STATUS INDICATOR LED

Power

Run

Error

SD

RD

STATUS

ON

ON

BL

BL

ON

Communicates normally with occasional CRC errors due to noise interference.

ON

ON

BL

BL

ON

Communicates normally but the Baud Rate and/or Station Address switches failed.
Error LED flashes approximately in 0.5 second intervals.

ON

ON

BL

BL

OFF

----

ON

ON

BL

OFF

ON

CRC error found in the received data.  Unable to respond.

ON

ON

BL

OFF

OFF

----

ON

ON

OFF

BL

ON

Normal communication

ON

ON

OFF

BL

OFF

----

ON

ON

OFF

OFF

ON

Unable to receive data addressed to the station.

ON

ON

OFF

OFF

OFF

----

ON

OFF

BL

BL

ON

Performs the interval-timed responses but CRC error found in receiving the refresh data.

ON

OFF

BL

BL

OFF

----

ON

OFF

BL

OFF

ON

CRC error found in the data addressed to the station.

ON

OFF

BL

OFF

OFF

----

ON

OFF

OFF

BL

ON

Link is not started.

ON

OFF

OFF

BL

OFF

----

ON

OFF

OFF

OFF

ON

No data addressed to the station.  Or unable to receive data addressed to the station due to 
noise interference.  (Missing parts of the data sent from the master)

ON

OFF

OFF

OFF

OFF

Unable to receive data due to wire breakdown

ON

OFF

ON

OFF

ON/

OFF

Faulty Baud Rate and/or Station Address setting

OFF

OFF

OFF

OFF

OFF

Power input removed.  Or power supply failure.

OFF = OFF, ON = ON, BL = Blinking

---- = Inconceivable in normal operations (e.g. LED failure)

Summary of Contents for R8-NC3

Page 1: ...ox 12W output current 1 6 A Excitation supply 24V DC 10 operational current 10A ENVIRONMENT Indoor use When heavy dust or metal particles are present in the air install the unit inside proper housing...

Page 2: ...4 3 2 1 0 9 8 7 6 Baud Rate Setting 0 156 kbps 1 625 kbps 2 2 5 Mbps 3 5 Mbps 4 10 Mbps front DIP SW Data Allocation Mode SW1 DATA ALLOCATION MODE SW1 1 ON 2 OFF Cyclic Expansion SW2 CYCLIC EXPANSION...

Page 3: ...ON OFF OFF ON Unable to receive data addressed to the station ON ON OFF OFF OFF ON OFF BL BL ON Performs the interval timed responses but CRC error found in receiving the refresh data ON OFF BL BL OF...

Page 4: ...nce bond the FE1 terminal to ground Caution FE1 terminal is NOT a protective conductor terminal EXC SUPPLY 24V INTERNAL POWER 5V PC CONFIGURATION JACK WIRING INSTRUCTIONS TENSION CLAMP TERMINAL BLOCK...

Page 5: ...utput Data The figure below shows the allocation of data sent from the power network module to the master 0 Module 1 2 3 4 5 6 7 8 9 10 11 12 14 13 15 2 4 6 8 10 12 14 30 31 30 0 15 RWr n 0 Input Data...

Page 6: ...H1 7_CH1 6_CH2 7_CH2 2 4 6 8 10 12 14 31_CH1 31_CH2 62 0 15 RWw n 0 16 m m cyclic expansion setting data areas are available for the R8 NC3 Field input data is set at the module s output data area The...

Page 7: ...t binary data is used for temperature data With C K temperature unit raw data is multiplied by 10 For example 25 5 C is converted into 255 With F temperature unit the integer section of raw data is di...

Reviews: