49647
Issue 1
Date: October 2019
www.edisonlightingdirect.com
Page 1 of 2
INSTALLATION INSTRUCTIONS
EL1500WH
Refer to website
data
DESCRIPTION
A self contained LED luminaire incorporating an LED module
and battery pack. Built into the system is a deep discharge
protection circuit for use with 3.6V 1.7Ah NiMH battery pack.
LUMINAIRE DIMENSIONS (mm)
SPECIFICATION
Supply Voltage
230Vac
10% 50/60 Hz
Supply Current
30mA max
Ambient Temperature
0
C to +35
C
Conductor size
2.5mm
2
max
Weight of Control Gear
246g (incl. battery)
Average Lumen Output
56lm
IP Rating of Luminaire
IP30
BATTERIES
The luminaire includes a 1.7Ah rechargeable NiMH battery pack
for 3 hour operation. Batteries must be replaced when the
luminaire no longer meets 3 hours duration.
RELEVANT STANDARDS
EN 61347-2-7
Lamp control gear
EN 60598-2-22
Luminaire
BS5266-1:2005/IEC62034 Automatic Testing
WARRANTY
This product is guaranteed for three years and covers faulty
workmanship and materials. The guarantee on the NiMH
batteries is one year. This “Return to Base” warranty requires
that the product is used within the terms and conditions stated
above, in our literature and on our website. Products returned to
us under warranty must be carriage paid. Mackwell Electronics
Ltd accepts no liability for costs incurred.
IMPORTANT
Please ensure that the information contained in this leaflet is
passed on to the user/maintenance engineer.
ELECTRICAL INSTALLATION
The luminaire should be installed by a qualified person in
accordance with the current wiring and building regulations.
Luminaires comply with the EMC directive in both modes of
operation, mains and emergency. The battery lead should be
connected only at the time of commissioning. Remove
transparent plastic cover to attach L & N.
Replace transparent plastic cover to avoid electric shock.
The LED is non-replaceable and the supplier should be
contacted in the unlikely event of a failure.
IMPORTANT
Mark the luminaire with the date of commissioning in the space
provided on the label
OPERATION
Upon connection of a permanent mains supply the indicator LED
lights to show the battery is receiving charge. Following an initial
charging period of 24 hours the unit will be capable of providing
3 hours emergency duration.