![M2I BOX-HMI Series Hardware Manual Download Page 9](http://html1.mh-extra.com/html/m2i/box-hmi-series/box-hmi-series_hardware-manual_3127628009.webp)
Industrial BOX-HMI Hardware Manual
M2I Corporation
11-35, Simin-daero 327beon-gil, Dongan-gu, Anyang-si, Gyeonggi-do 14055, Korea, Tel: +82-70-465-3366, Fax: +82-31-465-3355, www.m2i.co.kr
9 / 16
Transmission Speed
2400,4800,9600,19200,38400,57600,76800, 115200 bps
Data Type
Data Bit
7, 8 bit
Parity Bit
NONE, ODD, EVEN Parity
Stop Bit
1, 2 bit
Modular Jack
DSUB 9pin
5.1.3 COM1 Connector pin number and Signal name
Type
Pin No.
Signal
Direction
Meaning
9Pin Female
1
RDA(RD+)
Input
RS-422/485 Receive Data (+)
2
RD(RxD)
Input
RS-232C Receive Data
3
SD(TxD)
Output
RS-232C Send Data
4
RDB(RD-)
Input
RS-422/485 Receive Data (-)
5
SG
-
Signal Ground
6
SDA(SD+)
Output
RS-422/485 Send Data (+)
7
*1)
Power
-
+5V , 0.2A
8
*2)
GND
-
Power Ground
9
SDB(SD-)
Output
RS-422/485 Send Data (-)
*1, *2)
When need VCC for external equipment, use 7.VCC and 8.VCC GND that output is 0.2A.
5.1.4 COM2 Connector pin number and Signal name
Type
Pin No.
Signal
Direction
Meaning
9Pin Female
1
RDA(RD+)
Input
RS-422/485 Receive Data (+)
2
RD(RxD)
Input
RS-232C Receive Data
3
SD(TxD)
Output
RS-232C Send Data
4
RDB(RD-)
Input
RS-422/485 Receive Data (-)
5
SG
-
Signal Ground
6
SDA(SD+)
Output
RS-422/485 Send Data (+)
7
RTS
Output
RS-232C Send Request Signal
8
CTS
Input
RS-232C Send Available Signal
9
SDB(SD-)
Output
RS-422/485 Send Data (-)
* Be sure to connect the RD and SD to the RS-232C communication line by crossing each other with a Twisted Pair Cable.
Please connect SG directly.
* SG must be connected directly.
*
RS-422/485 communication line must use RDA and RDB as Twisted Pair Cable, SDA and SDB as Twisted Pair
Cable
.
*
Do not use shield wire of communication line as signal ground. It may cause communication failure
.
5.2 Ethernet Communication Specifications
5.2.1 Ethernet
Items
Contents
Ethernet Method
IEEE802.3i/IEEE802.3u, 10BaseT / 100BaseT
Speed
10M / 100Mbps
Communication Method
Base Band
Switching Method
AUTO MDIX