![M-system R8-CT4E Instruction Manual Download Page 3](http://html1.mh-extra.com/html/m-system/r8-ct4e/r8-ct4e_instruction-manual_3263621003.webp)
R8-CT4E
5-2-55, Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN
Phone: +81(6)6659-8201 Fax: +81(6)6659-8510 E-mail: [email protected]
EM-9794 Rev.1 P. 3 / 5
COMPONENT IDENTIFICATION
FRONT VIEW
SIDE VIEW
CT1
RUN
CT2
CT3
CT4
5
4
3
2
1
0
9
8
7
6
5
4
3
2
1
0
9
8
7
6
Status Indicator LED
Input Status Indicator LED
Internal Bus Connector
Input Connectors
Module Address Setting
Rotary SW
SW1
x10
x1
SW2
5
4
3
2
1
0
9
8
7
6
5
4
3
2
1
0
9
8
7
6
CARD ADD.
Terminator DIP SW
SW3
Term
On
Function Setting
DIP SW
1 2 3 4 5 6 7 8
SW4
On
■
INDICATOR LED
LED
OPERATION
FUNCTION
Status
OFF
Stopping
Green ON
Valid host communication
Green Blinking
Reading/writing configuration
Red ON
Setting error
Red Blinking
Parameter error
Input
Status
OFF
Input data in the range
Red Blinking
Input data out of range
■
INPUT CONNECTOR ASSIGNMENT
PIN
ID
FUNCTION
No.
1
k
Input
2
NC
No connection
3
NC
No connection
4
l
Input
1
2
3
4
■
MODULE ADDRESS
The left switch determines the tenth place digit, while the
right switch does the ones place digit of the address.
Address is selected between 0 to 30.
(Factory setting: 0)
Module Address Setting (x10)
Module Address Setting (x1)
5
4
3
2
1
0
9
8
7
6
5
4
3
2
1
0
9
8
7
6
■
OPERATING MODE
(*) Factory setting
• Clamp-on Current Sensor Setting
Same range for all channels. Use PC Configurator to set
independent ranges per channel.
CLUMP-ON CURRENT SENSOR
SW4
1
2
3
CLSE-R5 : 0 − 5A AC (*)
OFF
OFF
OFF
CLSE-05 : 0 − 50A AC
ON
OFF
OFF
CLSE-10 : 0 − 100A AC
OFF
ON
OFF
CLSE-20 : 0 − 200A AC
ON
ON
OFF
CLSE-40 : 0 − 400A AC
OFF
OFF
ON
CLSE-60 : 0 − 600A AC
ON
OFF
ON
• Configuration Mode
CONFIGURATION MODE
SW4-8
DIP switch setting (*)
OFF
PC Configurator and communication
ON
Note: Be sure to set unused SW4-4 through 4-7 to OFF.
■
TERMINATOR DIP SW
TERMINATOR SW
SW3
Without (*)
OFF
With
ON