background image

R8-DCM16ALK

P. 4 / 5

EM-9747 Rev.2

5-2-55, Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN

Phone: +81(6)6659-8201   Fax: +81(6)6659-8510   E-mail: [email protected]

 MODULE ADDRESS

Module address can be set with SW1-1 through 1-4 for the 
tens,  and SW1-5 through 1-8 for the ones place digit.  
Address is selected between 0 to 31.  (Factory setting: 0)

MODULE ADDRESS

SW1

1
5

2
6

3
7

4
8

0

OFF

OFF

OFF

OFF

1

OFF

OFF

OFF

ON

2

OFF

OFF

ON

OFF

3

OFF

OFF

ON

ON

4

OFF

ON

OFF

OFF

5

OFF

ON

OFF

ON

6

OFF

ON

ON

OFF

7

OFF

ON

ON

ON

8

ON

OFF

OFF

OFF

9

ON

OFF

OFF

ON

 OPERATING MODE

*Factory setting

• Interlock Communication Logic Reversal

Setting internal communication bus logic.

INTERLOCK COMMUNICATION LOGIC REVERSAL

SW2-1

Interlock function setting off: 1
Interlock function setting on: 
normal = 1, interlock = 0 

ON

Interlock function setting off: 0 (*)
Interlock function setting on: 
normal = 0, interlock = 1 

OFF

Caution:  1 and 0 values are validated as logic through internal 

communication bus logic. 

• Output at The Loss of Communication

Setting for all output.

OUTPUT AT THE LOSS OF COMMUNICATION

SW2-5

Output Hold (*) 

(last data correctly rerceived is hold

OFF

Stop output (Output fixed at OFF)

ON

• Terminator DIP SW

TERMINATOR SW

SW2-6

Without (*)

OFF

With

ON

• Configuration Mode

CONFIGURATION MODE

SW2-8

DIP switch setting (*)

OFF

PC Configurator and communicaton

ON

Caution:  SW2-2 through 2-4 and 2-7 are unused; be sure to turn 

OFF unused channels.

 FULL INTERLOCK FUNCTION

It is available to apply full interlock function to all outputs 
(Do1 through Do16)

FULL INTERLOCK FUNCTION

SW3-1

OFF

OFF

ON (*) (all outputs OFF if input OFF)

ON

Caution:  SW3-2 is unused; be sure to turn OFF unused chan

-

nels.

 INDIVIDUAL INTERLOCK

At  output,  it  is  available  to  apply  interlock  function  to  2 

points arbitrary.

• Individual interlock function 1

INDIVIDUAL INTERLOCK 1

SW4-1

SW6, 7  OFF

OFF

SW6, 7  ON (*) 
(Input OFF with output OFF)

ON

• Individual interlock function 2, channel

INDIVIDUAL INTERLOCK 1 

CHANNEL

SW6

SW7

Ones

Tens

ON

01 through 16

OFF

00, 17 through 99

• Individual interlock function 2

INDIVIDUAL INTERLOCK 2

SW5-1

SW8, 9  OFF

OFF

SW8, 9  ON (*) 
(Input OFF with output OFF)

ON

• Individual interlock function 2, channel

INDIVIDUAL INTERLOCK 2 

CHANNEL

SW8

SW9

Ones

Tens

ON

01 through 16

OFF

00, 17 through 99

Caution:  SW4-2 and 5-2 are unused; be sure to turn OFF un

-

used channels.

 PC CONFIGURATOR

The following parameters can be set with using PC Configu-

rator Software (model: R8CFG):
• Output at the startup
• Output at the loss of communication
• Common setting (loss of internal bus communication de

-

tection time)

Turn SW2-8 ON to allow programming by the PC Configu

-

rator  via  the  Power  /  Network  Module.

Refer to the users manual of the R8CFG for detailed opera

-

tion of the software program.