MADDALENA microCLIMA ULTRA Installation And Operating Instructions Manual Download Page 11

 

 

 

 

 

 

2015_03_03 

 

 

 

 

 

 

11 

 

13.2.1

 

General information about the M-Bus interface 

It  is  important  to  note  that  the  acknowledged  state of  the  art  technology  rules  and  the  relevant  legal  restraints 
(international and local; see 13.2.2 “Relevant norms, standards and literature on the M-Bus”) are to be observed. 
The installation has to be performed by authorized, skilled persons. 
If the regulations and the information in the installation and operating instruction manuals are not strictly followed, 
or if the installation is shown to be faulty, any resulting expenses will be charged to the company responsible for 
the installation. 
Recommended type of cable: Telephone cable J-Y(ST)Y 2x2x0.8mm². 
It is important to make sure that the topology of the M-Bus network (cable lengths and cross-sections) is suitable 
for the 

baud rate (2400 Bd) 

of the end instruments.  

Further information can be found in the detailed ‘Application Note M-Bus’ at 

www.engelmann.de

. 

13.2.2

 

Relevant norms, standards and literature on the M-Bus 

IEC 60364-4-41 (2005-12) 

Low-voltage electrical installations - Part 4-41: Protection for safety - 
Protection against electric shock 

IEC 60364-4-44 (2007-08) 

Low-voltage electrical installations - Part 4-44: Protection for safety - 
Protection against voltage disturbances and electromagnetic disturbances 

IEC 60364-5-51 (2005-04) 

Electrical installations of buildings - Part 5-51: Selection and erection of 
electrical equipment - Common rules 

IEC 60364-5-54 (2011-03) 

Low-voltage electrical installations - Part 5-54: Selection and erection of 
electrical equipment - Earthing arrangements and protective conductors 

EN 50310 (2010) 

Application of equipotential bonding and earthing in buildings with 
information technology equipment 

EN 13757-1:2002, 2:2004, 3:2004 

Communication systems for meters and remote reading of meters 

The M-Bus 

A Documentation, Version 4.8, M-Bus User group 

TI Technical Journal 

Texas Instruments Technical Journal Vol. 8, 1991 M-Bus 

13.2.3

 

Additional technical specifications 

The  installation  has  to  fulfil  the  requirements  of  the  relevant  norms,  standards  and  literature  (see  paragraph 
13.2.2) and the specifications as follows: 

Maximum voltage M-Bus 

42 V 

Minimum voltage M-Bus 

21 V 

Maximum ripple voltage 

200 mV; EN 13757-2:2004; 4.3.3.6 

Maximum voltage potential 
differences 

2 V 

13.2.4

 

Technical data M-Bus 

Primary address 

0 (factory setting); 1 – 250 (configurable) 

Baud rate 

2400; 300 (auto speed detect) 

13.2.5

 

Number of read-outs  

The number of possible read-outs depends on the number of instruments in the M-Bus network  

Number of instruments in 
network 

Read-outs per day primary 
address 

Read-outs per day secondary 
address (without using SND NKE) 

655 

275 

20 

485 

170 

60 

300 

90 

120 

190 

52 

250 

105 

27 

Table is only valid for Baud rate 2400! 

Summary of Contents for microCLIMA ULTRA

Page 1: ...lations for electrical installations are to be observed This product fulfils the requirements of the European Council Directive on Electromagnetic Compatibility EMC Directive 2004 108 EC The identific...

Page 2: ...be implemented at the installation site 4 2 General information on the ow sensor Be careful not to pick up the ow sensor on the plastic housing Always pick up and carry the sensor on the threaded or...

Page 3: ...9 3 260 12 60 24 180 14 4 5 3 DN25 5 10 200 G 2 20 100 40 130 28 8 8 2 6 300 110 30 9 5 4 Mounting position Cooling meter See section 5 Installation for Cooling Applications Straight pipe sections Non...

Page 4: ...g System Please inspect and check all dimensions to be sure that there is suf cient space in the intended location for installation of the ow sensor Flush the system thoroughly before installing the o...

Page 5: ...w The calculator should be mounted on the wall for example Attention must be paid that the cables connected to the calcu lator are laid such that condensation water cannot run along them and into the...

Page 6: ...lable which makes it possible for the wall mounting support to be mounted using standardized drill holes The centre to centre drill hole separation for the wall mounting unit and direct screw mounting...

Page 7: ...on Slowly open the shut off valves Check that there are no leaks Check the following points Are all the shut off valves open Is the meter of the right size Is the heating heating cooling system clear...

Page 8: ...dress factory setting is the serial number 10 Tariff register 1 Value alternating with tariff register no and criteria2 11 Tariff register 2 Values alternating with tariff register no and criteria2 12...

Page 9: ...to 100 3 to 130 for temperature range 1 to 180 C Temperature difference cooling K 3 to 50 Calculation of heat from K 0 05 Calculation of cooling from K 0 05 Dual purpose heat cooling meter K HC 0 5 Re...

Page 10: ...lustrations that apply depending on the interface Connection of M Bus Connection of pulse outputs or inputs Connection of pulse outputs heat cooling Connection of power pack Polarity is not important...

Page 11: ...magnetic disturbances IEC 60364 5 51 2005 04 Electrical installations of buildings Part 5 51 Selection and erection of electrical equipment Common rules IEC 60364 5 54 2011 03 Low voltage electrical i...

Page 12: ...tallation boxes substations they must be equipped with non metallic covers or doors The factory setting of the meters clock is standard winter Central European Time GMT 1 There is no automatic changeo...

Page 13: ...on of the installation mode only compact telegrams will be transmitted 13 4 Two additional pulse inputs optional only in conjunction with M Bus or radio With this option additional instruments with pu...

Page 14: ...h pulse without unit 1000 litres kWh pulse without unit Installation notes for pulse inputs It is important that the pulse cables are not be affected by or exposed to the M Bus voltage Check the polar...

Page 15: ...onic switch according to EN 1434 2 2007 Pulse values See chapter 13 5 1 to 13 5 3 Peak switching current 300 mA Switching voltage maximum 35 V Switching power maximum 300 mW Contact isolation 109 Ohm...

Page 16: ...ed circuited Rf sensor fault No calculations are carried out The registers for flow and energy are not being updated no new data is being stored Sensor cable severed sensor cable shorted circuited Int...

Page 17: ...Directive 2004 108 EC on EMC Directive 2006 95 EC on low voltage Directive 1999 5 EC R TTE The complete signed declaration can be found at www engelmann de 16 Manufacturer Engelmann Sensor GmbH Rudolf...

Reviews: