PC CONFIGURATOR
With configurator software, settings shown below are available.
Refer to the software manual of R8CFG for detailed operation.
■
CHANNEL INDIVIDUAL SETTING
PARAMETER
AVAILABLE RANGE
DEFAULT SETTING
Sensor type
CLSE-R5
CLSE-05
CLSE-10
CLSE-20
CLSE-40
CLSE-60
CLSE-R5
Lower range value
Depends on sensor type
0.000
Upper range value
Depends on sensor type
0.000
Fine zero adjustment
-320.00 to +320.00 (%)
0.00 (%)
Fine gain adjustment
-3.2000 to +3.2000
1.0000
Scaled range Zero
-32000 to +32000
0
Scaled range Span
-32000 to +32000
10000
Low-end cutout
0.0 to 5.0 (%)
1.0 (%)
■
CHANNEL BATCH SETTING
PARAMETER
AVAILABLE RANGE
DEFAULT SETTING
Loss of internal bus communication detection time
0.0 to 99.9 (sec.)
1.0 (sec.)
Configuration mode
DIP switch (OFF)
PC (ON)
DIP switch (OFF)
Note: Turn SW4-8 ON to allow programming by the PC Configurator via the Power/Network Module.
TERMINAL CONNECTIONS
Connect the unit as in the diagram below.
■
EXTERNAL DIMENSIONS unit: mm (inch)