INSTALLATION INSTRUCTIONS FOR:

VISTRAL 

self-contained emergency luminaire

1

1

2

2

3

3

1. Remove diffuser by inserting a screwdriver 

and prise out.

2. Remove lamp.

3. Remove reflector moulding by moving the 

lamp holders inwards.

When refitting reflector moulding ensure 
correct orientation.

Battery Replacement

Performance of the luminaire is dependent on the use of the correct type of   high 
temperature nickel-cadmium battery.
Battery life may be impaired if the luminaire is mounted in an ambient temperature 
greater than 25°C.   Store the luminaire or battery between 0°C and 25°C.  Replace 
with high temperature nickel-cadmium battery to the manufacturer's recommended 
part number. Connect the red lead to positive (+), the black lead to negative (-).  
Take care not to damage the sleeving.   The battery should be replaced when the 
rated duration is no longer achieved.   

Warning: 

When disposing of the battery do not pierce, incinerate or short circuit.   

The battery contains  cadmium and should therefore be disposed of in accordance 
with recognized disposal methods.

Safe Installation and Operation

1. Check the rating label for voltage and frequency before connecting to the 

electrical supply.

2. Ensure the mains supply is switched off and the battery disconnected when 

working on this luminaire, whether installing, re-lamping or carrying out any other 
servicing.

3. Use only the correct lamp and battery as indicated on the luminaire label.
4. Ensure the fixing is adequate for the luminaire weight.

Servicing

1. Ensure this instruction leaflet and recommendations for periodic inspection and 

test are presented to the authority responsible for the operation and maintenance 
of this luminaire.

2. Servicing, e.g. cleaning and lamp replacement, must only be carried out after the 

electricity supply has been switched off. Do not assume a luminaire with no lamps 
alight is switched off, always check before servicing. Do not touch the lamp pins 
or any terminals without first disconnecting the battery.

3. Cleaning should be carried out at regular intervals to ensure dirt does not 

accumulate to an extent that will impair the thermal safety of the luminaire. 
Regular cleaning will help to maintain the optical performance of the luminaire.

4. Failed lamps, starter switches and batteries must be replaced as soon as 

practicable by components of the same type. Replace the battery when the 
luminaire fails to achieve the rated duration marked on the luminaire.

This luminaire complies with BS EN 60598-2-22 and is suitable for interior use 
including defined escape routes. Normal ambient temperature 0°C to +25°C. 

Rated lumen output

Rated minimum luminaire output   in emergency mode in accordance with EN 
60598-2-22 is  70 lumens.              
This value is provided to permit checking of correct operation, determination of the 
lighting level on an escape route can only be made with full photometric data. 
Spacing to height tables are published in the Cooper Lighting and Safety catalogue. 