Macurco GBC Manual
REV – 1.2
[34-2900-0690-7]
4
|
P a g e
2.2
Models Options
Model Number
Number of Relays
Input Voltage
GBC-2-24
2 Relays
24 Volts AC or DC
GBC-4-24
4 Relays
24 Volts AC or DC
GBC-6-24
6 Relays
24 Volts AC or DC
GBC-8-24
8 Relays
24 Volts AC or DC
GBC-2-120
2 Relays
120 Volts AC
GBC-4-120
4 Relays
120 Volts AC
GBC-6-120
6 Relays
120 Volts AC
GBC-8-120
8 Relays
120 Volts AC
Table 2-1 – Model Options
2.3
Features
•
Shutdown up to 8 boilers individually via expansion relays
•
Customize up to 4 Expansion Relay Boards
•
24 VDC driver for horn/strobe (250 mA)
•
Audible Buzzer 90 dBA at 1ft
•
Output power supports combinations of 1 to 4 detector(s) (350 mA)
2.4
Specifications
•
Size: 8” x 6” x 3” (22.9 X 20.3 X 5 cm)
•
Weight: 3lbs.
•
Enclosure: Opaque Polycarbonate, NEMA 4X/6P (IP66/68)
•
Operating Temperature: 32 °F to 125 °F (0 °C to 52 °C)
•
Ambient humidity: 0% to 95% RH non-condensing
•
Voltage/Current:
o
GBC-X-24: 24 VAC or 24 VDC
o
GBC-X-120: 120 VAC
•
Relay Rating: SPDT, 120/240 VAC, 10 A Max (resistive)
•
Status Indicators (LED): Power, Alarm
•
Current at 24V
o
Sensor Connections: (Max 4) 3W ea., 0.125 mA ea.
o
Green & Red LED: 20 mA ea.
o
Buzzer: 30 mA ea.
o
4 x Expansion Relay Modules (2 relays ea.) 40 mA ea.
o
Horn / Strobe Output: 250 mA
Summary of Contents for GBC-2-120
Page 6: ...Macurco GBC Manual REV 1 2 34 2900 0690 7 6 P a g e Figure 3 2 Enclosure Dimensions ...
Page 7: ...Macurco GBC Manual REV 1 2 34 2900 0690 7 7 P a g e Figure 3 3 Mounting dimensions ...
Page 11: ...Macurco GBC Manual REV 1 2 34 2900 0690 7 11 P a g e Figure 3 6 Single Sensor Channel Wiring ...
Page 12: ...Macurco GBC Manual REV 1 2 34 2900 0690 7 12 P a g e Figure 3 7 Dual Sensor Channel Wiring ...
Page 16: ...Macurco GBC Manual REV 1 2 34 2900 0690 7 16 P a g e Figure 4 3 Relay Designation ...