounting support to be mounted using standardized drill holes The centre to centre drill hole separation for the wall mounting unit and direct screw mounting...

Page 7: ...on Slowly open the shut off valves Check that there are no leaks Check the following points Are all the shut off valves open Is the meter of the right size Is the heating heating cooling system clear...

Page 8: ...dress factory setting is the serial number 10 Tariff register 1 Value alternating with tariff register no and criteria2 11 Tariff register 2 Values alternating with tariff register no and criteria2 12...

Page 9: ...to 100 3 to 130 for temperature range 1 to 180 C Temperature difference cooling K 3 to 50 Calculation of heat from K 0 05 Calculation of cooling from K 0 05 Dual purpose heat cooling meter K HC 0 5 Re...

Page 10: ...lustrations that apply depending on the interface Connection of M Bus Connection of pulse outputs or inputs Connection of pulse outputs heat cooling Connection of power pack Polarity is not important...

Page 11: ...magnetic disturbances IEC 60364 5 51 2005 04 Electrical installations of buildings Part 5 51 Selection and erection of electrical equipment Common rules IEC 60364 5 54 2011 03 Low voltage electrical i...

Page 12: ...tallation boxes substations they must be equipped with non metallic covers or doors The factory setting of the meters clock is standard winter Central European Time GMT 1 There is no automatic changeo...

Page 13: ...on of the installation mode only compact telegrams will be transmitted 13 4 Two additional pulse inputs optional only in conjunction with M Bus or radio With this option additional instruments with pu...

Page 14: ...h pulse without unit 1000 litres kWh pulse without unit Installation notes for pulse inputs It is important that the pulse cables are not be affected by or exposed to the M Bus voltage Check the polar...

Page 15: ...onic switch according to EN 1434 2 2007 Pulse values See chapter 13 5 1 to 13 5 3 Peak switching current 300 mA Switching voltage maximum 35 V Switching power maximum 300 mW Contact isolation 109 Ohm...

Page 16: ...ed circuited Rf sensor fault No calculations are carried out The registers for flow and energy are not being updated no new data is being stored Sensor cable severed sensor cable shorted circuited Int...

Page 17: ...Directive 2004 108 EC on EMC Directive 2006 95 EC on low voltage Directive 1999 5 EC R TTE The complete signed declaration can be found at www engelmann de 16 Manufacturer Engelmann Sensor GmbH Rudolf...

Reviews: