TXP-C20_Instruction_Manual_(Rev1.0)
REV – 1.0
[34-2900-0207-5 ]
36
|
P a g e
5.2
TXP-C20 PY NEMA 4X Polycarbonate Wall Mount Enclosure
The TXP-C20 PY wall mount NEMA 4X enclosure is shown in Figure 5-3. Non-metallic enclosures are not grounded
by metal conduit. For internal ground points to be grounded to earth, the TB5 – GND terminal must have a proper
earth ground connection.
CAUTION
: NONMETALLIC ENCLOSURE DOES NOT PROVIDE GROUNDING BETWEEN CONDUIT
CONNECTIONS. USE GROUNDING TYPE BUSHINGS AND JUMPER WIRES. ALL FIELD WIRING MUST HAVE
INSULATION SUITABLE FOR AT LEAST 250V.
Figure 5-3 – PY NEMA 4X Enclosure