Macurco CD-6G Operation Manual
REV – 1.0
[34-2900-0510-9 ]
17
|
P a g e
4.4
4-20mA Loop
Clean Air – With the 4-20 mA function turned “On” and the current concentration of CO
P
2
P
ppm, the 4-20mA loop will output a
mA reading equivalent to the current gas reading of the detector.
Fan Level – With the 4-20 mA function turned “On” and the current concentration of CO
P
2
P
ppm detected is at or greater than the
Fan Relay Setting (Frs), the 4-20mA loop will output between 4 mA and 20 mA depending on the current concentration of CO
P
2
P
.
-9 12-Series 4-20 mA Output diagram
Alarm Level – With the 4-20 mA function turned “On” and the current concentration of CO
P
2
P
ppm detected is at or greater than
the Alarm Relay Setting (Ars), the 4-20mA loop will output between 4 mA and 20 mA depending on the current concentration of
CO
P
2
P
figure 3-9 12-Series 4-20 mA Output diagram
Trouble – With the 4-20 mA function turned “On” and Trouble Fan Setting enabled. The 4-20mA loop will output less than 4 mA
or greater than 20 mA depending on the Trouble condition. See section
4.5
Default – Factory Settings
Setting:
Default:
Power Up Test
Off
Display
On
Buzzer
On
Alarm Relay Setting
0.50% vol.
Alarm Relay Configuration
Normally Open (NO)
Fan Relay Setting
0.20% vol.
Fan Relay Delay
3 minutes
Fan Relay Minimum Runtime
0 minutes
Fan Relay Latching
Off
Trouble Fan Setting
Off
Awareness Alarm
Off
4-20mA
bAS
CAL
diS
Table 4-1 – Default settings
Summary of Contents for CD-6G
Page 2: ......
Page 5: ...Macurco CD 6G Operation Manual REV 1 0 34 2900 0510 9 4 P a g e ...
Page 44: ......
Page 47: ...Macurco CD 6G Operation Manual REV 1 0 34 2900 0510 9 4 L a p a g e ...
Page 64: ...Macurco CD 6G Operation Manual REV 1 0 34 2900 0510 9 21 L a p a g e ...
Page 88: ......
Page 91: ...Macurco CD 6G Operation Manual REV 1 0 34 2900 0510 9 4 p á g i n a ...