background image

 

 

49647 

Issue 1 

Date: October 2019 

www.edisonlightingdirect.com 

Page 1 of 2 

 

 

 

 

 

 

 

INSTALLATION INSTRUCTIONS  

EL1500WH 

 

Refer to websit

www.edisonlightingdirect.com

 for specific 

data 

 

DESCRIPTION 

A self contained LED luminaire incorporating an LED module 

and battery pack.  Built into the system is a deep discharge 

protection circuit for use with 3.6V 1.7Ah NiMH battery pack.    

 

LUMINAIRE DIMENSIONS (mm) 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

SPECIFICATION 

Supply Voltage   

230Vac 

 10% 50/60 Hz 

Supply Current   

30mA max 

Ambient Temperature  

0

C to +35

Conductor size   

2.5mm

2

 max

 

 

Weight of Control Gear 

246g (incl. battery) 

Average Lumen Output 

56lm 

IP Rating of Luminaire 

IP30 

 

BATTERIES 

The luminaire includes a 1.7Ah rechargeable NiMH battery pack 

for 3 hour operation.  Batteries must be replaced when the 

luminaire no longer meets 3 hours duration. 

 

RELEVANT STANDARDS

 

EN 61347-2-7 

 

 Lamp control gear 

EN 60598-2-22   

 Luminaire 

BS5266-1:2005/IEC62034  Automatic Testing 

 

WARRANTY

 

This product is guaranteed for three years and covers faulty 

workmanship and materials. The guarantee on the NiMH 

batteries is one year. This “Return to Base” warranty requires 

that the product is used within the terms and conditions stated 

above, in our literature and on our website. Products returned to 

us under warranty must be carriage paid.  Mackwell Electronics 

Ltd accepts no liability for costs incurred. 

 

IMPORTANT 

Please ensure that the information contained in this leaflet is 

passed on to the user/maintenance engineer. 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

ELECTRICAL INSTALLATION 

The luminaire should be installed by a qualified person in 

accordance with the current wiring and building regulations. 

 

Luminaires comply with the EMC directive in both modes of 

operation, mains and emergency.  The battery lead should be 

connected only at the time of commissioning.  Remove 

transparent plastic cover to attach L & N.   

Replace transparent plastic cover to avoid electric shock. 

The LED is non-replaceable and the supplier should be 

contacted in the unlikely event of a failure. 

 

IMPORTANT 

Mark the luminaire with the date of commissioning in the space 

provided on the label 

 

OPERATION

 

Upon connection of a permanent mains supply the indicator LED 

lights to show the battery is receiving charge. Following an initial 

charging period of 24 hours the unit will be capable of providing 

3 hours emergency duration. 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Reviews: