Macurco GBC Manual
REV – 1.2
[34-2900-0690-7]
15
|
P a g e
•
Relay Split (J6)
o
Jumper position 1 & 2 – “All”. (Default)
PCBA Rev 0.1: the “All” setting activates all populated relays 1-8 simultaneously
based on activation from sensors connected to Sensor 1 terminal.
Note:
When the jumper is set to “All” Sensor 2 terminal will
NOT
engage any of the
relays. Only the local buzzer (if jumper is enabled) and external horn/strobe will be
engaged during activation from the connected sensors.
o
Jumper position 2 & 3 – “Split”.
All populated relays 1 through 4 will activate simultaneously based on activation
from sensors connected to Sensor 1 terminal. The local buzzer (if jumper is
enabled) and external horn/strobe engages.
All populated relays 5 through 8 will activate simultaneously based on activation
from sensors connected to Sensor 2 terminal. The local buzzer (if jumper is enabled)
and external horn/strobe engages.
Figure 4-2 – Relay Jumper (J6)