background image

R8-NC3

5-2-55, Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN
Phone: +81(6)6659-8201 Fax: 

+81(6)6659-8510  E-mail: [email protected]

EM-9726  P. 2 / 7

COMPONENT IDENTIFICATION

FE

SLD

DB

DG

DA

Status Indicator LED

Miniature Jack Connector for Configuration

CC-Link Connector

Connector for

Power Supply and 

Excitation Supply

Function Setting 

DIP SW

8

7

6

5

4

3

2

1

   

FRONT VIEW

   

TOP VIEW

On

Terminator

DIP SW

On

Term

Baud Rate Setting

Rotary SW

Station Address Setting

Rotary SW

Internal Bus Connector

 

FRONT SWITCHES

•   Station Address

Station Address is selected between 1 and 99 in decimal.  
The upper switch determines the tenth place digit, while 
the lower switch does the ones place digit of the address.
(Factory setting: 00)

5

4

3

2

1

0

9

8

7

6

5

4

3

2

1

0

9

8

7

6

Station Address Setting (x1)

Station Address Setting (x10)

•   Baud Rate

Baud Rate is selected with the rotary switch.  Positions 5 
through 9 are unused.  Be sure to select between 0 to 4.
(Factory setting: 0)

5

4

3

2

1

0

9

8

7

6

Baud Rate Setting

0 : 156 kbps
1 : 625 kbps
2 : 2.5 Mbps
3 : 5 Mbps
4 : 10 Mbps

 

FRONT DIP SW

•   Data Allocation Mode

: SW1

DATA ALLOCATION MODE

SW1

1

ON

2 (*)

OFF

•   Cyclic Expansion

: SW2

CYCLIC EXPANSION

SW2

2 (*)

OFF

4

ON

(*) Factory setting
SW3 through SW8 are unused.  Be sure to turn them off.

 

TERMINATOR DIP SW

The termination resistor is connected to the network 
when it is turned on.

 

POWER SUPPLY, EXCITATION SUPPLY CONNECTOR 

ASSIGNMENT

Printed-circuit board connector (Phoenix Contact)

Header: MSTBV2,5/5-GF-5,08AU
Plug component: TFKC2,5/5-STF-5,08AU

  PIN 

ID 

FUNCTION

  No.
  1 

24V 

Power supply 24V DC

  2 

0V 

Power supply 0V DC

  3 

Excitation supply 24V DC

  4 

− 

Excitation supply 0V DC

  5 

FE1  Grounding

1

2

3

4

5

 

CC-LINK CONNECTOR ASSIGNMENT

Printed-circuit board connector (Phoenix Contact)

Header: MC1,5/5-GF-3,5
Plug component: TFMC1,5/5-STF-3,5

  PIN 

ID 

FUNCTION

  No.
  1 

DA 

DA

  2 

DG 

DG

  3 

DB 

DB

  4 

SLD  Shield

  5 

FE 

FE

1

2

3

4

5

 

STATUS INDICATOR LED

ID

COLOR FUNCTION

Power

Green

ON when the internal 5V power is in nor-
mal status.

Run

Green

ON with normal communication

Error

Red

ON when abnormal data is received.

SD

Green

ON with data transmitting

RD

Green

ON with data receiving

Summary of Contents for R8-NC3

Page 1: ...ox 12W output current 1 6 A Excitation supply 24V DC 10 operational current 10A ENVIRONMENT Indoor use When heavy dust or metal particles are present in the air install the unit inside proper housing...

Page 2: ...4 3 2 1 0 9 8 7 6 Baud Rate Setting 0 156 kbps 1 625 kbps 2 2 5 Mbps 3 5 Mbps 4 10 Mbps front DIP SW Data Allocation Mode SW1 DATA ALLOCATION MODE SW1 1 ON 2 OFF Cyclic Expansion SW2 CYCLIC EXPANSION...

Page 3: ...ON OFF OFF ON Unable to receive data addressed to the station ON ON OFF OFF OFF ON OFF BL BL ON Performs the interval timed responses but CRC error found in receiving the refresh data ON OFF BL BL OF...

Page 4: ...nce bond the FE1 terminal to ground Caution FE1 terminal is NOT a protective conductor terminal EXC SUPPLY 24V INTERNAL POWER 5V PC CONFIGURATION JACK WIRING INSTRUCTIONS TENSION CLAMP TERMINAL BLOCK...

Page 5: ...utput Data The figure below shows the allocation of data sent from the power network module to the master 0 Module 1 2 3 4 5 6 7 8 9 10 11 12 14 13 15 2 4 6 8 10 12 14 30 31 30 0 15 RWr n 0 Input Data...

Page 6: ...H1 7_CH1 6_CH2 7_CH2 2 4 6 8 10 12 14 31_CH1 31_CH2 62 0 15 RWw n 0 16 m m cyclic expansion setting data areas are available for the R8 NC3 Field input data is set at the module s output data area The...

Page 7: ...t binary data is used for temperature data With C K temperature unit raw data is multiplied by 10 For example 25 5 C is converted into 255 With F temperature unit the integer section of raw data is di...

Reviews: