12
Power Up
The GD-6 cycles through an internal self-test cycle for the first minute that it is powered. The unit will execute the test cycle any time
power is dropped and reapplied (i.e. power failure). During the self-test cycle the unit will display the firmware version number, then
count down from 60 to 0 (if the display setting is “On”) and finally go into normal operation. The alarm relay will be activated for 10
seconds and the fan relay for 60 seconds during the power-up cycle unless the “Power Up Test” (PUt) option is OFF. The indicator light
(LED) will flash green during the self-test cycle. At the end of the 1 minute cycle, the unit will take its first sample of the air and the
indicator light will turn solid green.
Operation
1.
With the display function turned “On”, the GD-6 will show the current concentration of gas % LEL or “0” (zero) in clean air.
When the gas concentration reaches the Fan Relay setting (10% LEL, for example) the display will flash back and forth
between “FAn” and “10”. With the display function turned ”Off”, the display does not show the gas concentration, but will show
“FAn” as long as the fan relay is activated.
2.
With the display function turned “On” and the gas concentration reaching the alarm relay setting, (20% LEL, for example) the
display will flash back and forth between “ALr” and “20”. The buzzer will sound indicating “Alarm” if the buzzer is turned “On”.
With the display function turned off the display does not show the gas concentration, but will show “ALr” when the Alarm relay
is activated.
3.
With the 4-20 mA function turned “On”, the 4-20 mA output will correspond to the concentration (0-50% LEL). The display will
show “FAn” and “ALr” and sound as outlined above.
Default Configuration – Factory Settings
The default Gas setting is mE (methane)
The default Power Up Test setting is On
The default Display setting is Off
The default Buzzer setting is Off
The default Alarm Relay Setting is activation at 20% LEL
The default Alarm Relay Configuration is Normally Open
The default Fan Relay Setting is activation at 10% LEL
The default Fan Relay Delay setting is 3 minutes
The default Fan Relay Runtime setting is 0 minutes
The default Fan Relay Latching condition is OFF
The default Trouble Fan Setting condition is OFF
The default 4-20 mA Output setting is On
To change settings, remove the Philips screw on the front of the GD-6. Pull off the front cover of the unit.