R7M-DC16A

P. 5 / 7

EM-7803-G Rev.5

5-2-55, Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN
Phone: +81(6)6659-8201 Fax: 

+81(6)6659-8510  E-mail: [email protected]

Use (e.g.) a shield cover 
when noise leaks through 
the opening.

To external apparatus

Keep the opening

for cabling as small as

possible.

Install an electromagnetically
shielded gasket when 
noise leaks through 
the opening.

Shielding is strengthened 
by using an electro-
magnetically shielded 
control panel.

By connecting the
internal panel plate 
and the panel cover with 
an earth strap, grounding 
may be strengthened and
EMC may be improved.

Ground the control panel 

at low impedance using 

 (e.g.) braided wires.

Keep the opening for 

ventilation as small as

posible.

Attach an electro-
magnetically shielded
filter when noise leaks 
through the opening.

Install the R7M Series inside

a control panel.

Attachment part of earth

clamp should be fixed with 

screw in conduction with the

internal panel plate.

• Points of cautions applicable when installing the R7M Series

Summary of Contents for R7M-DC16A

Page 1: ...e supplied by a Class 2 power sup ply CONFORMITY WITH EU DIRECTIVES The equipment must be mounted inside the instrument panel of a metal enclosure The actual installation environments such as panel co...

Page 2: ...1 Factory setting 00 Node Address Setting x10 BAUD RATE Baud Rate is selected with the rotary switch 5 4 3 2 1 0 9 8 7 6 Baud Rate Setting 0 38 4 kbps factory setting 1 19 2 kbps 2 9600 bps 3 4800 bps...

Page 3: ...X8 5 X6 4 X4 3 X2 2 4 7 6 3 2 5 1 X0 0V 24V DC FG SLD DG DB DA COM COM 10 Input Connection Examples PNP Connection NPN Connection EXTENSION CONNECTOR In order to improve EMC performance bond the FG te...

Page 4: ...o EMC Direc tive while it is installed in the control panel Warning and cautions when installing R7M are stated below Use control panels with an internal panel plate both made of metal when installing...

Page 5: ...using an electro magnetically shielded control panel By connecting the internal panel plate and the panel cover with an earth strap grounding may be strengthened and EMC may be improved Ground the co...

Page 6: ...Additional measures may be taken depending upon actual installation sites These points of cautions are illustrated in the next page Keep cables as short as possible It prevents noise emissions from th...

Page 7: ...m is not effective Points of cautions applicable when wiring the R7M Series To external apparatus Keep the cable as short as possible To external apparatus Shielded Cable Earth Clamp Remove a part of...