R8-DCM16ALK
P. 4 / 5
EM-9747 Rev.2
5-2-55, Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN
Phone: +81(6)6659-8201 Fax: +81(6)6659-8510 E-mail: [email protected]
■
MODULE ADDRESS
Module address can be set with SW1-1 through 1-4 for the
tens, and SW1-5 through 1-8 for the ones place digit.
Address is selected between 0 to 31. (Factory setting: 0)
MODULE ADDRESS
SW1
1
5
2
6
3
7
4
8
0
OFF
OFF
OFF
OFF
1
OFF
OFF
OFF
ON
2
OFF
OFF
ON
OFF
3
OFF
OFF
ON
ON
4
OFF
ON
OFF
OFF
5
OFF
ON
OFF
ON
6
OFF
ON
ON
OFF
7
OFF
ON
ON
ON
8
ON
OFF
OFF
OFF
9
ON
OFF
OFF
ON
■
OPERATING MODE
*Factory setting
• Interlock Communication Logic Reversal
Setting internal communication bus logic.
INTERLOCK COMMUNICATION LOGIC REVERSAL
SW2-1
Interlock function setting off: 1
Interlock function setting on:
normal = 1, interlock = 0
ON
Interlock function setting off: 0 (*)
Interlock function setting on:
normal = 0, interlock = 1
OFF
Caution: 1 and 0 values are validated as logic through internal
communication bus logic.
• Output at The Loss of Communication
Setting for all output.
OUTPUT AT THE LOSS OF COMMUNICATION
SW2-5
Output Hold (*)
(last data correctly rerceived is hold
OFF
Stop output (Output fixed at OFF)
ON
• Terminator DIP SW
TERMINATOR SW
SW2-6
Without (*)
OFF
With
ON
• Configuration Mode
CONFIGURATION MODE
SW2-8
DIP switch setting (*)
OFF
PC Configurator and communicaton
ON
Caution: SW2-2 through 2-4 and 2-7 are unused; be sure to turn
OFF unused channels.
■
FULL INTERLOCK FUNCTION
It is available to apply full interlock function to all outputs
(Do1 through Do16)
FULL INTERLOCK FUNCTION
SW3-1
OFF
OFF
ON (*) (all outputs OFF if input OFF)
ON
Caution: SW3-2 is unused; be sure to turn OFF unused chan
-
nels.
■
INDIVIDUAL INTERLOCK
At output, it is available to apply interlock function to 2
points arbitrary.
• Individual interlock function 1
INDIVIDUAL INTERLOCK 1
SW4-1
SW6, 7 OFF
OFF
SW6, 7 ON (*)
(Input OFF with output OFF)
ON
• Individual interlock function 2, channel
INDIVIDUAL INTERLOCK 1
CHANNEL
SW6
SW7
Ones
Tens
ON
01 through 16
OFF
00, 17 through 99
• Individual interlock function 2
INDIVIDUAL INTERLOCK 2
SW5-1
SW8, 9 OFF
OFF
SW8, 9 ON (*)
(Input OFF with output OFF)
ON
• Individual interlock function 2, channel
INDIVIDUAL INTERLOCK 2
CHANNEL
SW8
SW9
Ones
Tens
ON
01 through 16
OFF
00, 17 through 99
Caution: SW4-2 and 5-2 are unused; be sure to turn OFF un
-
used channels.
■
PC CONFIGURATOR
The following parameters can be set with using PC Configu-
rator Software (model: R8CFG):
• Output at the startup
• Output at the loss of communication
• Common setting (loss of internal bus communication de
-
tection time)
Turn SW2-8 ON to allow programming by the PC Configu
-
rator via the Power / Network Module.
Refer to the users manual of the R8CFG for detailed opera
-
tion of the software program.