R7M-CT4E

P. 2 / 7

EM-7803-R Rev.3

5-2-55, Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN
Phone: +81(6)6659-8201 Fax: 

+81(6)6659-8510  E-mail: [email protected]

COMPONENT IDENTIFICATION

5

4

3

2 1 0 9

8

7

6

5

4

3

2 1 0 9

8

7

6

5

4

3

2 1 0 9

8

7

6

ERR

RD

RUN

SD

PWR

X10

X1

NODE ADD.

B.RATE

CNFG.

1

2

3

4

5

6

7

8

4

5

6

7

1

2

3

10 11 12 13

2

3

4

1

15 16 17 18

7

8

9

6

14

5

(A)  Status Indicator LED
(B)  Node Address Setting Rotary SW
(C)  Baud Rate Setting Rotary SW
(D)  Operating Mode Setting DIP SW (SW1)
(E)  PC Configurator Jack
(F)  Modbus, Power Supply Terminals
(G)  Input Terminals

(A)

(F)

(G)

(B)

(C)

(D)

(E)

 

STATUS INDICATOR LED

ID

COLOR FUNCTION

PWR

Red

Turns on when the internal 5V is supplied 
ormally.

RUN

Red

Turns on when the data is received nor-
mally.

ERR

Red

Turns on when the received data is abnor-
mal. Blinks when setting is abnormal.

SD

Red

Turns on when the module is transmitting.

RD

Red

Turns on when the module is receiving.

 

NODE ADDRESS

Node Address is selected between 1 and 99 in decimal.  The 
left switch determines the tenth place digit, while the right 
switch does the ones place digit of the address.

5

4

3

2

1

0

9

8

7

6

5

4

3

2

1

0

9

8

7

6

Node Address Setting (x1)

Factory setting : 00

Node Address Setting (x10)

 

BAUD RATE

Baud Rate is selected with the rotary switch.

5

4

3

2

1

0

9

8

7

6

Baud Rate Setting

0 : 38.4 kbps (factory setting)
1 : 19.2 kbps
2 : 9600 bps
3 : 4800 bps

 

EXTENSION MODULE

Combinations with all extension modules are selectable.

 

OPERATING MODE

(*) Factory setting

•   Extension (SW1-1, 1-2)

SW1-1

SW1-2 EXTENSION

OFF

OFF

No extension (*)

ON

OFF

Discrete input, 8 or 16 points

OFF

ON

Discrete output, 8 or 16 points

•   Conversion Rate / Accuracy (SW1-3, 1-4)

SW1-3

SW1-4 CONVERSION RATE / ACCURACY

OFF

OFF

80 msec. / ±0.5% (*)

ON

OFF

40 msec. / ±0.5%

OFF

ON

20 msec. / ±1.0%

ON

ON

10 msec. / ±2.0%

•   Input Range (SW1-5, 1-6, 1-7, 1-8)

SW1-5

SW1-6

SW1-7

SW1-8 INPUT RANGE

OFF

OFF

OFF

OFF

CLSE-60 (*)

ON

OFF

OFF

OFF

CLSE-40

OFF

ON

OFF

OFF

CLSE-20

ON

ON

OFF

OFF

CLSE-10

OFF

OFF

ON

OFF

CLSE-05

ON

OFF

ON

OFF

CLSE-R5

ON

ON

ON

ON

PC Configurator setting

 

POWER SUPPLY, MODBUS TERMINAL ASSIGNMENT

4

DA

5

DG

6

+24V

1

DB

2

SLD

3

FG

7

0V

NO.

ID

FUNCTION, NOTES

1

DB

----

2

SLD

Shield

3

FG

FG

4

DA

----

5

DG

----

6

+24V

Power input (24V DC)

7

0V

Power input (0V)

 

INPUT TERMINAL ASSIGNMENT

10

K0

11

L0

12

K1

1

NC

2

NC

3

NC

13

L1

4

NC

14

NC

5

NC

15

K2

6

NC

16

L2

7

NC

17

K3

8

NC

9

NC

18

L3

NO.

ID

FUNCTION

NO.

ID

FUNCTION

1

NC

No connection

10

K0

AC current K0

2

NC

No connection

11

L0

AC current L0

3

NC

No connection

12

K1

AC current K1

4

NC

No connection

13

L1

AC current L1

5

NC

No connection

14

NC

No connection

6

NC

No connection

15

K2

AC current K2

7

NC

No connection

16

L2

AC current L2

8

NC

No connection

17

K3

AC current K3

9

NC

No connection

18

L3

AC current L3

Summary of Contents for R7M-CT4E

Page 1: ...nts in regard to the whole system and employ additional protective measures to ensure CE conformity Install lightning surge protectors for those wires connect ed to remote locations Choose a surge pro...

Page 2: ...otary switch 5 4 3 2 1 0 9 8 7 6 Baud Rate Setting 0 38 4 kbps factory setting 1 19 2 kbps 2 9600 bps 3 4800 bps EXTENSION MODULE Combinations with all extension modules are selectable OPERATING MODE...

Page 3: ...2 K3 L3 INPUT 3 12 13 15 16 17 18 Input Connection Example Kn Ln LOAD SOURCE k l CLAMP ON SENSOR EXTENSION CONNECTOR In order to improve EMC performance bond the FG terminal to ground Caution FG term...

Page 4: ...EMC Direc tive while it is installed in the control panel Warning and cautions when installing R7M are stated below Use control panels with an internal panel plate both made of metal when installing...

Page 5: ...using an electro magnetically shielded control panel By connecting the internal panel plate and the panel cover with an earth strap grounding may be strengthened and EMC may be improved Ground the con...

Page 6: ...dditional measures may be taken depending upon actual installation sites These points of cautions are illustrated in the next page Keep cables as short as possible It prevents noise emissions from the...

Page 7: ...m is not effective Points of cautions applicable when wiring the R7M Series To external apparatus Keep the cable as short as possible To external apparatus Shielded Cable Earth Clamp Remove a part of...