HydroController Parameters
Number
Name
Range
Description
00
Password
[0, 11000] Password for changing data setting
01
Max Frequency
[39.99,
99.99]
Max output frequency of the drive
02
Language
[Italiano,
English]
Language Setting
03
Nominal Freq.
[29.99,
99.99]
It sets the frequency in order to have Vmax
04
Configuration
[0, 2]
It sets master or slave configuration for the device
06
Acceleration
[0.7, 5.0] It sets acceleration time between frequency set at 0 to the frequency
set at max.
07
Deceleration
[0.7, 5.0] It sets deceleration time between frequency set at max to the frequency
set at 0.
08
Manual speed....
[0, Par.1] It sets frequency in manual mode
09
Drive status
[0, 105] Encoding number for reading a data set of the drive.
10
Autoclave status
[0, 104] Encoding number for reading a data set of the autoclave
11
Drive Rst Enab
[0, 31]
To allow automatic restart of the drive
12
Drive Rst Time
[0.1, 100] It sets delay time to restart the drive
13
Drive Rst Allow.
[0, 100] It sets number of restarts for the drive
14
Drive Rst Done
[0, 100] It displayed restarts number executed by the drive
15
Autoclave Rst Enab
[0, 7]
To allow automatic restart of the motor
16
Autoc Rst Time
[1, 1000] It sets delay time to restart the motor
17
Autoc Rst Allow.
[0, 100] It sets number of restarts for the motor
18
Autoc Rst Done
[0, 100] It displayed restarts number executed
19
Imon
........
Continuous current taken from the DC Bus
20
Pressure Shock
[0, 1]
It is set to 1 when it measured a pressure more than double of the
system pressure
21
Pid Min Fout....
[2.99,
45.03]
Minimum frequency applied to the motor
22
Min Pressure
[0, 3]
Minimum pressure for the system. For pressure below this value it will
be displayed a malfunctioning. (“Press insuff” / “No water”).
23
Pressure desired
[1, 7.5]
It sets pressure desired
24
SlowAtcRestart
[0, 100] Number of slow restart for autoclave in case of “No Water“ (1 each 50
minutes)
25
NoFluxTime
No flow time
26
Motor Power
[300, 2500] Is the power of the motor (only for XP models)
27
PID KI
[0, 50]
Integral Coefficient for regulator PID
28
Next OpMode
[0, 2]
It sets the operative mode for the next reset. (manual/1 pump
automatic/XP automatic)
29
Present OpMode
[0, 2]
Operative mode (after the reset)
30
Operating SpeedR
[0, Par.1] Applied frequency in manual mode
31
PrsSensor Freq..
Read frequency by sensor of pressure
32
PrsSensor offset [1500, 2500] Read frequency by sensor of pressure with pressure null
33
PrsSensor Hz/Atm [100, 10000] Variation of frequency respect of variation of 1Atm
34
MeasuredPressure
System pressure measured
35
ACMain
Supply voltage for HC
36
LoadCurrent(Amp)
Phase current for the motor
37
Temp.monitor
Measured temperature for power module (internal code for unit of
measurement)
38
Measured Flux
[0, 1023] Measured flow (internal code for unit of measurement)
39
Treshold Flux
[0, 1023] Threshold for minimum flow to indicate no flow state (internal code for
unit of measurement)
40
MaxTimeBrokePipe
[1.0,
1200.0]
Time for entering in state of “Press Insuff”
41
NoWater Time
Display the Time for entering in state of “No water”
42
Max_NoWater_Time
[1.0,
1200.0]
Time for entering in state of “No water”
43
Fout
[0, Par.1] Applied frequency to the motor
44
Vout
Applied voltage to the motor (internal code for unit of measurement)
45
BrokenPipeTime
Display the Time for entering in state of “Press Insuff”
46
Power
Adsorbed power supply by the pump
47
ExtRelayStatus
State of the thermal protections for the external relays (For version with
contactors)
48
MaxCorr (Amps)
[0.45,
Max rms for phase current